Loading…
Loading…
Tender Value
₹44,379
EMD Value
₹1,109
Closing Date
12 Jun 2026, 6:00 pm5d left
AEE
AEE,PWD,Ele.SDN,Tvpm
GENERAL-SITC of AC unit at UTM Machine Room KHRI Kazhakuttam-Voltage stabilizer work-General Electrical Work
2026_PWD_844647_3
ESDT/ET-284/2025-26
Open Tender
Electrical Works
90 days
PWD Electrical Sub Division, TVPM
Please refer tender documents
6 documents required · 6 mandatory
₹335
Yes
₹1,109
Yes
6 Jun 2026
6 Jun 2026
15 Jun 2026
6 Jun 2026
12 Jun 2026
6 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1Voltage stebilizer | ||||||
| 1.001 | OD274640/2025-2026:Supply, installation, testing and commissioning of 3-150 kVA SERVO CONTROLLED VOLTAGE STABILISER 3 Phase Unbalanced Air cooled Microprocessor controlled
Digital Voltage, Current & Frequency display Comprehensive protection Input voltage range (V L-L) *
Output voltage (V L-L) *
3 Phase Unbalanced Air cooled
3-150
Air
310-480 / 340-480 / 360-460
415 (380V/400V - optional)
3 Phase Unbalanced Oil cooled
3-2000
Oil
Output Voltage Regulation
Input frequency range
Efficiency
Effect of Load Power Factor
Waveform Distortion
Type of Servo Control
Servo Motor Drive
Under/ Over Voltage cutoff *
Overload cutoff
Short circuit protection
Single phasing prevention
Phase Reversal Trip
Stabiliser bypass
Transient Suppression
Emergency Off Switch
Frequency cut off protection
Input High Voltage Trip
Resetting mode
Display Type
Parameters displayed
Parameters displayed
LED indications
Input / Output Terminations
1% of nominal output voltage
47Hz ? 53Hz
>97%
Nil
Nil
Micro Controller based True RMS sensing and correction
Triac based drive for AC Step Synchronous motor
Electronic cutoff circuit with graded time delay, set @ +5% / -10% of nominal output voltage
CT based Electronic cutoff circuit with graded time delay set @ 110% of rated full load current
MCB / MCCB provided upto 100 kVA. Above 100 kVA HRC fuse (MCCB optional)
Provided
Provided
Provided up to 50 kVA 3-phase; Optional > 50 kVA
Spike Suppression through MOV is provided (Surge Arrestor is optional)
Provided
Optional
Optional
Manual / Auto option provided with programmable time delay
2 Line LCD Panel
Input & Output Voltages (Line & Phase), Output Currents & Frequency
Fault Annunciation, Event Log
Bolted Terminals up to 100kVA,Busbar 125kVA and above
* Custom settings or ranges possible. | - | each | 44,378.73 | - | BI01010001010000000000000515BI0100001114 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
BOQ_1444301.xls
BOQ • 0.30 MB
nit.pdf
Tender Documents • 0.02 MB
mom.pdf
Tender Documents • 0.19 MB
sbd.pdf
Tender Documents • 1.63 MB
sc.pdf
Tender Documents • 0.15 MB
Download all tender documents and submit your bid