| Sl No | Description | Qty | Unit | FI-TEC INFRA SOLUTIONS PRIVATE LIMITED H1 |
|---|---|---|---|---|
| 1.00Supply, installation, Testing and commissioning of One (1) no. 50 KVA 415V, 3 phase, 50Hz Diesel Generator set with acoustic enclosure &AMF Control PanelatIMG Regional Centre, Kozhikode | ||||
| 1.01 | OD23539/2023-2024 - SITC of 50 kVA Diesel Generator set complete with integral acoustic enclosure as per existing CPCB II norms and as per technical details given below 1. Engine a) Make of Engine - Cummins/ Kirlosker/Volvo/Catterpiller b) Type of Engine - Diesel Engine c) No. of Cylinders- 4. d) Method of Cooling – Liquid cooled with radiator. e) Aspiration -Turbo charged, charge air cooled. f) Design - Suitable for generating set operating. g) Output- As per manufactures standards. 2. Standard accessories with Diesel Engine. a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Mechanical governor g) Fuel filter h) Exhaust silencer i) Exhaust Muffler j) Lubricating oil filter. k) Battery Charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button. b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter. e) Battery charging Ammeter. 4. Safety Controls for Engine. a) Trip for low lubricating oil pressure. b) Trip for high water temperature. 5.Fuel pipe: Oil resistance flexible hoses of 20mm dia or nearest size MS pipe as per manufacturer's standard, 6 Brush less Alternator a) Make - Stamford/Kirlosker/KEL/LS b) Type - Self exited and self-regulated, brush less c) Capacity – 50 kVA/ 40 K W @ 0.8PF d) System of Voltage - 3 phase, 415 V, 4 wire system. e) Speed - 1500 rpm f) Voltage regulation band - +/-2.5% of rated voltage g) Frequency - 50 Hz h) Insulation - Class -F/H .The Alternator should confirm to IS 4722. Routine tests as per relevant ISS shall be conducted and test reports of the same shall be furnished at the time of delivery.Operation and service manual, spares and tools shall be provided. . 7.Fuel Tank Suitable size built in type integrated with the acoustic enclosure. Fuel connection shall be done as per standards.7. Battery. Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 8. Automatic Battery charger. Push button switch for ON/OFF - 1 set. Metallic DNB - 1No Solid state phase indication lamp for supply ON/OFF with HRC protection Supply of HSD for load test run, The standard Electric control panel integrated with acoustic enclosure comprising of the following. a) 125A,30/35KA,(63-80A rating) 4Pole MCCB having adjustable setting, b) Digital Multi function meter with accuracy class 1 to read parameters such as KW, KVA, PF, voltage, Current Frequency,Runing hour counter etc: c) Digital type single function KWH meter with accuracy class 1, d) LED type phase indication Lamp for indicating the presence of supply on all phases,10.Exhaust Piping ,Exhaust Piping shall be vent to the top of the nearest tallest building if required . If the pipe cannot be clamped/fixed to the building or any other structure of permanent nature necessary fabricated structures using
channel section or angle iron sections of adequate mechanical strength, duly painted with 2 coats of Heat retardant aluminium paint shall be provided for the support of the exhaust pipe. (Additional piping will be measured excluding the standard length of pipe supplied by the manufacturer.),
The DG set shall be tested as per relevant IS standards. Block load testing shall also be conducted. Droop characteristics shall also be tested and adjusted for enabling parallel operation. The load required for testing shall be made available at site by the selected agency at his own expenses.
The DG shall be guaranteed for 3 years from the date of commissioning .Any of the spares /components which are found to be defective during this period shall be replaced immediately free of cost | 1 | Each | 1,41,102 ₹9,25,002 Lowest |
| 1.02 | 90.17.7.6 - Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80 mm dia | 15 | Metre | 7,581.6 ₹49,701.6 Lowest |
| 1.03 | OD23540/2023-2024 Providing Aluminum Claddings for DG Exhaust pipe | 8 | Meter | 3,032.64 ₹19,880.64 Lowest |
| 1.04 | OD23541/2023-2024 Supply of High speed diesel (HSD) for fuel tank of DG set including conveyance, loading and unloading | 75 | Litre | 1,944 ₹12,744 Lowest |
| 1.05 | Supply and installation AMF panel suitable 50KVA D.G fabricated from CRCA sheet as per IS 8623 approved design including bus bar relay and contactor/MCCB indication lamp push button Auto/ Manual Selector switch etc as required incluing 6 pair copper control cable from generator to panel Board | 1 | No | 31,590 ₹2,07,090 Lowest |
| 1.06 | 90.16.1.6 Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG) | 50 | Metre | 5,054.4 ₹33,134.4 Lowest |
| 1.07 | 90.16.5.6 Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.6. mm ( 4 SWG) | 14 | Each | 280.1 ₹1,836.2 Lowest |
| 1.08 | 90.12.7.29 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core70 sq mm with factory made clamp | 10 | Metre | 1,642.68 ₹10,768.68 Lowest |
| 1.09 | 90.12.39.21 Supply & laying of one number PVC insulated and PVC sheathed armoured Auminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 70 sq mm | 80 | Metre | 13,141.44 ₹86,149.44 Lowest |
Tender Value
Refer Docs
EMD Value
₹25,000
Closing Date
28 May 2026, 5:00 pmClosed
Secretary
Secretary IMG Vikas Bhavan PO Thiruvananthapuram
Supply, installation, Testing and commissioning of One no 50 KVA 415V phase 50Hz Diesel Generator set with acoustic enclosure AMF Control Panel at IMG Regional Centre Kozhikode
2026_IMG_851252_1
63/2026/IMG
Open Tender
Loading Works/ Services
Supply and Service
30 days
IMG Kozhikode
Please refer Tender documents.
8 documents required · 8 mandatory
₹2,000
Yes
₹25,000
Yes
25 Jul 2026
15 May 2026
30 May 2026
15 May 2026
28 May 2026
15 May 2026
15 May 2026 - 18 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, installation, Testing and commissioning of One (1) no. 50 KVA 415V, 3 phase, 50Hz Diesel Generator set with acoustic enclosure &AMF Control PanelatIMG Regional Centre, Kozhikode | |||||
| 1.01 | OD23539/2023-2024 - SITC of 50 kVA Diesel Generator set complete with integral acoustic enclosure as per existing CPCB II norms and as per technical details given below 1. Engine a) Make of Engine - Cummins/ Kirlosker/Volvo/Catterpiller b) Type of Engine - Diesel Engine c) No. of Cylinders- 4. d) Method of Cooling – Liquid cooled with radiator. e) Aspiration -Turbo charged, charge air cooled. f) Design - Suitable for generating set operating. g) Output- As per manufactures standards. 2. Standard accessories with Diesel Engine. a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Mechanical governor g) Fuel filter h) Exhaust silencer i) Exhaust Muffler j) Lubricating oil filter. k) Battery Charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button. b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter. e) Battery charging Ammeter. 4. Safety Controls for Engine. a) Trip for low lubricating oil pressure. b) Trip for high water temperature. 5.Fuel pipe: Oil resistance flexible hoses of 20mm dia or nearest size MS pipe as per manufacturer's standard, 6 Brush less Alternator a) Make - Stamford/Kirlosker/KEL/LS b) Type - Self exited and self-regulated, brush less c) Capacity – 50 kVA/ 40 K W @ 0.8PF d) System of Voltage - 3 phase, 415 V, 4 wire system. e) Speed - 1500 rpm f) Voltage regulation band - +/-2.5% of rated voltage g) Frequency - 50 Hz h) Insulation - Class -F/H .The Alternator should confirm to IS 4722. Routine tests as per relevant ISS shall be conducted and test reports of the same shall be furnished at the time of delivery.Operation and service manual, spares and tools shall be provided. . 7.Fuel Tank Suitable size built in type integrated with the acoustic enclosure. Fuel connection shall be done as per standards.7. Battery. Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 8. Automatic Battery charger. Push button switch for ON/OFF - 1 set. Metallic DNB - 1No Solid state phase indication lamp for supply ON/OFF with HRC protection Supply of HSD for load test run, The standard Electric control panel integrated with acoustic enclosure comprising of the following. a) 125A,30/35KA,(63-80A rating) 4Pole MCCB having adjustable setting, b) Digital Multi function meter with accuracy class 1 to read parameters such as KW, KVA, PF, voltage, Current Frequency,Runing hour counter etc: c) Digital type single function KWH meter with accuracy class 1, d) LED type phase indication Lamp for indicating the presence of supply on all phases,10.Exhaust Piping ,Exhaust Piping shall be vent to the top of the nearest tallest building if required . If the pipe cannot be clamped/fixed to the building or any other structure of permanent nature necessary fabricated structures using
channel section or angle iron sections of adequate mechanical strength, duly painted with 2 coats of Heat retardant aluminium paint shall be provided for the support of the exhaust pipe. (Additional piping will be measured excluding the standard length of pipe supplied by the manufacturer.),
The DG set shall be tested as per relevant IS standards. Block load testing shall also be conducted. Droop characteristics shall also be tested and adjusted for enabling parallel operation. The load required for testing shall be made available at site by the selected agency at his own expenses.
The DG shall be guaranteed for 3 years from the date of commissioning .Any of the spares /components which are found to be defective during this period shall be replaced immediately free of cost | 1 | Each | - | - |
| 1.02 | 90.17.7.6 - Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80 mm dia | - | Metre | - | - |
| 1.03 | OD23540/2023-2024 Providing Aluminum Claddings for DG Exhaust pipe | - | Meter | - | - |
| 1.04 | OD23541/2023-2024 Supply of High speed diesel (HSD) for fuel tank of DG set including conveyance, loading and unloading | - | Litre | - | - |
| 1.05 | Supply and installation AMF panel suitable 50KVA D.G fabricated from CRCA sheet as per IS 8623 approved design including bus bar relay and contactor/MCCB indication lamp push button Auto/ Manual Selector switch etc as required incluing 6 pair copper control cable from generator to panel Board | - | No | - | - |
| 1.06 | 90.16.1.6 Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG) | - | Metre | - | - |
| 1.07 | 90.16.5.6 Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.6. mm ( 4 SWG) | - | Each | - | - |
| 1.08 | 90.12.7.29 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core70 sq mm with factory made clamp | - | Metre | - | - |
| 1.09 | 90.12.39.21 Supply & laying of one number PVC insulated and PVC sheathed armoured Auminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 70 sq mm | - | Metre | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.66 MB
BOQ_1438307.xls
BOQ • 0.29 MB
rfpnew.pdf
Tender Documents • 0.76 MB
datecorrigendum.pdf
PDF • 0.02 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .