Elementary dilapidated building Upper Primary at BMS Dangerpora B.W.O electric work
2026_PWDJK_305302_1
NIT No.312/2025-26 Dt/05/03/2026
Open Tender
Electrical Works
Percentage
BMS Dangerpora
Please refer Tender documents.
4 documents required · 4 mandatory
₹200
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹4,322
5 Mar 2026
5 Mar 2026
14 Mar 2026
5 Mar 2026
13 Mar 2026
5 Mar 2026
Wiring for light point / exhaust fan point/ceiling fan point with (P+N) 2X1.5 sq.mm FRLS-H ( Polycab/Havells/Finolex/Anchor /eqt make as approved by site engineer),PVC insulated copper conductor single core cable in surface / recessed Conduits (Anchor/polycab/Ravindra/equivalent make as approved by site engineer) , with 6Amp .modular switch (Anchor roma urban/legrand/SSK NV/equivalent make as approved by site engineer), modular plate, cover in front and suitable GI box etc of approved quality and make ISO/IEC Certified (quality of wire shall be approved before execution of wok by SITE In-charge Engineer strictly as required) job including cost of Circuit Wire in 1.5Sqmm Multi strand Copper wire from Switch board to D.B complete inculding of Conduits .
Supply and fixing of 6 amp/250 V A.C fan dimmer step type 2 module with cover plate Anchor Roma plus/SSK Legrand/ equivalent make as directed by engineer incharge.
Wiring for 6Amp Plug with(P+N+E) 3 x 2.5 sq.mm FRLS PVC , Polycab/ Havells/ Finolex/ Anchor / eqt make as approved by site ) Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit complete including Conduits.
Wiring for Power Plug with (P+N+E) 3 x 4 sq.mm FRLS-H Polycab / Havells /Finolex/ Anchor/ eqt make as approved by site engineer)PVCInsulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Anchor/ polycab/ Ravindra/equivalent make as approved by site engineer) suitable GI box etc as required .
Wiring for sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ Recessed medium class PVC conduit as required. (Wire shall be approved before execution of work by SITE in charge engineer strictly)
2x10 sq. mm + 1x10 sq. mm (Phase+N+E) power point sub main in one run from main panel to distribution boards ( Havells/ Finolex/ Anchor/ eq. make)
Supply installation,testing and commissioning of Hylum make bakalite sheets of approved quality ISI specification fixed with secrews of required sizes at existing inspection boxes complete job.
Supplying and fixing of 6 to 16 amp Rating ,single pole, *C* Curve MCB Miniature Circuit Breaker Legrand /Havells or L&T / Schneider/ABB/siemens/ eq. make to be approved by EIC
Supply installation ,testing and commissioning of following rating, Double pole, (P +N) 240 V, C* Curve MCB of Legrand/ Havells//L&T/Schiendar /ABB/Eq. make.
32 Amp. Legrand /Havells or L&T /Schneider/ABB/Siemens or eq. make to be approved by EIC
40Amp. Legrand /Havells or L&T /Schneider/ABB/Siemens or eq. make to be approved by EIC
63Amp. Legrand /Havells or L&T /Schneider/ABB/ Siemens or eq. make to be approved by EIC
Supplying and fixing following way, Triple pole and neutral sheet steel, MCB distribution board,( Havell/ legrand/ Shinider/SSK/ eq. make to be approved by EIC) 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator)
6 way, Double door
ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER Rod EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value .Supplying, Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 2OMM Wide copper strip as required /8No.copper bear wire in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through DWC High Density Poly ethylene Pipe having Corrugation complete job
Supply installation testing and commissioning of 18 W + LED Surface Mounted Panel light luminary fitting round shape with minimum system lumen efficency of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India authorised lab . The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years ,which includes replacement of fixtures of Philips / Havel's / Wipro or Jaquar or eq. make to be approved by EIC
Supply, Installation, Testing and Commissioning of 1200 mm sweep, ceiling fan with 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, etc. complete as required. USHA/Havells/Polycab/ Anchor or eq. make to be approved by EIC.
Supply, laying, Connecting and Commissioning of 35 sq mm 2 core XLPE/PVC insulated and steel armored 1.1 KV grade Aluminum Cable of Havel’s / eq. make with required size of thimbles dully crimped with hydraulic crimping tool including p/ fixing of saddles /clips with making of connection and partially to be laid underground through DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refilling the Trench
Supply, Laying, testing and commissioning of 100 Amp double pole MCB of Havells/Legrand/ABB/L&T or eq. make complete with connections
Supply installation testing and commissioning of 15/16 amp madular socket out let and 15/16 amp madular switch with modular plate and cover plate in box recessed in walla/ complete with refacing of walls sand and cement of existing holes as per ratio1;2;4 ISO/IEC certified of Havells/ Legrand/ Anchor / Schneidar/ L&T or eq. make to be approved by EIC shall be approved before execution of work.
Supply installation testing and commissioning of 6 pin5/6 amp modular 2No.Socket out let and modular 2No.switch with madular plate and madular cover in frunt with box recessed in walls complete with refacing of walls with sand and cement of existing holes as per ratio of 1;2;4. ISO/IFC certified of Havells/ Legrand /Anchor/Schniedar /L&T or eq. make to be approved by EIC shall be approved befor execution of work.
Supply and fixing of 6 amp/250 V A.C ceiling rose with adequate length 0.75 sq. mm PVC multistrand copper wire of approved quality FRLSH for connection of exhaust and celing fans of first floor of building complete job.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.09 MB
BOQ_991598.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .