Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹12.2 LAccepted-AOC HOUSE NO1201 NEAR HANUMAN MANDIR AT POST SHEL PIMPALGAON TAL KHED DIST PUNE PIN 410 501 | PALGHAR | MAHARASHTRA | 410501 | L-1 | Accepted-AOC AOC | |
| 2 | L-2₹12.4 L+₹28,047 (2.31%)Rejected-Finance | L-2 | Rejected-Finance Other than lowest bidder | |
| 3 | L-3₹14.6 L+₹2.4 L (19.7%)Rejected-Finance NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L-3 | Rejected-Finance Other than lowest bidder |
Tender Value
₹12.9 L
EMD Value
₹26,000
Closing Date
19 Feb 2024, 6:00 pmClosed
GE (AF) Naliya No. 1
GE AIR FORCE STATION NALIYA NO 01
REPAIR/MAINT OF FIRE ALARM SYSTEM OF NALIYA AND MOTHALA AF STATION UNDER GE AF NALIYA
2023_MES_634542_3
8950/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Naliya
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (AF) Naliya No. 1
₹26,000
Yes
8 Mar 2024
30 Jan 2024
21 Feb 2024
30 Jan 2024
19 Feb 2024
5 Feb 2024
Amount
Supply, Installation, Testing & Commissioning of SFS1-CPU card of EST3x fire alarm panel in repairs with below specifications: Voltage 24 VDC, Current: Standby 115 mA at 24 VDC Alarm 115 mA at 24 VDC Relay outputs: Quantity 3 (alarm, supervisory, and trouble) UL type Common Contact arrangement Form C Rating 30 VDC at 1 A resistive AUX power outputs: Quantity 2 Voltage 24 VDC, resettable or continuous Current 1.0 A each circuit, 1.0 A total Data network (RS-485) Nodes 2 to 64 (requires optional network card) Performance class Class A or Class B Wire type Twisted pair, 6 twists per foot, min. Circuit length 5,000 ft. (1,524 m) between any three panels Circuit resistance 90 Ω, max. Circuit capacitance 0.3 μF, max. Serial Port (RS-232) Annunciator port (RS-485) Performance class Class B and Redundant Class B Baud rate 9600 and 38400 Wire type Twisted pair, 6 twists per foot, min. Circuit length 4,000 ft. (1,219 m) Circuit resistance 90 Ω, max. Circuit capacitance 0.3 μF, max.
Supply, Installation, Testing & Commissioning in repairs of PS10-4B Power Supply board of existing Edwards Fire Alarm Panel (EST3x) 3X-SFS1R Red. SMPS Specifications : Mains voltage 94 to 264 VAC, 50/60 Hz AC Input Current : Standby 1.5 amps, Alarm 3.0 amps. Brownout level 93 VRMS Battery charging capacity 65 Ah max. Total Power : Voltage 24vdc Standby Current : 88mA Alarm Current : 169mA Supply Ratings : Current 10 amps (UL), 9.0amps (ULC). Output voltage: Special: 24 Vdc, Regulated: 24 Vdc Output current Special: 3 amps, Regulated: 1.5 amps. Operating environment : Temperature 32 to 120 °F (0 to 49 °C) Relative humidity 0 to 93% noncondensing. Make: EST/CIMCON/SIEMENS/ABB
Supply, Installation, Testing & Commissioning in repairs of 4X-LCD Display unit of EST3x fire alarm panel with below specifications: Operating current:Standby Alarm 55mA 66mA LCD display Backlit liquid crystal display 240 x 320 pixels 24 lines of 40 characters Operating environment Temperature Relative humidity 32 to 120 °F (0 to 49 °C) 0 to 93% noncondensing. Make: EST/CIMCON/SIEMENS/ABB
Supply, Installation, Testing & Commissioning in repairs of Loop card 3-SDC1 of EST3x fire alarm panel with below specifications: Voltage 24 VDC Operating current with fully loaded loop: Standby 3-SSDC1 144 mA; 3-SDDC1 264 mA Alarm 3-SSDC1 204 mA; 3-SDDC1 336 mA Smoke power 19.95 VDC max.1 Circuit: Configuration Class B, Style 4, DCLB; Class A, Style 6, DCLA Capacity 125 Signature Series detectors and 125 Signature Series modules per SLC Resistance 100 Ω with 250 devices Capacitance 0.5 μF max. Wire size 12 AWG (1.5 mm²) max. Termination Removable plug-in terminal strips on the SFS1-CPU main board and Signature module Operating environment Temperature 32 to 120 °F (0 to 49 °C) Relative humidity 0 to 93% noncondensing. Make: EST/CIMCON/SIEMENS/ABB
Supply, Installation, Testing & Commissioning in repairs of Sounder G1AVRF with below specifications: Sounder with mounting base, continuous normal operation for atleast 50 minutes with sound level 65db- 120db measured at 1.5m with sound output variation +5db complying with the specifications as appended below:- a) Power-12/ 24 V DC or 110 /220V AC, 1Ph, AC, 50Hz b) Range-1000 m. Make: EST/Morley/ IAS/CIMCON/SIEMENS/ABB/GST
Supply, Installation, Testing & Commissioning in repairs of 3X-NET Network Card with the ability to network up to 64 nodes on an EST3 network. The card must support Class B, Class A, and Class X wiring. The 3X-NET adapter card provides two independent RS 485 circuits: one for network data communications and one for digital audio communications. Make: EST/CIMCON/SIEMENS/ABB
Supply & Fix in repairs 12V/7AH SMF Battery for backup in case of power failure. Make : Exide/Solance/Amaron.
Supply, Installation, Testing and Commissioning in repairs electronically addressable intelligent combination of heat and photoelectric smoke detector with mounting base complying with EN 54 Standard and LPCB Approved with the specifications as appended below: a. Power 24V, </= 0.8mA (Standby current) <=5.0mA (Alarm Current). B. Class A2R. c. Indicator – Red flashes in normal and illuminates in alarm. d. Ingress protection IP-22 & material ABS. Make : Siemens/EST/CIMCON/SIEMENS/ABB/GST
Supply, installation, testing & commissioning in repairs conventional Sounder Cum strobe with mounting base, continuous normal operation for atleast 20 minutes with sound level 50db-120db measured at 1.5m with sound output variation +5db complying with the specifications as appended below:- a) Power-12/24 V DC or 110 /220V AC, 1Ph, AC, 50Hz b) Range-300m. Make: GST, Morley IAS, AGNI.
Supply, Installation, Testing & Commissioning in repairs of electronically addressable intelligent resettable type manual call point with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below:- a) Power- 24V, ≤ 0.6 mA (Standby Current) ≤1.8mA (Alarm Current) b) Class A , c) Initiating Mode- Pressing the action plate manually Resuming Mode-Manually Resumed by a special Key, d) Ingress Protection IP-43 & Material-ABS Make: GST, Morley IAS, HONEYWELL.
Supply, Installation, Testing & Commissioning in repairs of Programming card for programming of detectors and other devices in FACP Comm.Interface: USB interface Comm.Distance <15m <5m Baud Rate 2400bps Ambient Temperature 0℃~+40℃ Relative Humidity ≤95%, non condensing. Make: GST, Morley IAS, Honeywell.
Supply, Installation, Testing & Commissioning in repairs of RS485 TO RS232 and vice versa protocol converter with below specifications: supply: single phase 230v ac +/- 10% input: 2 wire rs485 output: rs232c isolation: 1000v dc optical isolation between input and output cabinet: din rail mount, abs moulded 12 terminal box of size 70*60*114 mm (H*W*D)
Supply, Installation, Testing & Commissioning in repairs of Process Indicator with retransmission output for monitoring of temperature and humidity (to be installed in RTU panel). Make: MULTISPAN/Radix/Masibus
Supply and Installation, Testing and Commissioning in repairs of 2 c x 1.5 sq mm Copper Conductor aluminium armored cable for RS-485 communication. The rate includes laying the cable and its termination with RS485 to RS232 converter to fetch data from RTU panel
Supply, Installation, Testing & Commissioning in repairs of RTD/HUMIDITY SENSOR FOR THE MEASUREMENT OF ROOM TEMPERATURE WITH INSTALLATION ACCESSORIES (TO BE INSTALLED INSIDE ROOM TO MEASURE TEMPERTURE). Make –Waree,RADIX,Wika
Supply, Installation, Testing & Commissioning in repairs Remote terminal unit with below specifications: a. 02 nos DI/DO for communication with slave units. b. Digital microprocessor based automatic programmable. c. EEPROM 1000/6000 with soft touch programming buttons. d. SMS sending module to upto 08 mobile numbers.
Supply, Installation, Testing & Commissioning in repairs of SMPS (Switch mode power supply) 230Volts AC 50 Hz output 5/12V DC. Make: Frontier / CIMCON/Siemens/Motorola
Supply, Installation, Testing & Commissioning in repairs of SMPS (Switch mode power supply) 230Volts AC 50 Hz output 24V DC. Make: Frontier/ CIMCON/Siemens/Motorola
Supply, Installation, Testing & Commissioning in repairs of GSM/GPRS Antenna compatible with Modem for wireless communication to and from RTU. Make: CIMCON/Siemens/Motorola
Supply, Installation, Testing & Commissioning in repairs of Wireless modem suitable for GSM/GPRS based communication system from RTU to MCS. GSM/GPRS modem to be mounted in RTU enclosure Make: CIMCON/Siemens/Motorola
Supply, Installation, Testing & Commissioning in repairs of Main Board of Siren control panel with the specifications as appended below:- a) Power- AC 230V, 50Hz, 0.5 A b) configurable for PC Port- RS-232 interface & communication card c) Battery backup of 04 Hours in non alarm condition and 15 Minutes in alarm condition. Make: Cimcon/Siemens/ABB.
Supply, Installation, Testing, Commissioning & recharge in repairs of 14 nos sim cards installed in each RTU panel of fire alarm and siren system installed at AF Stn Mothala & AF Stn Naliya with relevant sms pack.
Supply & Installation in repairs of Panel locks and Grommets of different sizes for cable entry/exit holes in the panel.
Supply, Installation, Testing & Commissioning in repairs of DI/DO, AI/AO circuit boards of siren system control panel. Input and Output range 24v DC. The card works on power supply of SMPS of 24v DC. Make: Frontier / CIMCON/Siemens/Motorola
Supply & Fix in Repair/Rewinding in repairs of Existing Rooftop siren, removing from site, repairing and then re-installing siren back to site. Siren of below specifications: Horizontal/vertical Single Mounting Three Phase 400/440V, 2800 RPM 50 C/s AC operated of different sizes & capacities ranging between 1.5 km 1 HP to 8 km 5 HP
Dismantling Siren RTU panel from one location and installing it back to another direction inside Main Guard Room with additional Cables, accessories & labour work. The work includes shifting of integrated siren control switches complete all as specified and as directed.
Supply, Installation, Testing and Commissioning in repairs of 2 c x 1.5 sq mm Copper Conductor aluminium armored cable. The rate includes installing the cable overhead from Armory section to Stn HQ and further extend it upto Sub-Guard room for Intruder alarm & siren system alert and its termination from amplifier to speakers.
Continental Engineers and contractors
Anil Builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .