Executive Engineer
Executive Engineer GD LJHP Gantmulla Baramulla
SITC of 11 KV Lightening Arrestors and 11 KV insulators compatible with existing 11 kv Bus Cubicle of all the three units at 3 x 35 MW LJHP power house, Baramulla, Kmr
2024_SPDC_268578_1
NIT no. 33 of 2024-25 dated 19/12/2024
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
LJHP Gantmulla Baramulla
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
Yes
CP and AO Baramulla
₹8,000
Yes
Online
27 Feb 2025
20 Dec 2024
22 Jan 2025
21 Dec 2024
21 Jan 2025
27 Dec 2024
27 Dec 2024
Amount
Supply, Installation, Testing and commissioning of compatible Lightening Surge Arrestor for Generator protection (39 MVA, 11KV, 2050A, 3 Phase) in bus duct/generator cubicle panels with 11KV bus bars at LJHP power house with following specifications:- 1. Type of Arrester Metal Oxide (Gapless) Polymer Station type Surge Arrester 2. Type of mounting Bracket type Pedestal Type 3. Applicable Standard IEC & IS standards 4. Nominal System Voltage / Highest System Voltage (kV) = 11 kV/12 kV 5. Rated Voltage of Arrester (kV rms) = 9 kV rms 6. Continuous Operating Voltage (C.O.V.) (kV rms)=7.65 kV rms 7. Installation Indoor (in BUS DUCT) 8. Type of construction Single Column, Single Phase 9. Connection Phase to Earth 10. Nominal discharge current rating (kA Peak) = 10 kA Peak 11. Nominal Rated current = 2.5 kA
Supply, Installation, Testing and commissioning of compatible 11 KV porcelain bus post insulators (as per existing) in bus duct/generator cubicle panels for square type bus bars (100mm x100mm) at LJHP power house with following specifications:- Applicable Standard IEC-60383/IS-731 Power Frequency withstand voltage Dry Min. 50 kVrms, Max. As per Requirement Wet Min. 35kVrms, Max. As per Requirement Lightning Impulse withstand voltage Positive Min. 70 kVpeak, Max. Negative Min. 70 kVpeak, Max. Creepage Distance As per Requirement/existing Cantilever Load 10kN, indoor type
Supply, Installation, Testing and commissioning of compatible Surge capacitor for (as per existing) in bus duct/generator cubicle panels for square type bus bars at LJHP power house with following specifications:- 12 KV, 0.5 mF (mili-Farad), 1 PH, 50 HZ, BASIC INS. LVL. 28/75, Single Bushing, Indoor Type Surge Protection Capacitor as per IS 11548 with Internal Discharge Resistor, All PP Impregnated With Non-Toxic Npcb Oil, Temp. Category: 50 Deg Celsius
Miscellaneous Items(clamps, fixtures, Nut & Bolts, etc) sundry items required for complete Job
VERSATILE ENGINEERING SOLUTIONS (BID ID -2308953)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .