Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹3.0 L
EMD Value
₹3,000
Closing Date
3 Dec 2026, 5:00 pm7d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
EXECUTIVE ENGINEER PWD ELECTRICAL
ELECTRICAL DIVISION PWD ERODE
Renewal of 3.5 KVA UPS in the Collector Chamber and Main Meeting Hall at District Collectorate building in Karur District
2026_PWD_726529_1
NIT07/TNo101/2026-27
Open Tender
Electrical Works
Lump-sum
30 days
KARUR
Please refer Tender documents.
9 documents required · 9 mandatory
₹0
₹3,000
19 Nov 2026
19 Nov 2026
4 Dec 2026
19 Nov 2026
3 Dec 2026
19 Nov 2026
180 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Renewal by Supply, Erection, Testing and Commissioning of uninterrupted Power supply (UPS) (Sine Wave) (Microteck/ Amaron/ Luminious/ Exide) unit of capacity 2KVA with input Voltage 12V DC Supply, Output Voltage 230V, 50HZ AC Supply with following accessories/ Circuits and with following accessories and with 1Hour of Battery backup at full load respectively.
1.Battery charging Device. 2.Inverter Circuit.
3.Over load as well as short circuit.
4.Indication for operations like Battery charging, overload, Low Battery etc.
5.Reset Switch - 1No.
6.Tall Tubular Battery - 1No. of 12V AC IT 500 150AH (Reputed make )
7.Two layer Wooden/ Steel stand. | 1 | No | 61,740 | ₹61,740 |
| 2 | Supply and fixing of 3500VA UPS with 4Nos 12 V 150 AH tubular battery [Exide IT 500] with 1 hour back up and 48months warranty for mentioned capacity on full load operation and the following features.[V- Guard /APC/equivalent]
a) Inverter shall be free from workman ship defects sharp edges nicks, scratches, burs etc., all fasteners shall be fixed properly. The equipment's shall be complete with all parts and all parts shall be functional.
b) Enclosure shall conform to protection requirement of IRL to IS 13947 (part 1) 1993.
c) Switching device shall be most ET (or) IGBT.
d) Switching frequency shall be above 50HZ.
II. Input ; 120 v to 260 v 50 HZ single phase AC
III. Output : The variation in output voltage from NO- load to full load expressed as a percentages of no load voltage shall not exceed +15% over + 10 % and 20 % variation of the rated DC input voltage. The frequency of the output voltage shall be 50 HZ + 1.3%.
IV). Inverter efficiency minimum 85% as per CI.T.93 of ISS.
v) Over load: inverter shall with stand 10% overload for at least 10 minutes.
V).Protections.
VI). a) Input voltage goes outside the range 120 to 260 volts the system shall switch over to inverter mode.
b). over voltage short circuit and over load at inverter output terminals.
c).Battery reverses polarity. | 1 | No | 1,30,000 | ₹1,30,000 |
| 2.01 | d). Protection against over discharge,
The load shall be cut off as soon as the voltage of the battery terminal falls blow.
i) 10.5 v for 12 v and
ii) 21v for 24v battery system.
e). The inverter shall incorporate an arrangements for automatic charge over of load from main supply to the inverter AC output incase of failure of mains supply with correct pending indication as per Clause 5.6 of IS 13314/ 1992
f). inverter should have surge protection also
VII indicators.
a) Following indicators shall be provided.
i) Mains presence. ii) Mains mode. iii) Battery charging.
iv) INVERTER MODE v) Battery low.
80 battery bank; 12 Volts lead battery to IS 7372 (1995) with amdts.No1,2&3 shall be reputed makes from the following i.e Exide /Amci/yuosa pretolite /kirloskar/ amarraja. ISI marked.
9) Battery stand with wheel angle iron frame arranged. | - | - | - | - |
| 3 | Renewal by Supply and fixing of 12V batteries wired in series to provide higher voltage efficiency and stable backup power | 3 | No | 19,982 | ₹59,946 |
| 4 | Less Credit of Old Materials | 1 | Each | 500 | ₹500 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.07 MB
BOQ_872162.xls
BOQ • 0.39 MB
TNO_101_Tender_Conditions.pdf
Tender Documents • 0.47 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .