Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹46.2 LAccepted-AOC B 39 UPPER GROUND FATEH NAGAR NEW DELHI 110018 | WEST | DELHI | 110018 | 1 | Accepted-AOC AOC | |
| 2 | 2₹49.2 L+₹2.4 L (5.10%)Rejected-Finance | 2 | Rejected-Finance NOT L-1 | |
| 3 | 3₹49.6 L+₹2.7 L (5.80%)Rejected-Finance | 3 | Rejected-Finance NOT L-1 | |
| 4 | 4₹49.8 L+₹3.0 L (6.34%)Rejected-Finance 2 A NARENDRA APPARTMENT CENTRAL JAIL ROAD SUBHASH BRIDGE AHMEDABAD 380027 | AHMEDABAD | AHMEDABAD | GUJARAT | 380027 | 4 | Rejected-Finance NOT L-1 | |
| 5 | 5₹50.5 L+₹3.7 L (7.82%)Rejected-Finance 203 NABIL APARTMENT ASHOK NAGAR OPP HATHIKHANA ANAJ MARKET TULSIWADI ROAD KARELIBAUG VADODARA 390018 GUJARAT | VADODARA | GUJARAT | 390018 | 5 | Rejected-Finance NOT L-1 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
13 Feb 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE ARMY BHUJ
GE ARMY BHUJ
REPAIR/ REPLACEMENT OF LT CABLES AND ALLIED ITEMS AT KHAVADA AND MIL STATION BHUJ AND GHANDIGHAM UNDER AOR OF GE(A) BHUJ
2023_MES_575671_1
8978
Open Tender
Civil Works - Others
Item Rate
180 days
ARMY AREA BHUJ
REFER TENDER
6 documents required · 6 mandatory
₹500
GE ARMY BHUJ
₹90,000
Yes
26 Mar 2023
18 Jan 2023
14 Feb 2023
18 Jan 2023
13 Feb 2023
8 Feb 2023
Amount
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc for laying of cables, erection of poles, struts/ stays etc not exceeding 10 sqm on plan and getting out in soft loose soil.
Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil.
Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point in soils.
M & L for sand filling in trenches for cushioning of LT cables punning after filling complete as specified and as directed. Note: Punned thickness shall only be measured and paid
Supply and lay un-reinforced precast concrete cable cover , class , LV , Type I flat size 250 x 150 x 40 mm laid dry in treches over under ground cables.
S & F GI pipe, light grade, of size 50 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection .
S & F GI pipe, light grade, of size 40 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection .
S & F GI pipe, light grade, of size 80 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection .
Dismantaling of any type and size ACSR conductor complete all as specified and directed by Engr-in-Charge.
Dismantaling of stay assembly including demolation of concrete etc complete all as specified and directed by Engr-in-Charge.
Dismantaling of insulator any size and any type complete all as specified and directed by Engr-in-Charge.
Dismantaling of cross arm of MS chanel or angle sections any type any size etc complete all as specified and directed by Engr-in-Charge.
Disconnecting, taking out, removing old existing unserviceable LT underground cable any size and type etc complete all as specified and directed.
Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 4 core 16 Sqmm laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed.
- ditto- here in before Item 14 but of size 3.5 core 25 Sqmm
- ditto- here in before Item 14 but of size 3.5 core 35 Sqmm
- ditto- here in before Item 14 but of size 3.5 core 50 Sqmm
- ditto- here in before Item 14 but of size 3.5 core 70 Sqmm
- ditto- here in before Item 14 but of size 3.5 core 95 Sqmm
- ditto- here in before Item 14 but of size 3.5 core 240 Sqmm
- ditto- here in before Item 14 but of size 2 core 16 Sqmm
- ditto- here in before Item 14 but of size 2 core 25 Sqmm
M&L for cable jointing kit LT 1.1 KV straight through joint 70 sqmm to 240 Sqmm 4 Core , heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
M&L for cable jointing kit LT 1.1KV straight through join 16 sqm to 25 sqmm 2 core,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
M&L for cable jointing kit LT 1.1KV straight through joint 16 sqmm to 25 Sqmm 4 core ,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-
Incoming
(a) Copper Bus bar, 600 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 400 A 36 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal magnetic release 415 volts 160 A 36 KA-01
(c) MCCB 4 Pole thermal magnetic release 415 volts 200 A 36 KA-01
(c) MCCB 4 Pole thermal magnetic release 415 volts 125 A 36 KA-02
(c) MCCB 4 Pole thermal magnetic release 415 volts 160 A 36 KA-01
(c) MCCB 4 Pole thermal magnetic release 415 volts 25 A 25 KA-02
(c) MCB 4 Pole 415 volts 16 A 10 KA-02
(h) Spare compartment for 100 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 02 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-
Incoming
(a) Copper Bus bar, 250 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 160 A 35 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal adjustable magnetic release 415 volts 25 A 16 KA-07
(h) Spare compartment for 25 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following including taking down:-
Incoming
(a) Copper Bus bar, 300 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 200 A 36 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal magnetic release 415 volts 25 A 16 KA-08
(h) Spare compartment for 25 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following including taking down :-
Incoming
(a) Copper Bus bar, 200 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 125 A 35 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal adjustable magnetic release 415 volts 25 A 16 KA-06
(h) Spare compartment for 25 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following including taking down :-
Incoming
(a) Copper Bus bar, 240 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 160 A 35 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal adjustable magnetic release 415 volts 25 A 16 KA-07
(h) Spare compartment for 25 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following including taking down :-
Incoming
(a) Copper Bus bar, 240 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 160 A 35 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
(g) On load change Over switch of capacity 160 Amps 4 Pole complete.
Outgoing
(c) MCCB 4 Pole thermal adjustable magnetic release 415 volts 63 A 16 KA-01
(c) MCCB 4 Pole thermal adjustable magnetic release 415 volts 25 A 16 KA-04
(c) MCB DP 240 volts 25 A 10 KA-05
(c) MCB 4 Pole 415 volts 16 A 10 KA-02
(d) Digital Timer including contactor of suitable capacity - 02 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following including taking down :-
Incoming
(a) Copper Bus bar, 100 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 63 A 25 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal adjustable magnetic release 415 volts 16 A 16 KA-01
(c) MCB DP 240 volts 16 A 10 KA-04
(h) Spare compartment for 16 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following including taking down :-
Incoming
(a) Copper Bus bar, 60 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 25 A 16 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
(g) On load change Over switch of capacity 160 Amps 4 Pole complete.
Outgoing
(c) MCCB 4 Pole thermal adjustable magnetic release 415 volts 40 A 16 KA-01
(c) MCCB 4 Pole thermal adjustable magnetic release 415 volts 16 A 16 KA-01
(h) Spare compartment for 16 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following including taking down :-
Incoming
(a) Copper Bus bar, 60 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 25 A 16 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCB 2 Pole 240 volts 16 A 16 KA-03
(h) Spare compartment for 16 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
M&L for three core PVC insulated sheathed(heavy duty) unarmoured copper conductor cable (for phase and neutral) of size 1.5 Sqmm including PVC conduit heavy duty 15 mm size for connection drawing through pole or GI brackets of street light fittings to junction box complete all as directed.
Supply and fixing in replacement old unserveceable cable junction box with new pole mounted thermoplastic cable junction box for street light with IP-65 protection, weather proof with metric knockouts for cable entry for outdoor installation with front door opening system including terminals for one incoming and two outgoing cables of size 16/25 sqmm 4 core, one MCB SP 3 to 6 Amp 240V AC with mounting clamp of flat iron, nut, bolt and washers complete all as specified and directed .
M&L , earthing complete for machinary / Equipment installed at power house / sub station with galavanised steel earth plate electrode of size 60 cmx 60 cmx 6 mm thick buried directly in ground ( earth pit not less then 2.25 m deep below the normal ground level ) with top edge of the earth plate not less then 1.5m below normal Ground level connected galvanised earth lead wire 4.0mm dia by means of bolts, nuts, washerws and check nuts all shown in electrical plate No.5 of SSR Part- I connected to main board / disribution board complete .Earthing GI lead and GI protection pipe 15 mm dia light grade upto 7.5 m from earth pit connecting to machinary/ equipment, testing point, all as specified and testing on completion all as per directed.
Note :- (i) The unit rate shall also included for earth work in hard /dense soil , PCC type C-I (1:3:6) chamber , PCC 1:2:4 type B-I cover 50 mm thick reinforced with 8 mm dia TMT bars,150 mm c/c both ways, funnel with watering pipe 20 mm dia medium graded , GI protection pipe light grade 15 mm dia and wire mesh complete in addition to items No. 1(a) to (e) of preamble (notes) under sub heading earthing specified on SI page No. 389 of SSR Part - II.
(ii) Earthing lead and GI protection pipe beyond 7.5 mtrs will be measured and paid separatelly if required under appropriate Schedule.
Note :- (i) Earthing shall be tested as specified in casul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On teting after complataion of earthing , if the desired earth resistance is not obatined the earthing wiil be re done by the contractor at his on risk and cost to the entire satisfaction of the Engr - in - charge.
M&L , earthing complete for machinary / Equipment installed at power house / sub station with galavanised steel earth plate electrode of size 60 cmx 60 cmx 6 mm thick buried directly in ground ( earth pit not less then 2.25 m deep below the normal ground level ) with top edge of the earth plate not less then 1.5m below normal Ground level connected galvanised earth strip 32X6 mm by means of bolts, nuts, washerws and check nuts all shown in electrical plate No.5 of SSR Part- I connected to main board / disribution board complete .Earthing GI lead and GI protection pipe 15 mm dia light grade upto 7.5 m from earth pit connecting to machinary/ equipment, testing point, all as specified and testing on completion all as per directed.
Note :- (i) The unit rate shall also included for earth work in hard /dense soil , PCC type C-I (1:3:6) chamber , PCC 1:2:4 type B-I cover 50 mm thick reinforced with 8 mm dia TMT bars,150 mm c/c both ways, funnel with watering pipe 20 mm dia medium graded , GI protection pipe light grade 15 mm dia and wire mesh complete in addition to items No. 1(a) to (e) of preamble (notes) under sub heading earthing specified on SI page No. 389 of SSR Part - II.
(ii) Earthing strip and GI protection pipe beyond 7.5 mtrs will be measured and paid separatelly if required under appropriate Schedule.
Note :- (i) Earthing shall be tested as specified in casul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On teting after complataion of earthing , if the desired earth resistance is not obatined the earthing wiil be re done by the contractor at his on risk and cost to the entire satisfaction of the Engr - in - charge.
Taking down carefully existing unserviceable aluminum/copper point wiring (light, fan, socket or power) of any description & in any position complete including all fittings & fixtures such as switches, ceiling roses, pendants, regulators, socket, light fittings, lamp holders etc including taking out and removing serviceable fittings/fixtures and making good the disturbed surface of walls, floors, ceiling etc. to match with the existing surfaces complete all as specified and directed
M&L for point wiring with using 1.5 Sqmm (nominal area) multi standard copper conductor, single core, FRLS PVC insulated & unsheathed cable, 1100 volts grade with and including concealed PVC conduit of adequate size sunken type pressed steel terminal box and junction boxes 1.6mm thick of suitable size, duly painted with one coat of red oxide primer and two coats of black bituminous paint for mounting fittings and wiring to be terminated in pressed steel sunken boxes with and including all accessories and using 1.5 Sqmm (nominal area) stranded copper conductor single core conductor, FRLS PVC insulated & unsheathed cable as in earth wire connected to common earth dolly complete all as specified and directed for following:- NOTE :- (i) Quoted rate shall be deemed to include the cost of cutting chases in walls / pillars /column etc. of any description for concealing the boxes to required depth & making good the disturbed surface in CM 1:4 including finishing the surface to match with the existing surface. (ii) Fittings like switches, sockets, regulators, lamp holders, light fittings shall be measured and paid for separately under appropriate item of Schedule `A'. (iii) The quoted rates shall be deemed to be inclusive for provision suitable white frame and conncted accesories all as specfied and directed.
One light/buzzer point controlled by one; one way switch.
One fan/exhaust fan point controlled by one, one way switch
One 3 pin socket out let 5 amp (independent) point controlled by one way switch.
One 3 pin socket out let 5 amp point on the (same board) with other switches.
All as per item No. 40 here-in-before but with 2.5sq mm size FRLS pvc insulated and unsheathed 1100 volts grade single core stranded (multistrand) copper conductor cable for 3 pin socket outlet 15 amp on independent board.
S&F ceiling rose surface bakelite 63.5 x 20 mm, three terminals, complete all as specified and directed.
Supply and fix modular switch 6A,1 way 230 volts AC circuit complete all as specified and directed.
Supply and fix modular switch 16A,1 way 230 volts AC circuit complete all as specified and directed.
Supply and fix modular Socket, 6A - 2/3 pin combined 2 module, 230 volts AC circuit complete all as specified and directed.
Supply and fix modular Socket 6A/16A - 2/3 pin combined 2 module,230 volts AC circuit complete all as specified and directed.
Supply and fix single module fan regualtor,1000W, 230V AC circuit complete all as specified and directed.
S & F buzzer, ding dong AC 230 Volt single pole complete as specified.
Supply LED 20 W high quality indoor batten type tube light fitting with PC housing and as well light application CCT 6000 K, electrical connection of three core 0.5 sqmm copper flexible connection from ceiling rose to tube light fitting and with proper square box for fitting of tube light fitting complete all as specified and directed by Engr-in-charge
S&F lamp holder PVC / Polycarbonate type with cord grip cap suitable for LED lamp fitting complete all as specified and directed by Engr-in-charge
Taking down carefully MCBs, Metal clad plug, distribution boards/main switches of any type and size and S & F sheet metal enclosure powder painted for MCB DB SPN 08 way double door with IP-42 protection with Din rail and busbar complete all as specified and directed by accepting officer
Taking down carefully MCBs, Metal clad plug, distribution boards/main switches of any type and size and S & F sheet metal enclosure powder painted for MCB DB SPN 04 way double door with IP-42 protection with Din rail and busbar complete all as specified and directed by accepting officer
Supply and fixing MCB SPN, 6 to 32 Amps in `C’ series having current rating 10 KA complete all as specified and directed.
S&F MCB single pole, 6 to 32 Amps in `C’ series having current rating 10 KA complete all as specified and directed
M&L for point wiring with using 1.5 Sqmm (nominal area) multi standard copper conductor, single core, FRLS PVC insulated & unsheathed cable, 1100 volts grade with and including PVC casing and capping of adequate size fixed on surface with PVC rawl plugs with sunken type pressed steel terminal box and junction boxes 1.6mm thick of suitable size, duly painted with one coat of red oxide primer and two coats of black bituminous paint for mounting fittings and wiring to be terminated in pressed steel sunken boxes with and including all accessories and using 1.5 Sqmm (nominal area) stranded copper conductor single core conductor, FRLS PVC insulated & unsheathed cable as in earth wire connected to common earth dolly complete all as specified and directed for following:- NOTE :- (i) Quoted rate shall be deemed to include the cost of cutting chases in walls / pillars /column etc. of any description for concealing the boxes to required depth & making good the disturbed surface in CM 1:4 including finishing the surface to match with the existing surface. (ii) Fittings like switches, sockets, regulators, lamp holders, light fittings shall be measured and paid for separately under appropriate item of Schedule `A'. (iii) The quoted rates shall be deemed to be inclusive for provision of covering sunken boards/terminal boxes / junction boxes of any shape and size with 3mm thick laminated sheet fixed with suitable brass screws and cup washers
One light/buzzer point controlled by one; one way switch.
One fan/exhaust fan point controlled by one, one way switch
One 3 pin socket out let 5 amp (independent) point controlled by one way switch.
One 3 pin socket out let 5 amp point on the (same board) with other switches.
All as per item No. 56 here-in-before but with 2.5sq mm size FRLS pvc insulated and unsheathed 1100 volts grade single core stranded (multistrand) copper conductor cable for 3 pin socket outlet 15 amp on independent board.
S&F switch flush type, 5/6 Amps, single pole, one way, 230 volts AC circuit complete all as specified and directed.
S & F Bell push, flush type 5 AMP AC 230 Volt single pole complete as specified.
S&F switch socket outlet five pin, 5 Amps, flush type, 230 volts AC circuit complete all as specified and directed.
S&F switch socket outlet combination, multipurpose, three pin, 15 Amps & three pin 5 Amps controlled by one switch , flush type, 230 volts AC circuit complete all as specified and directed.
S&F Socket outlet 2 in 1, 3 pin, 6 and 16 amp flush type 230 volts AC circuit complete all as specified and directed.
S&F Socket outlet 2 in 1, 3 pin, 6A, 230 volts AC circuit complete all as specified and directed.
Disconnecting, taking out, removing old existing unserviceable LT underground cable and Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade ,laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed of size 2 core 10 sqmm :-.
- do- as per Item 64 here in above but of size 4 core 16 Sqmm
Suppl and fix suitable contactor for 5HP motor , AC3 415V 50 Hz including removing burn out contactor and make starter in working condition all as specfied and directed.
Supply and fix motor protection circuit breaker (MPCB) IP 65 of suitable for 5 HP capacity of motor and suitable for IE2, IE 3, IE4 motors, of rated frequency of 50 HZ, impulse withstand voltage 6 KV, complete all as specified and directed by Engr-in-charge
Supply and lay Galvanized iron pipe, medium class of dia 50mm including all fittings such as bends, tees, elbows, reducers, unions, plugs, sockets etc laid in bldgs complete all as specified and directed by Engr-in-charge
All as per item no 68 here in before but of dia 40mm complete
All as per item no 68 here in before but of dia 25mm complete
Supply and fix PP R gate valves (brass insert) of dia 50 mm complete all as specified and directed by Engr-in-charge
Supply and fix PP R gate valves (brass insert) of dia 25 mm complete all as specified and directed by Engr-in-charge
Takaing down burnout motor by disconnceting pump shaft and rewinding of 5HP motor completely as per exsisting gauge copper winding and proper insulation material and refixing the same after rewinding all as specfied and directed by Engineer-in-Charge
Takaing down damaged pump impeller by disconnceting incoming pipes and motor and replacemnet of impeller of suitable size directed by Engineer-in-Charge
supply and fix in replacemnet timer for star delta starter all as specfied and directed
Labour only for repairing and attending the complaint of Split/WindowAC/ Water cooler/Refrigeratorby highly skilled tradesman and carryout minor repair and making functional complete all as specified and directed at site. Note :- (replacement of spare part will be measured and paid separately under appropriate items )
Disconnecnting, dismantling and taking out the non functional Air Conditioner window type/Split type/water cooler of any description, any make and in any position 1.5 TR/2.0 TR capacity Single Phase 50 HZ, strip opening, coil of indoor unit and brazing the discharge and suction line by and checking & retightening of all electrical connections. Replacement of minor part such as nut, bolts, screws, washers, fixing properly bracket housing of capacitors, relay incl replacment of unserviceable parts, cleaning and servicing of the AC with using caustic soda/detergent powder solution, taking out and removing unserviceable/defective wiring & parts incl painting the bottom with one coat of black synthetic enamel paint, replacement of unserviceable and defective parts brazing reassembling and testing of the AC complete all as specified and directed. Note :- (i) The replacement of defective/nonfunctional parts shall be measured & paid for seperatly as` supply only' under appropriate item of Schedul A and fixing charges for new items are deemed to be included under this item. (ii) The rate for above items are deemed to include for transpotation of AC to & from workshop as approved by Engr-in-Charge for necessary unserviceable screws/nuts/bolts /washer/packing etc with new one. (iii) Charging of gas if required shall be measured and paid for separatly under appropriate item of schedule A however vacuum and pressure leakage testing with nitrogen (N2) if any required is deemed to be included under the units rate quoted by the contractor for this item.
S&F compressor sealed unit suitable for 1.5 TR Capacity for any type of window AC Single Phase 230 Volts incl brazing to suction & discharge line vaccum testing with and including charging of refrigerant gas (R-22) & testing incl disconnecting and taking out existing defective compressor of any description & in any position complete all as specified and directed. Make, Kirloskar,Tecumsha, Whrilpool
All as per Item No. 78 here in above but for Split 1.5 TR capacity
S&F in replacement of Sealed unit compressor for 40/80 ltrs capacity water cooler including vacuum testing and filling of refrigerant gas to required pressure.
M&L for replacment of old unsv starting relay box carefully from window/Split type A/C 1 to 2 TR capacity of any make including making necessary elect connections,
All as per Item No. 81 here in above but for water coolers 40 to 80 Ltr capacity
S&F in replacement over load protector suitable for 1.5 AC/WC 40/80 Ltr capacity
S&F Thermostat suitable for A/C, Water coolers, Refrigerators, Make- Kelton/Infass/Renutrol
S & Fix repair Starting capacitor 240 V, of the following size complete all as specified and as directed for 80 to 100 MFD
S & Fix repair Starting capacitor 240 V of the following size complete all as specified and as directed for 100 to 150MFD
S & Fix repair of Running capacitor 240 Volts of following size for 4/6 MFD
S & Fix repair of Running capacitor 240 Volts of following size for 30/36 MFD
S & Fix repair of Running capacitor 240 Volts of following size for 45/50/60 MFD
M&L for charging of refrigerant gas R-22/R-410A complete unit or to make up required pressure in existing air conditioner, window type invertor split AC/hot & cold split AC of any description any capacity any make and in any position complete all as specified and directed complete all as specified and directed.
M&L for charging of refrigerant gas 134A/600A to make up the required pressure in any type refrigerator complete all as specified and as directed.
Disconnecnting and taking out existing defective AC electric motor of any description & in any position of size 1/7 HP to 1/5 HP 230 Volts, strip opening for rewinding and removing to & from workshop for rewinding as apporved by Engr-in-Charge, rewiding with appropriate size copper supper enameled wire as approved incl insulating material such as illuminous paper, leatherized paper , cotton tape, glass sleeving, insulating varnish etc, testing at workshop to the entire satisfaction of Engr-in-Charge, transpotation & fixing the motor at site incl necessary connecting & testing complete all as specified and directed.
S& F in replacement fan motor AC 230 V high speed suitable for split AC 1.5/2 ton for any Make of AC all as specified and directed.
Supply and fix in repair copper made Condenser/Evaporator coil assembly complete suitable for 1.5/2.0 Ton window type/Split type AC unit complete including necessary brazing, welding, pressure and testing etc, replacement of worn out misc items required at site complete all as specified and as directed.
S&F in replacement Swing motor for indoor unit of Split type AC 1.5/2 Ton capacity all as specified and directed.
S&F in replacement of PCB of electronic circuit complete including display panel, signal receiving slot, display PCB (ie Remote) all as per existing one and suitable for 1.5/2 Ton Window type A/C : Make Blue Star, Videocon, LG, Samsung
All as per item No 96 but for 1.5/2 Ton Split Type A/C Ltr capacity
Supply and fix in replacement of remote controller unit of Air Conditioner Split Type/Window type of any description any make and in any position 1.5/2 TR capacity
S&F in replacement of drain pipe for water Cooler & Split type AC 1.5/2.0 ton Capacity as per existing sample all as specified and directed
M&L for testing of complete existing Window type/Split type AC unit of any description, any make & in any position by vacuum and pressure testing with Nitorgen (N2) and brazing the leakage/damaged copper pipe as required at site and charging of the refrigerant gas to required pressure and testing on completion complete all as directed by Engr-in-Charge. Make:- as per existing make of unit.
Dismantling and taking out exiting defective Copper tubing off Size of any description & in any position and supplying and fixing new copper tubing special annealed pressure copper purity min 99.9% and making flairing at both ends for connections including Brass nut of any size as required and incl insulating material etc and testing complete all as Specified and directed.
Supply and fixing fan blade of any type and any description suitable for motor of any capacity for AC/water cooler/Refrigerator complete all as specified and directed.
M&L for Replacement of existing unserviceable / damaged portion of the body of the water coolers i.e. in bottom / top / frame etc. with and including using new, 18 SWG, MS black sheet, cut to size, made to shape and size including necessary mouldings etc and fixing and riveting /bolting with existing parts / portion of the water cooler complete all as specified and directed.
S & F earth plug and socket, single pole, neutral sheet metal enclosures with a two pin, plug and socket 20Amp, 240 volts with and including one MCB, SP, 20A, 240 Volts all as specified and directed.
Shreeganesh Construction
Shree Builders
Shree Krushna Supply Corporation
Ell Ess Contractor
Jinendra Chemicals
Dighard Electricals
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .