Executive Engineer Mech. Irrig. Div. Baramulla
Mechanical Irrigation Div. Baramulla
LIS Sheeri-Construction of Cement concrete Channel at damaged spots on main canal and sub minors at Spots, jacketing of delivery tanks and providing crate work near supply channel.
2026_IFC_325460_1
eNIT 22 of 2026-27 (Sheeri) MISD Baramulla
Open Tender
Civil Works
Percentage
420 days
Baramulla
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Mech. Irrig. Div. Baramulla
₹4.8 L
Mechanical Irrigation Div. Baramulla
21 Sept 2026
21 Sept 2026
14 Oct 2026
21 Sept 2026
13 Oct 2026
21 Sept 2026
2 Oct 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Electro Mechanical Works | |||||
| 1.01 | Design, Supply, Installation, Testing and Commissioning of 20 Cusec, 43 m dynamic head Vertical Turbine pumping unit of lift Irrigation Scheme Sheeri-I as per following site conditions and specifications:
Technical Specifications
I. PUMP SPECIFICATION:
1) Make: Kirloskar/Wilo/Flow more/Mather Platt or equivalent as per EOI of Superintending Engineer mechanical Circle Kashmir I&FC Department Srinagar.
2) Model :To be quoted
3) Type : Centrifugal Vertical Turbine pit mixed flow
4) Discharge : 20 Cusec
5) Total Dynamic Head : 43 meters
6) Pump power input at duty point :To be quoted
7) Water to be handled : Raw water containing silt
8) No. of stage: 2
9) Lubrication : Self water lubrication
10) Vibration Level: as per HIS
11) Noise Level: As per HIS
12) Sealing arrangement: Gland packed/Mechanical Seal/As per OEM
13) Discharge bend: below machine floor level
14) Pump efficiency at duty point without negative tolerance :85 % or above
15) Speed (Rpm): 995
16) Diameter of Suction column pipe: To be quoted
17) Diameter of Delivery : To be quoted
18) Material of Impeller : SS ASTM A351/ CF8M
19) Material of Head shaft : SS AISI 410 / to be quoted
20) Impeller key / Thrust ring/ retaine/ split ring/ shaft/ sleeves/coupling: SS 410
21) Material of Line shaft, column Shaft Bowl Shaft : SS AISI 410
22) Column pipe : Flanged column pipe fabricated out of MS plate of adequate thickness and length As per OEM
23) Material of Pump casing : Close fine grained cast iron confirming to IS-210 Grade-260
24) Strainer: Basket type MS Galvanised / to be quoted.
25) Motor Stand/ Sole plate : MS as per IS 2062: 1992
26) Nuts and Bolts: High Tensile Steel/Carbon Steel
27) Bowl assemblies Suction bellvand bowl shall be made :Close fine grained cast iron confirming to IS-210 Grade-260
28) Material of shaft sleeves :SS AISI 410 /as per OEM to be Quoted
29) Impeller and wearing ring: SS ASTM A351/CF8M
30) Discharge Head: MS Fabricated/ OEM
II. Motor/Prime Mover Specifications:
1) Type : Vertical Solid Shaft sq cage induction motor.
2) Make : Kirloskar / ABB / Crompton/ equivalent make
3) Speed : 995 rpm
4) Capacity : 452 HP
5) No of phases : 03 phase 415 V + 10%, 50 Hz, AC supply.
6) Winding : Copper wound squirrel cage
7) Type of enclosure : TEFC
8) Class of insulation: F
9) IP Rating: 55.
10) Duty type : S1
11) Motor efficiency: IE2 (95%)
III. Pump unit shall be provided with suitable discharge head with proper stuffing box arrangement, non-reverse ratchet, coupling, sole plates, foundation bolts etc as per standard specification. The job also involves any welding work etc. required during installation of pumping unit at site shall be arranged by the firm itself. | 1 | Job | 65,01,984 | ₹65,01,984 |
| 1.02 | Providing, fitting, testing and commissioning of 1 MVA Distribution transformer for LIS Sheeri-I
11/ 0.433kV,1 Mva 3-Phase Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Copper Wound) and with LV Cable Box having detachable Aluminum Gland plate Transformers should have arrangements for vertical takeoff cable with OCTC (off ckt. Tap changer). Filling of transformer oil upto required level of the transformer.
Make = Castrol, Servo, HP conforming to IS 335
The Toil shall be filled in transformer at site | 1 | Job | 16,12,000 | ₹16,12,000 |
| 1.03 | Supply Installation Testing and commissioning of 10 Ton Chain Pully Block with monorail for LIS Sheeri-I and having spur-gear configuration, enclosed load-bearing parts, an automatic load brake system, and carry an official ISI mark. Hand and load chains must be calibrated to provide a minimum 06-meter true vertical lift height. Unit must come integrated with a manual push/geared monorail travel trolley configured to sit tightly on the lower flange of the ISMB 300 bridge girder. (Approved makes: Induff, Globe, Pull-lift, or equivalent). The job also includes painting of ISMB beam by way removing/scrubbing old existing colour with the help of skilled painter , tools and tackles and then applying of metal primer coat then painting with two coats of A grade enamel yellow paint (preferable make: Neurolac, Berger, asian), All tools and tackles, skilled labour required for the completion of work shall be arranged by the firm it self. | 2 | Job | 75,000 | ₹1,50,000 |
| 1.04 | Upgradation of 1 Mva Sub Station of LIS Sheeri-I of below mentioned Specification
1 Fabrication, supply, installation, testing & commissioning of 09 Mtr long M.S steel tubular poles (410 SP33) .. Each pole shall have suitable size of holes for accommodating nuts & bolts and base plate of suitable size fitted at the bottom for grouting. (pit depth = 1.35 Mtr) (02 No)
2 Cement bottoming 1:2:4 mix as per Standards 0.5 cum per pole (02 Job)
3 Supply, installation, testing of ISMC-75 channels with clamps, nuts & bolts, washers (9 feet x 7 no =63 feet = 19 mtr ) @ 6.8kg/mtr = 129.2kg + 15 kg nuts bolts clamps = 144.2 kg
4 Providing and painting of one coat of red oxide paint and two coat of aluminum paint to MS pole. (02 job)
5. Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required (06 No)
5 Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required. (01 Set)
6 Providing and fitting of 11 KV 200A 3-ph Gang operated Air Break Switch (01 Set)
7 Providing of 11Kv DO Operating Rod (FRP) with min. 18 ft length (01 Job)
8 Supply and erection of 200A horn gap fuse set suitable for 3 wire, 11 KV overhead lines. (01 Set)
9 Providing and fitting of danger plate. (01 Job)
10 Providing and fixing of anti-climbing device with clamps, etc. (02 Job)
11 Providing and fitting of 0.5 ACSR with the help of skilled labor, tools & tackles. 150 Mtr
12 Supplying and laying 25mm X 5mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (01 Job)
13 Painting of old existing 1 Mva Transformer by way removing/scrubbing old existing color with the help of skilled painter, tools and tackles and then applying one coat of epoxy primer and two coats of epoxy paint (preferable make: Nerolac, Berger, Asian equivalent), All tools and tackles, skilled labor required for the completion of work shall be arranged by the firm itself. | 1 | Job | 1,25,320 | ₹1,25,320 |
| 1.05 | Renovation/ upgradation to Existing 2000 Amp main control Pannel of LIS Sheeri-I having specifications as mentioned below: -
1 Providing, fitting and testing of Main 2000 Amp ACB in Main Control panel, CN-CS 2000 of L&T/ Havells/ Schneider/ Equivalent make as per EOI of SE Mech. Circle Kmr. I&FC Department Srinagar 2000 A, 3 Pole, Breaking capacity 50 kA.
2 Providing, fitting and testing of outgoing ACB for 20 cusec VT pumping unit in Main Control panel: CN-CS 800 C series fixed ACB of L&T/ Equivalent make as per EOI of SE Mech. Circle Kmr. I&FC Department Srinagar In 800 A, 3 Pole, Breaking capacity 50 kA with spreaders. (02 No)
3 Providing, fitting and testing outgoing ACB for 10 cusec VT pumping unit in Main Control panel: CN-CS 630 C series fixed ACB of L&T/ Equivalent make as per EOI of SE Mech. Circle Kmr. I&FC Department Srinagar in 630 A, 3 Pole, Breaking capacity 50 kA with spreaders. (02 No)
4 Providing, fitting and testing of 63 Amp MCCB in main control panel for Lightning. (01 No)
5 Providing, fitting and testing of 96 mm analogue ammeters with selector switches and CT coil all complete 4 Nos.
6 Providing, fitting and testing of 96 mm analogue voltmeters with selector switches all complete 4 Nos.
7 Providing, fitting and testing of analogue frequency meter (45–55 Hz) 1 No.
8 Providing, fitting and testing of 125 mm analogue ammeters with selector switches and CT coil all complete 1 Nos.
9 Providing, fitting and testing of 125 mm analogue Voltmeter with selector switches all complete 1 Nos.
10 Providing, fitting and testing of LED indications for phase for main control panel. (15 No)
11 Replacement of damaged 1.5 sq mm copper control wiring with new one in main control panel with the help of skilled labor tools and tackles for the completion of work (15 mtr).
12 Providing, fitting and testing of PVC wire ducts, ferrules, tinned copper lugs and terminal blocks.
13 Painting of Main Control Pannel by way removing/scrubbing old existing color with the help of skilled painter, tools and tackles and then applying one coat of epoxy primer and two coats of epoxy paint (preferable make: Nerolac, Berger, Asian, equivalent), All tools and tackles, skilled labor required for the completion of work shall be arranged by the firm itself.
14 Replacement of damaged Bus bar tapping, PVC wire ducts, ferrules, tinned copper lugs and terminal block in main control panel with new one with the help of skilled labor for the completion of job.
Note: During the installation of new ACBs in main control panel any modification/New bus bar etc required during execution of work shall be arranged by the firm itself. | 1 | Job | 6,97,000 | ₹6,97,000 |
| 1.06 | Copper Cable: Supply, installation, testing & commissioning of single core 630 sq mm XLPE insulated, and PVC outer sheathed copper cable to be laid from main control panel to voltage stabilizers to starters to 20 cusec pumping units . The job also includes the fitting of cable along the walls of the Pump house by using clamps and laid underground where ever necessary as per site requirement. The cable shall be thimble at each end with copper thimble using a crimping tool. The cable shall be of following specification Voltage: 1100V Insulation: XLPE insulated, PVC double sheathed Make of cable: Gloster/Havells/ Finolex /National/as approved in EOI SE Mechanical Kashmir Thimble: Dowell Make. | 100 | Mtr | 20,345 | ₹20,34,500 |
| 1.07 | Supply, Installation, Testing & Commissioning of 600 KVA capacity copper wound voltage stabilizer at LIS Sheeri I of below mentioned specifications:
i. Capacity: 600 Kva Three phase
ii. Type: Manually controlled
iii. Cooling: Oil Cooled
iv. Make: Reputed make
v. Input Voltage: 300-500 volts (phase to phase),
200-270 volts (phase to Neutral)
vi. Output Voltage: 415 volts +10 % (phase to phase)
240 volts + 10 % (phase to Neutral) Suitable for: 100 % BALANCED
vii. Application: Indoor type
viii. Phase: 3-Ph, 4 wires
ix. Frequency: 50 HZ + 3 %
x. Response time: Instantaneous (millisecond)
xi. Mode of operation: Manual
xii. Suitability: Suitable for all Power Factors
xiii. Duty Cycle: Continuous 24 Hrs.
xiv. Efficiency: 98 % at full load.
xv. Losses at No Load: As per standards
xvi. Losses at Full Load: As per standards
xvii. Laminations used: Imported low Losses CRGO
xviii. Laminations – M4 Grade
xix. Class of Insulation: Class-A. Greater Than 6 M ohms
xx. Break Down Strength: 500-volt AC for 1 minute (for whole unit)
xxi. Transformer winding: Copper strip.
xxii. Container: 2-3mm thick MS steel with enameled paint
xxiii. Voltage regulator: 8/6 steps with suitable amperage
ADDITIONAL FEATURES:
1 Earth fault protection.
2 High Grade CRGO Lamination.
3 99.9% pure copper.
4 High efficiency.
INSTRUMENT ACCESSORIES:
1 Main “ON” indicating lamps in each phase.
2 Voltmeter with input & output sides.
3 Selector switch 03 no.
4 Transformer Oil up to required level of the stabilizer
Make = Castrol , Servo, Hp conforming to IS 335 The Toil shall be filled in stabilizer at site
GENERAL ARRANGEMENTS:
The container shall have cooling radiators & mounted on sliding wheels, other fittings would include as follows: Lifting Lugs, Earthing Terminals-2 nos. Oil Level indicators, Rating Plate, Name plate, draining valve at appropriate place. The Job also include painting of voltage stabilizer by way applying one coat of epoxy primer and two coats of epoxy paint (preferable make: Nerolac, Berger, Asian ,equivalent ), All tools and tackles, skilled labor required for the completion of work shall be arranged by the firm itself. | 1 | Job | 8,00,000 | ₹8,00,000 |
| 1.08 | Dismantling of 400 kva voltage stabilizers, opening top lid, taking out the voltage regulator and Core, checking all connection lead insulation and providing and fitting of new insulation wherever required for connection leads, refitting of voltage regulator and assembling voltage stabilizer properly after proper servicing/ repair. The job involves welding work to oil tank at leakage spots to make it leak proof. Connecting of leads of all incoming and outgoing connections and testing of Voltage Stabilizer at site on full load. The Job also include providing and fitting of new Voltmeter, Ampere meter having range (0-500) selector switch, phase indicating lamp, control wiring, bush rods both input and output. The Job also involves providing and filling of transformer oil / Type II inhibited oil conforming to IS 335 for Stabilizer up to required level and testing on full load. (Preferred make: Power oil/ Indian Oil Servo/ HPCL). The Job also include painting of voltage stabilizer by way removing/scrubbing old existing color with the help of skilled painter , tools and tackles and then applying one coat of epoxy primer and two coats of epoxy paint (preferable make: Nerolac, Berger, Asian), All tools and tackles, skilled labor required for the completion of work shall be arranged by the firm itself. | 1 | job | 1,55,000 | ₹1,55,000 |
| 1.09 | Supply, installation, testing & commissioning of 425 HP capacity fully automatic auto transformer starter of below mentioned specification.
1 Providing, fitting and testing Main contractor assembly having a range not less than 1250 A, Make L&T/ABB/schneider/Equivalent make as approved in EOI of SE mechanical circle Kashmir I&FC Department Srinagar. (01 No)
2 Providing, fitting and testing Delta contractor assembly having a range not less than 630 A, Make L& T/ABB/schneider Equivalent make as approved in EOI of SE mechanical circle Kashmir I&FC Department Srinagar. (01 No)
3 Providing, fitting and testing Star contractor assembly having a range not less than 400 A, Make L&T/ ABB/schneider Equivalent make as approved in EOI of SE mechanical circle Kashmir I&FC Department Srinagar.(01 No)
4 Providing, fitting and testing Thermal overload relay of suitable capacity MN series of L&T/ABB Equivalent make as approved in EOI of SE mechanical circle Kashmir I&FC Department Srinagar.(01 No)
5 Providing, fitting and testing Motor protection relay of suitable capacity MN series of L&T/ ABB / Equivalent make as approved in EOI of SE mechanical circle Kashmir I&FC Department Srinagar. (01 No)
6 Providing, fitting and testing Double timer assembly (electro pneumatic) having a range of 0 -60 second of L& T /ABB / Equivalent make as approved in EOI of SE mechanical circle Kashmir I&FC Department Srinagar. (01 No)
7 Providing, fitting and testing Single phase preventer of suitable capacity with selectable under & over voltage of L&T/ABB Equivalent make as approved in EOI of SE mechanical circle Kashmir I&FC Department Srinagar.(01 No)
8 Providing, fitting and testing Control MCB of suitable capacity amperes range.
9 Providing, fitting and testing Electrolytic copper bus bar strips of suitable size & capacity duly tinned air insulated and mounted on suitable Bakelite insulation
10 Providing, fitting and testing One number Digital/Amalog voltmeter 0-500V & one no. Ammeter digital/Analog type along with 3 No. CT coils having range 0- 500A fitted in each bus bar.Make L&T/ABB/AE/EE make.
11 Providing, fitting and testing ON/OFF LED push button type RED & Green color of 5A-415V, 50HZ, L&T/ABB/Equivalent make.
12 Providing, fitting and testing Frequency Meter, C.T coils and other accessories as per requirement/Design should be included.
13 Providing, fitting and testing Complete internal wiring of the control panel for operating equipment by using adequate capacity single core copper wire of Havells/polycab/equivalent make. The wiring shall be fitted with plastic washers for identification of each wire at various joints.
14 Panel for housing of all the equipment fabricated out 14 SWG gauge sheet metal of adequate size to house all the equipment with enough space to reach out to any equipment for repair/replacement. The panel shall have hinged door at the front with proper locking arrangements. The housing shall be provided with a base frame fabricated out of ISMC & welded /bolted at the bottom. The housing shall be provided with necessary cut out spaces for fitment of meters, push buttons actuator incoming & out coming connections. The panel shall be free standing, floor mounted, totally enclosed, vermin proof, the panel shall be RAL 7035/7032 Powder coated. The panel shall have air vents for proper ventilation. Auto Transformer coil shall be made out of 1st class electrolytic copper strips having suitable capacity for the above starter. The coil shall be provided with F class insulation tape. The coil shall have tapings taken out at 50%, 65% and 80% The Core of the auto transformer shall be fabricated out of 1st class silicon 90 grade pota sheets cut to size and then tightening of the same adequately. The auto-transformer tank shall be fabricated out of MS sheet of suitable thinness to make the tank leak proof. which shall have a lid at the top provided with holes for tightening the same of the tank. The tank shall have to be fitted at back side of the starter. o. Providing and fitting of high-grade low viscosity transformer oil (Make Castrol/Servo/ Hp) conforming to IS 335 up to the required level in the tank so that the auto- transformer coils get fully immersed. Adequate capacity electrolytic copper bus strips or cables shall be fitted for internal connections. | 1 | job | 6,50,000 | ₹6,50,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.68 MB
BOQ_1100071.xls
BOQ • 0.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .