Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹27.5 LAccepted-AOC HAVELI FALIYA NALIYA KUTCH 370 655 | KACHCHH | GUJARAT | 370655 | ₹27.5 L | L-1 | Accepted-AOC AOC |
| 2 | L-2₹35.8 L+₹8.3 L (30.1%)Rejected-Finance SHOP NO 02 DADA COMPLEX NEAR DENA BANK NALIYA TAL ABDASA KUTCH GUJRAT 370 655 | KACHCHH | GUJARAT | 370655 | ₹35.8 L+₹8.3 L (30.1%) | L-2 | Rejected-Finance Other than lowest Bidder |
| 3 | L-3₹38.7 L+₹11.1 L (40.4%)Rejected-Finance 103 HARIAKSH PLAZA HOSPITAL ROAD BHUJ KUTCH GUIARAT 370001 | BHUJ | KUTCH | GUJARAT | 370001 | ₹38.7 L+₹11.1 L (40.4%) | L-3 | Rejected-Finance Other than lowest Bidder |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
21 Dec 2023, 6:00 pmClosed
GE AF Naliya No 1
GE Air Force Station Naliya No 01
REPAIRS MAINT AND CALIBRATION OF RMU VCBS WITH REPLACEMENT OF UNSERVICEABLE HT UG CABLE WITH CONNECTED WORK AT AF STN NALIYA UNDER GE AF NALIYA
2023_MES_629442_1
8927/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Naliya
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE AF Naliya No 01
₹60,000
Yes
7 Mar 2024
23 Nov 2023
29 Dec 2023
23 Nov 2023
21 Dec 2023
8 Dec 2023
Amount
M&L for maintenance and servicing of RMU 11 KV, 400/ 630 /1200 Amps by cleaning of all mechanisum parts and bushing tightening of all connections, checking , control wiring, servicing etc, refixing the RMU its original position including proper setting of manual/ auto motorize operation of RMU, checking/setting of tripping system, etc complete all as specified and directed. Note:- Maintenance to be carried out by authorised person and test certificate shall be furnished
M&L for Maintanance, Calibration of VCB relay by injecting High voltage through CTS checking the over load system of VCB up to 90 % rated load and artificial fault creation and setting of relay by 10 to 15 % of rated load removing u/s overload and earth fault relay including connection with power pack, opening out the trolley, checking the operation of VCB mechanically and electrically through shunt trip coil including energizing of springs automatically, checking of TNC switch including testing and commissioning complete all as directed. Note:- Maintaenance, Calibration to be carried out by authorised person and test certificate shall be furnished during payment.
Replacement of complete power pack unit of 220 V/110 V AC input and 110 V/24V DC output fixed inside the HT VCB/RMU unit complete for back up of the tripping system of Circuit Breaker etc. complete all as specified and as directed.
Supply, install and testing in replacement of digital four pole non directional Microprocessor based IDMTL 3 over current +1 Earth fault with instantaneous element relay with high set & Aux. supply 20-110 volt DC as per existing make and model complete all as specified and directed.
M&L for replacement of automatic spring charge motor of the Vacuum circuit breaker of existing make and model complete all as specified and directed.
S & F in replacement of 11 KV current transformer (CTs) for HT panels indoor type resin cast epoxy type of 13.1 KA/sec having ratio 60/5+5 Amps suitable for metering and protection of panels including control cables as per site requirement and fixing on bus bar section having class of accuracy 5P10, burden 15 VA. complete all as directed
S & F in replacement PT unit three phase three limb, epoxy type up to 11 KV draw out type single ratio having primary 11 KV & secondary voltage 110 volts 200 VA class I, including necessary bus bar connection & wiring for metering after disconnecting of HT supply from HT VCB of capacity 630 Amps complete all as directed.
S&F in replacement of vacuum interrupter as per existing make and model and suitable for 11 KV HT VCB 11 KV 630/800A capacity.
S&F in replacement fixed contact block as per existing make and model and suitable for V.C.B 11 KV 630/800 Amps capacity complete all as specified and as directed.
S&F in replacement moving contact block as per existing make and model and suitable for V.C.B 11 KV 630 /800 Amps capacity complete all as specified and as directed.
S&F in replacement of motor & gear assembly 220Volt AC motorised mechanism as per existing make and model and suitable for V.C.B 11 KV 630/800 Amps capacity including testing & putting on load complete all as specified and as directed.
S&F in replacement of closing coil assembly 24/110V DC as per existing make and model and suitable for HT VCB 11 KV 630/ 800A capacity complete all as specified and as directed.
S & F in replacement of tripping coil assembly 24/110V DC as per existing make and model and suitable for HT VCB 11 KV 630/800A capacity complete all as specified and as directed.
S & F in replacement of auxiliary switch (6 No+6NC) as per existing make and model and suitable for HT VCB 11 KV 630/800 Amps capacity complete all as specified and as directed.
M&L for tracing out HT cable fault through HT fault locator machine by HT expert and testing of HT cable through megger and repair the same complete all as specified and as directed. Note:- The cost of the earth work, equipment and person required for locating fault is inclusive in unit rate (ii) Joint of cable will be measured and paid separately under relevant item.
Labour only for shifting of RMU/VCBs panel complete from one place to another place by disconnecting its all electrical connections transporting though their own veh and loading unloading etc. Note- The cost of transporting vehicle and crane is deemed to be included in unit rate.
Supply, jointing and testing of cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 50 sqmm to 95 sqmm complete all as Specified and directed.
Supply, jointing and testing of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of 50 to 95 Sqmm complete all as specified and directed.
Supply, jointing and testing cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 50 to 95 sqmm. complete all as specified and directed.
Supply, jointing and testing of cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 120 to 185 sqmm complete all as directed.
Supply, jointing and testing of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of 120 to 185 Sqmm complete all as specified and directed.
Supply, jointing and testing cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminum conductor cable of size 120 to 185 sqmm complete all as specified and directed.
M& L for cutting under the road / pavement / hard standing or in any other situation with the help of manual labour for crossing of U/G cable through it and making both the end good complete all as specified and directed .
Supply and laying galvanised steel water tubing, light grade, IS-1239 marked with all fittings ISI marked and laid in trenches under roads, through drains, fixed to poles/walls with required size flat iron clamp bolts, nuts and washers, for cable protection of 100 mm dia, including taking out old/existing pipes, complete all as specified and directed.
Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc. 10sqm on plan and not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and directed.
Taking out HT UG cables of 95/120 Sqmm by excavation and earth work in any type of soil, removing bricks or PCC cover of any size, stacking serviceable cable for reuse complete all as specified and directed NOTE:- (i) Excavation, Joints & Jointing materials, new cable, additional bricks/PCC Covers, sand shall be measured & paid for separately under relevant item.
Supply & lay in replacement of HT 11 KV 3 core 95 Sqmm cable in trenches/fixed to poles/wall, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable( HT ), heavy duty with aluminum conductor, 11000 volts (earthed) grade 95 Sqmm x 3 core all as specified and directed. Note : (i) Excavation, earthwork, cable joints, sand cushioning & cable cover shall be measured and paid separately if required.
Labour for re-laying the serviceable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminum conductor, 11000 volts Earthed, grade cross sectional area 95/120 sqmm 3 core in trenches/fixed to poles/wall, complete all as specified and directed. Note : (i) Excavation, earthwork, cable joints, sand cushioning & cable cover shall be measured and paid separately if required
M&L for sand cushioning for UG cables using dry sand, gently punning down all as directed and specified. Note : For measurement purpose punned thickness shall be considered
Supply and laying unreinforced precast concrete cable covers class HV type I, flat size 300x180x40 mm laid transverse to cable complete all as specified and as directed.
Labour for relaying of unreinforced precast concrete cable covers class HV type I, flat size 300x180x40 mm laid transverse to cable complete all as specified and as directed.
Returning filling in soil and including spreading leveling watering and well ramming in layers n.exc. 25 cm thick complete all as specified and as directed.
Removing excavated soil to a distance n.exc. 50 mtr and depositing where directed at a level n.exc. 1.5m above the starting points complete all as specified and as directed.
Supply, fabricate, testing and commissioning of factory made HT outdoor distribution panel board single door of size 1200mm x 1200mm x 800mm including locking arrangement cubical type dust and virmin proof, weather proof, aesthetical designed, IP54 degree of ingress protection, fabricated with 3mm thick CRCA sheet with front and rear opening including 3 strips of copper bus bar of 600 Amps current carrying capacity insulated with colour sleeves, porcelain/epoxy insulators 11000V, rail channel, cable entry, danger notice plate of 11000 Volt, angle iron frame of size 50x50x6mm and 60cm grouted in ground and 60cm above GL including necessary excavation, foundation, PCC etc. complete duly powder coated of approved colour all as specified and directed.
NEELKANTHA ASSOCIATE
Vijay Construction Co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .