Loading…
Loading…
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
30 Sept 2026, 6:00 pm
Garrison Engineer (AF) Naliya No. 1
Garrison Engineer (AF) Naliya No. 1 370655
REPAIR REPLACEMENT OF FIRE ALARM SYSTEM AT MOTHALA UNDER GE AF NALIYA
2026_MES_788843_1
8238/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
Air Force Station Naliya
As per tender documents
7 documents required · 7 mandatory
₹500
GE(AF) Naliya No. 1
₹20,000
Yes
11 Sept 2026
11 Sept 2026
2 Oct 2026
11 Sept 2026
30 Sept 2026
25 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing & Commissioning in repair of SFS1-CPU card of EST3x fire alarm panel with below specifications:
Voltage 24 VDC, Current: Standby 115 mA at 24 VDC Alarm 115 mA at 24 VDC
Relay outputs: Quantity 3 (alarm, supervisory, and trouble) UL type Common
Contact arrangement Form C Rating 30 VDC at 1 A resistive AUX power outputs: Quantity 2
Voltage 24 VDC, resettable or continuous Current 1.0 A each circuit, 1.0 A total Data network (RS-485)
Nodes 2 to 64 (requires optional network card) Performance class Class A or Class B
Wire type Twisted pair, 6 twists per foot, min.
Circuit length 5,000 ft. (1,524 m) between any three panels Circuit resistance 90 Ω, max.
Circuit capacitance 0.3 μF, max. Serial Port (RS-232) Annunciator port (RS-485)
Performance class Class B and Redundant Class B Baud rate 9600 and 38400
Wire type Twisted pair, 6 twists per foot, min. Circuit length 4,000 ft. (1,219 m)
Circuit resistance 90 Ω, max. Circuit capacitance 0.3 μF, max. Make: EST/Bosch/Honeywell. | 1 | Each | 100 | ₹100 |
| 2 | Supply, Installation, Testing & Commissioning in repiar of PS10-4B Power Supply board of existing Edwards Fire Alarm Panel (EST3x) 3X-SFS1R Red.
SMPS Specifications :
Mains voltage 94 to 264 VAC, 50/60 Hz
AC Input Current : Standby 1.5 amps, Alarm 3.0 amps. Brownout level 93 VRMS
Battery charging capacity 65 Ah max. Total Power : Voltage 24vdc
Standby Current : 88mA Alarm Current : 169mA
Supply Ratings : Current 10 amps (UL), 9.0amps (ULC). Output voltage: Special: 24 Vdc, Regulated: 24 Vdc Output current Special: 3 amps, Regulated: 1.5 amps.
Operating environment : Temperature 32 to 120 °F (0 to 49 °C) Relative humidity 0 to 93% noncondensing.
Make: EST/Bosch/Honeywell. | 1 | Each | 101 | ₹101 |
| 3 | Supply, Installation, Testing & Commissioning in repiar of 4X-LCD Display unit of EST3x fire alarm panel with below specifications:
Operating current:Standby Alarm 55mA 66mA
LCD display Backlit liquid crystal display 240 x 320 pixels 24 lines of 40 characters
Operating environment Temperature
Relative humidity
32 to 120 °F (0 to 49 °C)
0 to 93% noncondensing. Make:EST/Bosch/Honeywell. | 1 | Each | 102 | ₹102 |
| 4 | Supply, Installation, Testing & Commissioning in repiar of Loop card 3-SDC1 of EST3x fire alarm panel with below specifications:
Voltage 24 VDC
Operating current with fully loaded loop:
Standby 3-SSDC1 144 mA; 3-SDDC1 264 mA Alarm 3-SSDC1 204 mA; 3-SDDC1 336 mA
Smoke power 19.95 VDC max.1
Circuit: Configuration Class B, Style 4, DCLB; Class A, Style 6, DCLA Capacity 125 Signature Series detectors and 125
Signature Series modules per SLC Resistance 100 Ω with 250 devices Capacitance 0.5 μF max.
Wire size 12 AWG (1.5 mm²) max.
Termination Removable plug-in terminal strips on the SFS1-CPU main board and Signature module
Operating environment
Temperature 32 to 120 °F (0 to 49 °C)
Relative humidity 0 to 93% noncondensing. Make: EST/Bosch/Honeywell. | 1 | Each | 103 | ₹103 |
| 5 | Supply, Installation, Testing & Commissioning in repiar of 3X-NET Network Card with the ability to network up to 64 nodes on an EST3 network.
The card must support Class B, Class A, and Class X wiring.
The 3X-NET adapter card provides two independent RS 485 circuits: one for network data communications and one for digital audio communications.
Make: EST/Bosch/Honeywell. | 1 | Each | 104 | ₹104 |
| 6 | Supply & Fix in repiar 12V/7AH SMF Battery for backup in case of power failure. Make : Exide/Solance/Amaron. | 3 | Each | 105 | ₹315 |
| 7 | Supply, Installation, Testing & Commissioning in repiar of Programming card for programming of detectors and other devices in FACP Comm.Interface: USB interface Comm.Distance <15m <5m Baud Rate 2400bps Ambient Temperature 0℃~+40℃ Relative Humidity ≤95%, non condensing. Make: GST, Morley IAS, Honeywell. | 1 | Each | 106 | ₹106 |
| 8 | Supply, Installation, Testing & Commissioning in repiar of RS485 TO RS232 AND VICE VERSA PROTOCOL CONVERTER WITH BELOW SPECIFICATIONS: SUPPLY: SINGLE PHASE 230V AC +/- 10% INPUT: 2 WIRE RS485 OUTPUT: RS232C ISOLATION: 1000V DC OPTICAL ISOLATION BETWEEN INPUT AND OUTPUT CABINET: DIN RAIL MOUNT, ABS MOULDED 12 TERMINAL BOX OF SIZE 70*60*114 MM (H*W*D) | 1 | Each | 107 | ₹107 |
| 9 | Supply, Installation, Testing & Commissioning in repiar of Process Indicator with retransmission output for monitoring of temperature and humidity (to be installed in RTU panel). Make: MULTISPAN/Radix/Masibus | 1 | Each | 108 | ₹108 |
| 10 | Supply, Installation, Testing & Commissioning in repiar of RTD/HUMIDITY SENSOR FOR THE MEASUREMENT OF ROOM TEMPERATURE WITH INSTALLATION ACCESSORIES (TO BE INSTALLED INSIDE ROOM TO MEASURE TEMPERTURE). Make –Waree,RADIX,Wika | 1 | Each | 109 | ₹109 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
Tender8238.pdf
Tender Documents • 0.96 MB
BOQ_884234.xls
BOQ • 0.49 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .