Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.6 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹30.8 L+₹21,515.08 (0.70%)Rejected-AOC 8 34A FATHIMAPURAM TAMILNADU | TAMILNADU | L2 | Rejected-AOC L2 | |
| 3 | Rejected-Technical | - | Rejected-Technical PQ criteria not meeting |
Tender Value
₹31.3 L
EMD Value
₹50,000
Closing Date
31 May 2023, 5:00 pmClosed
Chief Executive Officer
Park Centre, Technopark Phase I Campus, Thiruvananthapuram,-695581
ELECTRIFICATION WORKS OF PLUG AND PLAY MODULES PROPOSED AT THE ROOFTOP OF BHAVANI BUILDING, TECHNOPARK PHASE-I CAMPUS.
2023_ETPK_576931_1
ETPK/PH-I/2023-24/E-01
Open Tender
Electrical Works
Item Rate
50 days
Technopark Phase I campus
Refer tender document
3 documents required · 3 mandatory
₹2,950
₹50,000
Park Centre,Technopark Phase I Campus
29 Nov 2023
18 May 2023
2 Jun 2023
18 May 2023
31 May 2023
22 May 2023
22 May 2023
Amount
INTERIOR ELECTRIFIICATION WORKS(PART-A)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for three light point controled with one switch with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for Four light point controled with one switch with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed PVC conduit as required.
2Rx1.5sqmm with 1R 1.5sqmm Green wire for earthing
2Rx2.5sqmm with 1R 1.5sqmm Green wire for earthing
2Rx4sqmm with 1Rx1.5sqmm Green wire for earthing
4Rx4sqmm with 1Rx1.5sqmm Green wire for earthing
Supplying and drawing of UTP 4 pair CAT 6 LAN cable in the existing surface/ recessed PVC conduit as required.
Cat 6 cable
Supplying and fixing of 20mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of 25mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of 20mm of PVC flexible conduit along with accessories in surface
Supply and Fixing of 20mm ISI medium class PVC casing and capping of following diamensions along with accessories through wall in surface/ceiling
Supply and Fixing of 25mm ISI medium class PVC casing and capping of following diamensions along with accessories through wall in surface/ceiling
Supply and fixing of LED recess mounted (round type) down light with minimum lumen outout of 1200 Lumen, PC defuser, CRI>=100,PF>=0.95 ,CCT >=5700 K ,Efficacy >=100 lm/W
Supply and fixing of LED recessed ceiling fixture 600X600mm with a minimum lumen output of 2880 lumens ,CRI >= 90,PF>=0.95, ,CCT>= 5700K, Efficacy>=110 lm/W
Supply and Installation of Independent plug point with 6A 3 pin plug socket controlled by 6A switch with suitable modular plate, GI box/PVC box in recess/ surface .
Supply and installation of combined modular plug point for 6A, 3 pin plug socket controlled by 6A modular switch in the same switch board with suitable modular plate, GI box/PVC box in recess/ surface
Supply and Installation of Independent plug point with 16A plug socket controlled by 16A switch with suitable modular plate ,GI box/PVC box in recess/ surface .
Supply and Installation of Computer Socket(R-J45 jack) with suitable modular plate , GI box/PVC box in recess/ surface.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, IP 43, dust protected, duly powder painted, inclusive of 100 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required.
3P 8W VDB Double Door
3P 12W VDB Double Door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections,powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
3P 6W DB Double Door
3P 8W DB Double Door
Supplying and fixing following way, single pole and neutral, IP 43, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
1P 6W DB Double Door
1P 8W DB Double Door
Supplying and fixing following 40 A double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 32A, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required
Supplying and fixing 32A, four pole, 415 V, isolator with metallic enclosure with connections, testing and commissioning etc. as required
Supplying and fixing following rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following pole in the existing MCB DB complete with connections, testing and commisioning.
5A to 32A ,SP MCB
5A to 32A ,DP MCB
MCB Blanking plate
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts,RCBO, having a sensitivity current 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, RCBO, having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supply & laying of Following XLPE Aluminium armoured power cable (A2XFY), conductors of best conductivity aluminium 1.1kV grade of the following sizes in the existing TRAY/RCC/ HUME / STONE WARE/ GI/ DWC pipe / Concrete trench/Clamping on wall etc. as required.
2x06 Sqmm A2XFY Cable
4x10 Sqmm A2XFY Cable
4x16 SqmmA2XFY Cable
3.5x35 qmm A2XFY Cable
Supply and providing end termination for following XLPE AL armoured cable (A2XFY) including cost of cable gland(Siemens type/tropdor type compression gland) , lugs, earthing, crimping etc
4x10 Sqmm A2XFY Cable
4x16 SqmmA2XFY Cable
3.5x35 qmm A2XFY Cable
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Supply, laying/fixing of 6 SWG GI for earthing of switchboard and jointing as per IS:3043 / 87 in open trench / walls / pulling through pipes etc as required.
SUB PANEL
Incomer:
Outgoings:
160A,25kA, 4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-1 Nos 125A,25kA, 4P,Thermal magnetic type MCCB with all accessories including spreader link and extended rotary handle-2 Nos 3-phase TOD meter,class 0.5s with RS 485 communication port- 3 Nos 3Ph Direct kWH meter 10-60A- 3 Nos 60/5A ,5VA cast resin type,Class 0.5s CT - 9 Nos
APFC PANEL- 40kVAR
Design, supply, erection, testing and commissioning of cubicle type floor mounting made out of14SWG, MS sheet enclosure with 250A, 415Volts, 3 phase,not less than 25kA, TP&N,50 Hz Aluminium busbars, single busbar system, cable chamber,Voltmeter,Ammeter, protection relays, with necessary interconnection, painting, earthing,power factor controlloer,APFC relay & CT with ratio 50/5A-10VA (cast resin) etc.comprising of the following, the board shall be fabricated as per the SLD
Incomer:
160A, 4-pole 25 kA, Motorised MCCB, Thermal magnetic type, variable settings ,extended rotary handle,Spreader Terminals, etc are required- 1 nos
Outgoings:40kVAR
1 set of 25 KVAR MPP (Metalised Poly Propylene) Capacitor with 63A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 25 KVAR as required. 1 set of 15 KVAR MPP (Metalised Poly Propylene) Capacitor with 32A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 15 KVAR as required. 1 set of 10 KVAR MPP (Metalised Poly Propylene) Capacitor with 32A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 10 KVAR as required. 1 sets of 5 KVAR MPP (Metalised Poly Propylene) Capacitor with 32A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 5 KVAR as required. 1 sets of 3 KVAR MPP ( Metalised Poly Propylene) Capacitor with 32A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 5 KVAR as required. 1 sets of 2 KVAR MPP ( Metalised Poly Propylene) Capacitor with 32A,TP, 25kA MCCBs,Cap.Duty Contactors,7% detuned Al reactor with switching steps in the rating of 2 KVAR as required. With necessary Aluminium busbars, interconnections, providing Digital Voltmeter,Ammeter , RYB and “ON / OFF / TRIP" indicating lamp at incomer, control PT, CTs, MPCBs and MCB and APFC Relay etc. and all other necessary accessories as per the specification/SLD. The APFC panel shall be capable of disconnection in case the DG supply is sourced from ATS. Necessary arrangements including wiring, DG supply sensing, Contactors and any other accessories required should be done for auto cutoff during DG supply and should return to normal operational condition after EB supply restoration. Each KVAR capacitor in a separate compartment with necessary ventilation arrangemnts or weld mesh arrangements as required by the KSEI guidelines.
Providing and fixing following rating and breaking capacity and pole MCCB with all accessories including extended rotary handle, spreader links etc in existing cubicle panel board by dismantling the existing switchgear including drilling holes in cubicle panel, making connections, necessary modification in panel, busbar etc. as required.
200 Amp, 36 KA
Supply & laying of Following A2XFY (Aluminium) power cable, conductors of best conductivity aluminium 1.1kV grade of the following sizes in the existing TRAY/RCC/ HUME / STONE WARE/ GI/ DWC pipe / Concrete trench/Clamping on wall etc. as required.
3.5x185 Sqmm A2XFY (Aluminium) Cable
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5x185 Sqmm XLPE Al Cable
Supply and erection of vertical and horizontal type cable trays and cable supports fabricated out of MS angles (ISA) and MS flats with sufficient width and spacing between successive cross members and supported at adequate spacing. The cable trays and supports shall be painted with two coats of Zinc Chromate primer and two coats of enamel paint. (Size as specified by Technopark as per site conditions)
Supply and providing 3 mm thick sythetic type and 1 m wide electrical grade chequered type rubber mat to withstand 3.3 kV dielectric strength conforming to IS 15652 (2006).
Supply of CO2 Extinguisher 4.5Kg, Fire rating of 55B, PESO approved Aluminium cylinders with CCOE certification, IS 15683:2018 standard, Certifications from BIS, EN, CE, ISI and date of manufacture imprinted on cylinder, coated with High Glossy PU Paint, anti corrosive make, Discharge hose with the conductive wires to dissipate the static charge generated during CO2 discharge, Carbon dioxide gas having a purity of 99.5% and conforming to IS15222, “D” handle for ease of carrying and operator safety, Cold impact extrusion can, Used-Unused Mechanism, Squeeze Grip, Gross Weight 11.16 Kg, Empty Weight 6.66Kg, Can Height 860mm, Diameter 140mm, Discharge time minimum 8 Seconds, Controllable discharge mechanism, Range minimum 2m, two piece floating spindle valve with a handwheel to operate, venyl sticker/label with all the details including operational instructions, 10 years warranty
Preparation of all drawings submitting and getting approval from Kerala State Electrical Inspectorate by a Licensed A Class Electrical Contractor for the electrification of proposed modules, load additions and modification works which include current and past additions in the existing Transformers (11kV/433V- 1250kVA 1250kVA,1600kVA), DG's (500kVAx2nos, 625kVAx2nos) HT & LT panels in substatons, submitting of Completion certificates and arranging inspection, getting sanction and energization certificate etc, providing and fixing neatly Laminated Electrical schemes and layout for Bhavani Substation.
Fathima Engineering Co. Pvt. Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .