| Sl No | Description | Qty | Unit | M/s Bombay Novelty Stores L2 | Abhishek Enterprises L3 | JYOT ENTERPRIES L1 |
|---|---|---|---|---|---|---|
| 1.00 | Taking down carefully existing unserviceable aluminum/copper point wiring (light, fan, socket or power) of any description & in any position complete including all fittings & fixtures such as switches, ceiling roses, pendants, regulators, socket, light fittings, lamp holders etc including taking out and removing serviceable fittings/fixtures and making good the disturbed surface of walls, floors, ceiling etc. to match with the existing surfaces complete all as specified and directed. | 530 | Point | 20 ₹10,600 Lowest | 50 ₹26,500 | 20 ₹10,600 Lowest |
| 2.00M&L for point wiring with using 1.5 Sqmm (nominal area) with multi standard copper conductor, single core, FRLS PVC insulated & unsheathed cable, 1100 volts grade , ISI -694 marked with valid CML No in and including medium grade, PVC concealed conduit in stone masonry of any thickness of dia not less than 20 mm and conduit accessories, ISI marked with valid CML no (IS-9537-19 for conduit and IS :3419:19765 for conduit accessories )concealed in wall with mild steel/ pressed steel sunken box (with earth dolly) of 1.6mm thick of suitable size, duly painted with two coats of anti corrosive paint/aluminium paint over a coat of red oxide primer externally covered with modular cover and plate for fixing of modular switch,socket etc including PVC insulated multi stranded copper conductor to commom earth and connecting to earth dolly complete all as specfied and dircted for the following:- NOTE :- 1. The complete wiring installation shall be carried out in accordance and conformity with IS 732:1989 "code of practise for electrical wiring(latest version). 2. The unit rate aganist item of PVC concealed conduit point wiring includes for MS pressed steel sunken box for modular wiring GI sunken box duly painted with two coats of anti corrosive paint/black bituminous paint externally and two coated of aluminium paint over a coat of red oxideprimer internally for fixing switches,regulator, socket outlet etc with modular plate & box ISIS marked. 3.All screws,fasteners ,bolts,nuts & washer etc shall be of cadmium plated, The cost of which deemed to be included in the unit rate. 4.The complete wiring installtions shall be tested on completion as specfied in particular specfications. 5.The cutting/leaving , forming chases shall be done with electric cutter and not by chiselling. 6.Cutting chases in stone masonry wherever shall be deemed to be included in unit rate. 7.The completed wiring Quoted rate shall be deemed to include the making good the disturbed surface for concealed with CM 1:4 cement motor including finishing the surface to match with the existing surface. 8. Fittings like modular switches, sockets, regulators, lamp holders, light fittings shall be measured and paid for separately under appropriate item of Schedule `A'. | ||||||
| 2.01 | One light/buzzer point controlled by one; one way switch complete all as specified and directed. | 100 | Point | 680 ₹68,000 | 650 ₹65,000 | 547 ₹54,700 Lowest |
| 2.02 | One fan/exhaust fan point controlled by one, one way switch complete all as specified and directed. | 40 | Point | 680 ₹27,200 | 650 ₹26,000 | 547 ₹21,880 Lowest |
| 2.03 | One 3 pin socket out let 5 amp (independent) point controlled by one; one way switch complete all as specified and directed. | 30 | Point | 680 ₹20,400 | 650 ₹19,500 | 547 ₹16,410 Lowest |
| 2.04 | One 3 pin socket out let 5 amp point on the (same board) with other switches complete all as specified and directed. | 15 | Point | 160 ₹2,400 | 500 ₹7,500 | 140 ₹2,100 Lowest |
| 3.00 | All as per item No. 2 here-in-before but with 2.5sq mm size FRLS single core pvc insulated and unsheathed 1100 volts grade single core stranded (multistrand) copper conductor and 2.5sqmm PVC insulated and unsheathed cable 1100 volts grade with multistrand copper conductor as earth wire for 3 pin socket outlet 15 amp on independent board complete all as specified and directed. | 25 | Point | 780 ₹19,500 Lowest | 900 ₹22,500 | 790 ₹19,750 |
| 4.00M&L for point wiring with using 1.5 Sqmm (nominal area) with multi standard copper conductor, single core, FRLS PVC insulated & unsheathed cable, 1100 volts grade , ISI -694 marked with valid CML No in and including medium grade, PVC casing caping and it connected accessories, ISI marked with valid CML with PVC sunken box externally covered with modular cover and plate for fixing of modular switch,socket etc including PVC insulated multi stranded copper conductor to commom earth and connecting to earth dolly complete all as specfied and dircted for the following:- NOTE :- 1. The complete wiring installation shall be carried out in accordance and conformity with IS 732:1989 "code of practise for electrical wiring(latest version). 2. The unit rate aganist item of PVC concealed conduit point wiring includes for MS pressed steel sunken box for modular wiring GI sunken box duly painted with two coats of anti corrosive paint/black bituminous paint externally and two coated of aluminium paint over a coat of red oxideprimer internally for fixing switches,regulator, socket outlet etc with modular plate & box ISI marked. 3.All screws,fasteners ,bolts,nuts & washer etc shall be of cadmium plated, The cost of which deemed to be included in the unit rate. 4.The complete wiring installtions shall be tested on completion as specfied in particular specfications. 5.The cutting/leaving , forming chases shall be done with electric cutter and not by chiselling. 6.Including removing old unservicable wiring and finishing the surface to match with the existing surface. 7. Fittings like modular switches, sockets, regulators, lamp holders, light fittings shall be measured and paid for separately under appropriate item of Schedule `A'. | ||||||
| 4.01 | One light/buzzer point controlled by one; one way switch complete all as specified and directed. | 180 | Point | 800 ₹1,44,000 | 450 ₹81,000 Lowest | 450 ₹81,000 Lowest |
| 4.02 | One fan/exhaust fan point controlled by one, one way switch complete all as specified and directed. | 50 | Point | 800 ₹40,000 | 450 ₹22,500 Lowest | 450 ₹22,500 Lowest |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
6 Jun 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE ARMY BHUJ
BHUJ
CERTAIN EM WORKS TO VARIOUS BLDGS OF POCKET A B C D AND KHAVDA UNDER AGE EM OF GE ARMY BHUJ
2025_MES_707644_1
8320
Open Tender
Civil Works
Item Rate
270 days
GE ARMY BHUJ
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GE ARMY BHUJ
₹90,000
Yes
29 Aug 2025
10 May 2025
9 Jun 2025
10 May 2025
6 Jun 2025
23 May 2025
Amount
Taking down carefully existing unserviceable aluminum/copper point wiring (light, fan, socket or power) of any description & in any position complete including all fittings & fixtures such as switches, ceiling roses, pendants, regulators, socket, light fittings, lamp holders etc including taking out and removing serviceable fittings/fixtures and making good the disturbed surface of walls, floors, ceiling etc. to match with the existing surfaces complete all as specified and directed.
M&L for point wiring with using 1.5 Sqmm (nominal area) with multi standard copper conductor, single core, FRLS PVC insulated & unsheathed cable, 1100 volts grade , ISI -694 marked with valid CML No in and including medium grade, PVC concealed conduit in stone masonry of any thickness of dia not less than 20 mm and conduit accessories, ISI marked with valid CML no (IS-9537-19 for conduit and IS :3419:19765 for conduit accessories )concealed in wall with mild steel/ pressed steel sunken box (with earth dolly) of 1.6mm thick of suitable size, duly painted with two coats of anti corrosive paint/aluminium paint over a coat of red oxide primer externally covered with modular cover and plate for fixing of modular switch,socket etc including PVC insulated multi stranded copper conductor to commom earth and connecting to earth dolly complete all as specfied and dircted for the following:- NOTE :- 1. The complete wiring installation shall be carried out in accordance and conformity with IS 732:1989 "code of practise for electrical wiring(latest version). 2. The unit rate aganist item of PVC concealed conduit point wiring includes for MS pressed steel sunken box for modular wiring GI sunken box duly painted with two coats of anti corrosive paint/black bituminous paint externally and two coated of aluminium paint over a coat of red oxideprimer internally for fixing switches,regulator, socket outlet etc with modular plate & box ISIS marked. 3.All screws,fasteners ,bolts,nuts & washer etc shall be of cadmium plated, The cost of which deemed to be included in the unit rate. 4.The complete wiring installtions shall be tested on completion as specfied in particular specfications. 5.The cutting/leaving , forming chases shall be done with electric cutter and not by chiselling. 6.Cutting chases in stone masonry wherever shall be deemed to be included in unit rate. 7.The completed wiring Quoted rate shall be deemed to include the making good the disturbed surface for concealed with CM 1:4 cement motor including finishing the surface to match with the existing surface. 8. Fittings like modular switches, sockets, regulators, lamp holders, light fittings shall be measured and paid for separately under appropriate item of Schedule `A'.
One light/buzzer point controlled by one; one way switch complete all as specified and directed.
One fan/exhaust fan point controlled by one, one way switch complete all as specified and directed.
One 3 pin socket out let 5 amp (independent) point controlled by one; one way switch complete all as specified and directed.
One 3 pin socket out let 5 amp point on the (same board) with other switches complete all as specified and directed.
All as per item No. 2 here-in-before but with 2.5sq mm size FRLS single core pvc insulated and unsheathed 1100 volts grade single core stranded (multistrand) copper conductor and 2.5sqmm PVC insulated and unsheathed cable 1100 volts grade with multistrand copper conductor as earth wire for 3 pin socket outlet 15 amp on independent board complete all as specified and directed.
M&L for point wiring with using 1.5 Sqmm (nominal area) with multi standard copper conductor, single core, FRLS PVC insulated & unsheathed cable, 1100 volts grade , ISI -694 marked with valid CML No in and including medium grade, PVC casing caping and it connected accessories, ISI marked with valid CML with PVC sunken box externally covered with modular cover and plate for fixing of modular switch,socket etc including PVC insulated multi stranded copper conductor to commom earth and connecting to earth dolly complete all as specfied and dircted for the following:- NOTE :- 1. The complete wiring installation shall be carried out in accordance and conformity with IS 732:1989 "code of practise for electrical wiring(latest version). 2. The unit rate aganist item of PVC concealed conduit point wiring includes for MS pressed steel sunken box for modular wiring GI sunken box duly painted with two coats of anti corrosive paint/black bituminous paint externally and two coated of aluminium paint over a coat of red oxideprimer internally for fixing switches,regulator, socket outlet etc with modular plate & box ISI marked. 3.All screws,fasteners ,bolts,nuts & washer etc shall be of cadmium plated, The cost of which deemed to be included in the unit rate. 4.The complete wiring installtions shall be tested on completion as specfied in particular specfications. 5.The cutting/leaving , forming chases shall be done with electric cutter and not by chiselling. 6.Including removing old unservicable wiring and finishing the surface to match with the existing surface. 7. Fittings like modular switches, sockets, regulators, lamp holders, light fittings shall be measured and paid for separately under appropriate item of Schedule `A'.
One light/buzzer point controlled by one; one way switch complete all as specified and directed.
One fan/exhaust fan point controlled by one, one way switch complete all as specified and directed.
One 3 pin socket out let 5 amp (independent) point controlled by one; one way switch complete all as specified and directed.
One 3 pin socket out let 5 amp point on the (same board) with other switches complete all as specified and directed.
All as per item No. 4 here-in-before but with 2.5sq mm size FRLS single core pvc insulated and unsheathed 1100 volts grade single core stranded (multistrand) copper conductor and 2.5sqmm PVC insulated and unsheathed cable 1100 volts grade with multistrand copper conductor as earth wire for 3 pin socket outlet 15 amp on independent board complete all as specified and directed. (Note:- only one point per circuit)
Supply and fix in repair ceiling rose surface bakelite, three terminals, 230V AC with polycarbonate body complete all as specified and directed.
Supply and fix in repair modular switch 6 Amp, one way, 1 module, 230 volts AC circuit complete all as specified and directed.
Supply and fix in repair modular switch 16 Amp, one way, 1 module, 230 volts AC circuit complete all as specified and directed.
Supply and fix in repair modular bell switch 6 Amp, one way, 1 module, 230 volts AC circuit complete all as specified and directed.
Supply and fix in repair modular socket, 6 Amp, 2/3 pin combined, 2 module, 230 volts AC circuit complete all as specified and directed.
Supply and fix in repair switch socket modular , 6 /16 Amp, 2/3 pin combined, 2 module, 230 volts AC circuit complete all as specified and directed.
Supply and fix in repair modular fan regulator 120 W 2 module complete all as specified and directed.
Supply in repairs earth plug and socket, single pole, neutral sheet metal enclosures with a two pin, plug and socket 20Amp, 240 volts with and including one MCB, SP, 20A, 240 Volts complete all as specified and directed.
Supply and fix in multi music ding dong AC 230 Volt single pole complete all as specified and directed.
Supply and fix in repair lamp holder PVC / Polycarbonate type suitable for LED lamp fitting including LED 9watt bulb complete all as specified and directed.
Supply and fixing LED lights fitting 1x 20 W, 220V,AC decorative box type with driver, holder including LED tube light connecting upto PVC insulated 3 core flexible cable from ceiling rose to fitting drawn through in PVC flexible conduit including as per site requirement and 2 Nos of round or square PVC bolck for fixing of FTL fitting complete all as specified and directed.
Supply and fix in repair LED 10 W high quality indoor batten type tube light fitting with PC housing and as well light application CCT 6000 K, electrical connection of three core 0.5 sqmm copper flexible connection from ceiling rose to tube light fitting and with proper square box for fitting of tube light fitting complete all as specified and directed.
Taking down carefully MCBs, Metal clad plug, distribution boards/main switches of any type and size and S & F sheet metal enclosure powder painted for MCB DB SPN 08 way double door with IP-42 protection with Din rail and busbar complete all as specified and directed.
Taking down carefully MCBs, Metal clad plug, distribution boards/main switches of any type and size and S & F sheet metal enclosure powder painted for MCB DB SPN 04 way double door with IP-42 protection with Din rail and busbar complete all as specified and directed.
Taking down carefully MCBs, Metal clad plug, distribution boards/main switches of any type and size and S & F sheet metal enclosure powder painted for vertical type MCB DB TPN 04 way double door with IP-42 protection with Din rail and busbar complete all as specified and directed.
Taking down carefully MCBs, metal clad plug, distribution boards/main switches of any type and size and Supplying and fixing sheet metal enclosure powder painted for MCB DB vertical type TPN 4 way double door with dinrail and busbar with IP-43 protection with door earthing and isolated neutral bar and insulated busbar assembly including MCCB of 100 Amps complete all as specified and directed.
Supply & Fix in repair MCB TPN, 63 Amps in `C’ series having current rating 10 KA complete all as specified and directed.
Supply & Fix in repair MCB SPN, 6 to 32 Amps in `C’ series having current rating 10 KA complete all as specified and directed.
S&F in repair MCB single pole, 6 to 32 Amps in `C’ series having current rating 10 KA complete all as specified and directed.
Taking Down Old Unserviceable Submain wiring complete including all accessories and making good the disturbed surfaces complete all as specified and directed.
M & L for Sub main wiring with 2 runs of PVC insulated unsheathed multi stranded single core copper conducter 6 Sqmm drawn through PVC concealed conduit in stone masonry/brick masonry including accessaries with 6sqmm PVC insulated earth wire fixed to the existing wall with saddles, screws etc after removing the unserviceable wiring and connecting up complete all as specified and directed. (Note: 2 runs of cable and one run earth wire and concealed PVC conduit will be measured as one length.)
M & L for Sub main wiring with 4 runs of PVC insulated unsheathed multi stranded single core copper conducter 6 Sqmm drawn through PVC conduit/casing capping including accessaries with 6 sqmm PVC insulated earth wire fixed to the existing wall with saddles, screws etc after removing the unserviceable wiring and connecting up complete all as specified and directed. (Note: 4 runs of cable and one run earth wire and conduit/Casing & Caping will be measured as one length.)
M&L for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth lead wire 4mm dia, (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 15 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit and 40 mm thick precast RCC cover in 1 : 2 : 4 type B-1 with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle complete all as specified & directed. NOTE: Earth lead wire and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item and additional earth GI earth wire/protection pipe etc. if any required at site shall be measured and paid for separately under appropriate item of Schedule `A’
M & L for repair/replacement to light fittings, sockets, switches and bell and in any type and capacity and in any position including replacing unserviceable item or replacing whole fixture, fittings in internal electrification complete all as specified and directed.
Supply only LED lights fitting 1x 20 W, 220V,AC decorative box type with driver, holder including LED tube rod connecting upto PVC insulated 3 core flexible cable from ceiling rose to fitting drawn through in PVC flexible conduit including as per site requirement and 2 Nos of round or square PVC bolck for fixing of FTL fitting complete all as specified and directed.
Supply only LED 10 W high quality indoor batten type tube light fitting with PC housing and as well light application CCT 6000 K, electrical connection of three core 0.5 sqmm copper flexible connection from ceiling rose to tube light fitting and with proper square box for fitting of tube light fitting complete all as specified and directed.
Supply only fan regulator electronic, step type, socket non modular suitable for ceiling fans of any capacity, pre-wired 230 volts AC 50Hz supply 100Watt complete all as specified and directed.
Supply only lamp older PVC / Polycarbonate type suitable for LED lamp fitting complete with LED bulb 9W complete all as specified and directed.
Supply only Bell push, flush type 5 AMP AC 230 Volt single pole complete all as specified and directed.
Supply only socket outlet five pin, 5 Amps, flush type, 230 volts AC circuit, as per model at site complete all as specified and directed.
Supply only switch socket outlet combination, multipurpose, three pin, 15 Amps & three pin 5 Amps controlled by one switch , flush type, 230 volts AC circuit as per model at site complete and 4 holes on corner complete all as specified and directed.
Supply only switch flush type, 5/6 Amps, single pole, one way, 230 volts AC circuit complete all as specified and directed.
Supply only switch socket outlet combination, multipurpose, three pin, 5/6 Amps & three pin 5 Amps controlled by one switch , flush type, 230 volts AC circuit complete and 4 holes on corner complete all as specified and directed.
Supply only multimusic buzzer ding dong AC 230 Volt single pole complete all as specified and directed.
Supply and laying Rigid non-metallic PVC conduit but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc of size 25mm dia including drawing cable, wire through PVC conduit complete all as specified and directed.
Supply and laying Rigid non-metallic PVC flexiable protected corrugated conduit of size 20mm for loose wire near DB including drawing wire through conduit complete all as specified and directed.
Supply and laying in repiar of PVC casing and caping but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc of size 25mm dia including drawing cable, wire through PVC casing capping complete all as specified and directed.
Supply only 9W LED bulb complete all as specified and directed.
Supply only ceiling rose surface bakelite , three terminals, 230V AC with polycarbonate body complete all as specified and directed.
Supply only modular switch 6 Amp, one way, 1 module, 230 volts AC circuit complete all as specified and directed.
Supply only modular switch 16 Amp, one way, 1 module, 230 volts AC circuit complete all as specified and directed.
Supply only modular bell switch 6 Amp, one way, 1 module, 230 volts AC circuit complete all as specified and directed.
Supply only modular socket, 6 Amp, 2/3 pin combined, 2 module, 230 volts AC circuit complete all as specified and directed.
Supply only switch socket modular , 6 /16 Amp, 2/3 pin combined, 2 module, 230 volts AC circuit complete all as specified and directed.
Supply only modular fan regulator 120 W 2 module complete all as specified and directed.
supply only 15A Top suitable for exsiting board complete all as specified and directed.
Supply only ceiling rose PVC base complete all as specified and directed.
Supply and fix in repair plastic Modular surface mounted switch board of 1 module including modular front , back plate and plastic suken box complete all as specified and directed.
All as per above item No 53 but of 2 module complete all as specified and directed.
All as per above item No 53 but of 3 module complete all as specified and directed.
All as per above item No 53 but of 4 module complete all as specified and directed.
All as per above item No 53 but of 6 module complete all as specified and directed.
All as per above item No 53 but of 8 module complete all as specified and directed.
All as per above item No but of 10 module complete all as specified and directed.
Supply only MCB TPN, 63 Amps in `C’ series having current rating 10 KA complete all as specified and directed.
Supply only MCB SPN, 6 to 32 Amps in `C’ series having current rating 10 KA complete all as specified and directed.
S&F only MCB single pole, 6 to 32 Amps in `C’ series having current rating 10 KA complete all as specified and directed.
Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. with brushless direct current motor (BLDC) complete all as specified and directed.
Supply & fix Air Circulator fans 230 volts single phase oscillating 450 mm sweep suitable for wall mounting complete all as specified and directed.
Supply and fix electronic meters temper proof LCD display with polycarbonate cover 230 Volt , 10-60 Amps , accuracy class - I , 50 Hz,conforming to IS 13779,IP - 54 with parameters to show data , time,current reading , load , PF,voltage and KWH complete all specified and directed.
Supply and fix electronic meters temper proof LCD display with polycarbonate cover 415 Volt , 10-60 Amps , accuracy class - I , 50 Hz,conforming to IS 13779,IP - 54 with parameters to show data , time,current reading , load , PF,voltage and KWH complete all specified and directed.
Supply and fix PVC plastic MCB Box 2 way indoor PVC MCB enclosre box complete all as specified and directed.
Supply only LED spot (recessed) white light 15 W round type AC 90 - 260 volts including all accessories and fixing arrangement complete all as specified and directed.
Supply only LED spot (recessed) white light 12 W round type AC 90 - 260 volts including all accessories and fixing arrangement complete all as specified and directed.
Supply only LED spot (recessed) white light 6 W round type AC 90 - 260 volts including all accessories and fixing arrangement complete all as specified and directed.
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light,6000K complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core 0.5 sqmm flexible copper conductor cases of suitable size complete all as specified and directed.
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light,3000K complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core 0.5 sqmm flexible copper conductor cases of suitable size complete all as specified and directed.
Supplying and fixing 1100 Volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed flate 3 core cable of size 6 Sqmm complete all as specified and directed.
Supply and fix desert cooler, plastic body electric driven (single phase), having nominal air flow capacity of more then 4000 CFM ,Honeycomb cooling pads design, ice chamber,water level indicator,Four way air deflection,Easy Mobility on wheels including all necessary arragement complete all as specified and directed
Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300 mm sweep with,Double bearing, heavy duty motor, protective steel bird guard including making holes in any type of wall of any thickness and making holes in any type of wall, good finishing with PCC complete all as specfied and directed.
Supply and fix Water heater storage type, electric,capacity 25 litres.BEE 5 star rated,Digital display, anati scalant, Anti corrosive, Buit in safe shock module, 5 in 1 safety valve ,Knob control, 2 Nos of conncetor pipe including all fixing acessories complete all as specfied and directed.
Supply and fix exhaust fan, Plastic body AC single Phase. 230V of size 300 m sweep with, blades, and frame and louvers complete all as specified and directed.
Supplying and fixing 1100 Volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed flate 3 core cable of size 10 Sqmm complete all as specified and directed.
Labour only for repairing and attending the complaint of Split/WindowAC/ Water cooler/Refrigerator/deep freezer by highly skilled tradesman and carryout minor repair and making functional complete all as specified and directed.(Note :- replacement of spare part will be measured and paid separately under appropriate items )
Disconnecnting, dismantling and taking out the non functional Air Conditioner window type of any description, any make and in any position 1.5 TR/2.0 TR capacity Single Phase 50 HZ, strip opening, coil of indoor unit and brazing the discharge and suction line by and checking & retightening of all electrical connections. Replacement of minor part such as nut, bolts, screws, washers, fixing properly bracket housing of capacitors, relay incl replacment of unserviceable parts, cleaning and servicing of the AC with using caustic soda/detergent powder solution, taking out and removing unserviceable/defective wiring & parts incl painting the bottom with one coat of black synthetic enamel paint, replacement of unserviceable and defective parts brazing reassembling and testing of the AC complete all as specified and directed. (Note :- (i) The replacement of defective/nonfunctional parts shall be measured & paid for seperatly as` supply only' under appropriate item of Schedul A and fixing charges for new items are deemed to be included under this item. (ii) The rate for above items are deemed to include for transpotation of AC to & from workshop as approved by Engr-in-Charge for necessary unserviceable screws/nuts/bolts /washer/packing etc with new one. (iii) Charging of gas if required shall be measured and paid for separatly under appropriate item of schedule A however vacuum and pressure leakage testing with nitrogen (N2) if any required is deemed to be included under the units rate quoted by the contractor for this item.)
Disconnecnting, dismantling and taking out the non functional Air Conditioner Split type of any description, any make and in any position 1.5 TR/2.0 TR capacity Single Phase 50 HZ, strip opening, coil of indoor unit and brazing the discharge and suction line by and checking & retightening of all electrical connections. Replacement of minor part such as nut, bolts, screws, washers, fixing properly bracket housing of capacitors, relay incl replacment of unserviceable parts, cleaning and servicing of the AC with using caustic soda/detergent powder solution, taking out and removing unserviceable/defective wiring & parts incl painting the bottom with one coat of black synthetic enamel paint, replacement of unserviceable and defective parts brazing reassembling and testing of the AC complete all as specified and directed. (Note :- (i) The replacement of defective/nonfunctional parts shall be measured & paid for seperatly as` supply only' under appropriate item of Schedul A and fixing charges for new items are deemed to be included under this item. (ii) The rate for above items are deemed to include for transpotation of AC to & from workshop as approved by Engr-in-Charge for necessary unserviceable screws/nuts/bolts /washer/packing etc with new one. (iii) Charging of gas if required shall be measured and paid for separatly under appropriate item of schedule A however vacuum and pressure leakage testing with nitrogen (N2) if any required is deemed to be included under the units rate quoted by the contractor for this item.)
M & L for servicing of following appliances comprising of through cleaning, lubricating of all moving parts, replacement of wornout screws, bolts etc to make the unit for smooth operation for :- Note :- (replacement of spare part will be measured and paid separately under appropriate items )
(a) Water coolers 40 to 150 ltrs cooling capacity complete all as specified and directed.
(b) Refrigerator of 165 to 310 ltrs capacity complete all as specified and directed.
(c) Deep freezers of Upto 425 ltrs capacity complete all as specified and directed.
Taking down defective /unserviceable AC compressor of any make of capacity 1.5 TR and S&F compressor sealed unit suitable for 1.5 TR Capacity for any type of window AC Single Phase 230 Volts incl brazing to suction & discharge line vaccum testing with and including charging of refrigerant gas as per existing & testing incl disconnecting and taking out existing defective compressor of any description & in any position complete all as specified and directed.
Taking down defective /unserviceable AC compressor of any make of capacity 2.0 TR and S&F compressor sealed unit suitable for 1.5 TR Capacity for any type of window AC Single Phase 230 Volts incl brazing to suction & discharge line vaccum testing with and including charging of refrigerant gas as per existing & testing incl disconnecting and taking out existing defective compressor of any description & in any position complete all as specified and directed.
Taking down defective /unserviceable AC compressor of any make of capacity 1.5 TR and S&F compressor sealed unit suitable for 1.5 TR Capacity for any type of Split AC Single Phase 230 Volts incl brazing to suction & discharge line vaccum testing with and including charging of refrigerant gas as per existing & testing incl disconnecting and taking out existing defective compressor of any description & in any position complete all as specified and directed.
Taking down defective /unserviceable AC compressor of any make of capacity 2.0 TR and S&F compressor sealed unit suitable for 1.5 TR Capacity for any type of Split AC Single Phase 230 Volts incl brazing to suction & discharge line vaccum testing with and including charging of refrigerant gas as per existing & testing incl disconnecting and taking out existing defective compressor of any description & in any position complete all as specified and directed.
M&L for checking for leakages, creating vacuum, charging of R-410 gas in the unit to the required pressure complete all as specified and directed for the following appliances:-
(a) Split type AC 1.5/2 Ton capacity complete all as specified and directed.
(b) Window type AC 1.5/2.0 Ton capacity complete all as specified and directed.
(c) Water coolers 40 to 150 ltrs capacity complete all as specified and directed.
(d) Refrigerator of 165 to 310 ltrs capacity complete all as specified and directed.
(e) Deep freezers of Upto 425 ltrs capacity complete all as specified and directed.
Supply only starting relay complete all as specified and directed for the following appliances:-Make- Hitech
(a) Window type AC 1.5/2.0 Ton capacity complete all as specified and directed.
(b) Split type AC 1.5/2 Ton capacity complete all as specified and directed.
(c) Water coolers 40 to 150 ltrs capacity complete all as specified and directed.
(d) Refrigerator of 165 to 310 ltrs capacity complete all as specified and directed.
(e) Deep freezers of Upto 425 ltrs capacity complete all as specified and directed.
Supply only capacitors of the following capactities for ACs water coolers, refrigerators, Deep frizers etc as per site requirement complete all as specified and directed.
Supply, installation including brazing, jointing copper tubing superior quality of dia 5/8” completes all as specified and as directed.
Supply, installation including brazing, jointing copper tubing superior quality of dia 1/2” completes all as specified and as directed.
Supply, installation including brazing, jointing copper tubing superior quality of dia 3/8” completes all as specified and as directed.
Supply, installation including brazing, jointing copper tubing superior quality of dia 1/4” completes all as specified and as directed.
M&L for shifting of split type AC from one location to other location including fixing evaporator unit with gitties/fastner, cutting wall/concrete incl arrangement of T&P for laying copper tubing, positioning condensing unit, laying copper tubing incl brazing work, connecting drain pipe, making good disturbed surface complete all as specified and as directed. (Note- Any additional copper tubing required for the work is included in the item)
S&F in replacement of remote control ( micro- processor) unit suitable make of split type AC 1.5/ 2 TR complete all as specified and directed.
Supply only thermostats of of following :-
(a) Window type AC 1.5/2.0 Ton capacity complete all as specified and directed.
(b) Split type AC 1.5/2 Ton capacity complete all as specified and directed.
(c ) Water coolers 40 to 150 ltrs capacity complete all as specified and directed.
(d) Refrigerator of 165 to 310 ltrs capacity complete all as specified and directed.
(e) Deep freezers of Upto 425 ltrs capacity complete all as specified and directed.
Supply only condenser unit of the following appliances including making of all connectiions as specified and directed by Engr-in-charge following :-
(a) Window type AC 1.5/2.0 Ton capacity complete all as specified and directed.
(b) Split type AC 1.5/2 Ton capacity complete all as specified and directed.
(c) Water coolers 40 to 150 ltrs capacity complete all as specified and directed.
(d) Refrigerator of 165 to 310 ltrs capacity complete all as specified and directed.
(e) Deep freezers of Upto 425 ltrs capacity complete all as specified and directed.
Supply only cooling coil of following :-
(a) Window type AC 1.5/2.0 Ton capacity complete all as specified and directed.
(b) Split type AC 1.5/2 Ton capacity complete all as specified and directed.
(c) Water coolers 40 to 150 ltrs capacity complete all as specified and directed.
(d) Refrigerator of 165 to 310 ltrs capacity complete all as specified and directed.
(e) Deep freezers of Upto 425 ltrs capacity complete all as specified and directed.
Supply only internal wiring kit complete sutaible for following :-
(a) Window type AC 1.5/2.0 Ton capacity complete all as specified and directed.
(b) Water coolers 40 to 150 ltrs capacity complete all as specified and directed.
(c) Split type AC of any make and capcity 1.5/2 ton complete all as specified and directed.
(d) Refrigerator of 165 to 310 ltrs capacity complete all as specified and directed.
(e) Deep freezers of any make & cap 200 to 425 ltrs capacity complete all as specified and directed.
Supply only condenser fan motor complete with necessary mounting bracke to and base frames for :-
(a) Window type AC of any make capactiy 1.5 Ton cap complete all as specified and directed.
(b) Water coolers of any make and cap 40 to 150 ltrs capacity complete all as specified and directed.
(c) Split type AC of any make and capcity 1.5/2 ton complete all as specified and directed.
(d) Deep freezers of any make & cap 200 to 425 ltrs capacity complete all as specified and directed.
Supply only heavy duty PVC flexible pipe with necessary jubilee clamps for water cooler/split ACs/Window ACs drains of size :-
(a) 15mm dia bore complete all as specified and directed.
(b) 20 mm dia bore complete all as specified and directed.
Supply only PCB of split type AC Cap 1.5/ 2 TR as per existing make and model complete all as specified and directed.
Supply only front grill of window type AC as per sample complete all as specified and directed.
Supply only air filters of split type AC of 1.5/2.0 TR capacity as per existing pattern complete all as specified and directed.
Supply only new coling fan motor for window type AC1.5TR/2TR complete all as specified and directed.
Supply only new cooling fan motor for split type AC of 1.5/2.0 TR capacity complete all as specified and directed.
Taking down defective /unserviceable water cooler (capacity 40 ltrs) compressor of make tecumseh/kirloskar/emerson , transporting to company authorized outlet , collecting company repaired compressor of same make in replacement of unserviceable compressor, transporting back to site, refixing including brazing work etc, pressure testing & establishing vacuumed for dehydration complete all as specified and directed.
Taking down defective /unserviceable refrigarator (upto capacity 260 ltrs) compressor of make tecumseh/kirloskar/emerson , transporting to company authorized outlet , collecting company repaired compressor of same make in replacement of unserviceable compressor, transporting back to site, refixing including brazing work etc, pressure testing & establishing vacuumed for dehydration complete all as specified and directed.
Taking down defective /unserviceable Refrigrator (upto capacity 320 ltrs) compressor of make tecumseh/kirloskar/emerson , transporting to company authorized outlet , collecting company repaired compressor of same make in replacement of unserviceable compressor, transporting back to site, refixing including brazing work etc, pressure testing & establishing vacuumed for dehydration complete all as specified and directed.
Taking down defective /unserviceable Deep frizer (capacity upto 425 ltrs) compressor of make tecumseh/kirloskar/emerson , transporting to company authorized outlet , collecting company repaired compressor of same make in replacement of unserviceable compressor, transporting back to site, refixing including brazing work etc, pressure testing & establishing vacuumed for dehydration complete all as specified and directed.
S&F in replacement of water tap for water cooler of capacity 40 Ltrs / 150 Ltrs, complete all as specified and directed.
M&L for Disconnecting,taking down and removing of ceiling fan of any description, any sweep and from any position / locations and connecting up from ceiling rose or connector to ceiling fan, necessary oiling and greasing including supplying and replacing of damaged nuts, bolts, rubber seal , clamps and replacement of unserviceable parts if any, making necessary adjustment and proper alignment of blades, connecting to existing electric sources with using new 1.5 sqmm 3 core multistanded PVC insulated copperwire FRLS to required length and testing at site complete all as specified and directed. (Note : (i) The unserviceable winding / bearing or any parts shall be paid measured and paid for separately as "supply only" under appropriate item of sch "A" . (ii) Burnt out windings replaced and paid for separately under appropraite item of Sch 'A' . (iii) Labour charges for fixing of items which is mentioned here - in - after as supply only is deemed to be included quoted rate.)
Taking out & removing old burnt-out windings of electric celling fans/BLDC fan of any description and rewinding of fan motor with appropriate size super enameled copper wire as approved by the Engineer-in-charge including insulating material such as illuminous paper, Letherized paper, cotton tape, glass sleeving, insulating varnish etc testing at workshop and transportation to site, connecting and testing on full load to the entire satisfaction of Engr-in-charge of ceiling fan/exhaust fan/Air circulators/Wall mounted fans/Pedestal fan complete all as specified and directed.
Supply only bearing of celling fans for celling fans of 1200/1400mm sweep suitable for different makes /type of fans complete all as specified and directed.
Supply only bushes gun metal suitable for celling fans 1200/1400mm sweep of any size complete all as specified and directed.
Supply only rubber reel type synthetic rubberwith 14.5 mm hole suitable for hooks of celling fans complete all as specified and directed.
Supply only nuts, bolts and washers of appropriate size for hanging of celling fan including split pins of galvanished iron 1/8" dia, 2" length complete all as specified and directed.
Supply only top/bottom (Set of Two) canopy of required size complete with tightening screws complete all as specified and directed.
Supply only down rod 30cm long made out of heavy grade MS pipe with necessory threading at both ends holes as required with suitable matching colour of ceiling fan 1200/1400mm complete all as specified and directed.
Supply only condenser/capacitor suitable for 230 volts singls phase celling fan 1200mm/1400 sweep of approved make and quilty of capacity 2.5 MFD complete all as specified and directed.
Supply only fan blade (set of three), complete with tightening bolts/screws, made of suitable for any make and colour of suitable for ceiling fan complete all as specified and directed.
Description all as per sl item No 115 here in before but for exhaust of any size/make complete all as specified and directed. (Note : (i) The unserviceable winding / bearing or any parts shall be paid measured and paid for separately as "supply only" under appropriate item of sch "A" . (ii) Burnt out windings replaced and paid for separately under appropraite item of Sch 'A' . (iii) Labour charges for fixing of items which is mentioned here - in - after as supply only is deemed to be included quoted rate.)
Rewinding of exhaust fan 300mm to 450mm sweep AC 230 volts single phase with super enameled copper wire of appropriate size including packing insulating material, soldering, varnishing , assembling and testing complete all as specified and directed.
Supply only ball bearing suitable for exhaust fan 300 to 450mm sweep of different make complete all as specified and directed.
Supply only exhaust fan frame made out of MS sheet for any make and size of exhaust fan with suitable size of nuts, bolts lugs and washers complete all as specified and directed.
Supply only fan blade (set of three), complete with tightening bolts/screws, made of suitable for any make and colour of exhaust fan complete all as specified and directed.
Description all as per item No 123 here - in - before but capacity 4 MFD for exhaust fan of approved make and quality complete all as specified and directed.
Disconnecting electrically and mechanically the existing geyser of any description, any capacity and make/type and in any position for repair/replacement/painting/cleaning etc including disconnecting existing cold & hot water pipe connections, strip opening of geyser for descaling of tank, element, thermostate, inlet/outlet water pipe connection etc using suitable chemical/wire brush, brazing/soldering/welding of inner tanks for stopping any leakage, replacement of unserviceable parts reassembling the same after, repair/descaling, fixing in position incl, connecting inlet/outlet water pipe connection, electrical connections any testing of geyser complete all as specified and directed. (Note : U/s parts replaced with new one shall be measured and paid for separately as "Supply only" under appropriate item of Sch "A")
Supply only of following items for geyser complete all as specified and directed.
(a) Apparatus plate heavy duty rubber gasket suitable for 03/06/25/50 Ltr of any size complete all as specified and directed.
(b) Geyser element 1.5 KW complete all as specified and directed. Make :- Theata/Venus
(b) Geyser element 2.0 KW complete all as specified and directed. Make :- Theata/Venus
(d) Thermostate switch ISI Marked complete all as specified and directed.
(e) S/S inner tank Capacity 25 Ltrs heavy duty complete all as specified and directed.
(g) S/S Copper inner tank capacity 50 Ltr heavy duty complete all as specified and directed.
(h) Indicator lamp of any type/colour complete all as specified and directed.
(j) CP connection 450mm long nylon braided and double flat with nut and washers both side complete all as specified and directed.
(k) All as per item no 132.08 but of size 300mm long complete all as specified and directed.
(l) Copper flexible cable PVC insulated 3 core 40/.0076 complete all as specified and directed.
(m) Outer body 50 Ltr capacity Geyser sutaible for existing make complete all as specified and directed.
(o) Outer body but 25 ltr capacity Geyser sutaible for existing make complete all as specified and directed.
(r) Plug top 3pin 15 Amps ISI Marked complete all as specified and directed.
M&L for cleaning after taking down complete body including fitting and fixtures of desert coolers of capacity 4000/5000 cum/hours of any make with wire including removal of all sludge, loose paint dirt etc and preparationand cleaning of surface for painting and applying two coats of synthetic enamenl spray paint inside and outside surfaces and applying two coats rubber seal paint inside the water tank etc complete all as specified and directed.
S&F in replacement Submersible PVC pump for desert cooler 230 volt single phase 50 HZ complete all as specified and directed.
S&F in replacement of fan motor copper wound for desert cooler for operation on AC single phase 230 / 250 volts 50 HZ 1440 RPM complete all as specified and directed.
Supply & replacement of wood wool pad ( Set of three) heavy duty for desert cooler complete all as specified and directed.
Supply & fixing in replacement of capacitor 4 MFD complete all as specified and directed.
Supply & fixing in replacement desert cooler fan blades made of galvanised iron sheet of appropriate thickness complete all as specified and directed.
S&F in replacement of 3 Pin Top, 5 Amp for desert coolers complete all as specified and directed.
Supply and fix in replacement of BLDC fan PCB(Control board ) complete all as specfied and directed.
NOTE APPLICABLE FOR ALL ITEMS :- If rate quoted for similar/identical items in same part of Sch ‘A’ is at variance, the lowest rate quoted shall only be considered for payment to the contractor.
M/s Bombay Novelty Stores (BID ID -3313690)
Abhishek Enterprises (BID ID -3315297)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .