Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹13.9 LAccepted-AOC KALATALAV TA ABDASA DIST KUTCH GUJARAT PIN 370 660 | KACHCHH | GUJARAT | 370660 | ₹13.9 L | L-1 | Accepted-AOC Lowest Bidder |
| 2 | L-2₹15.7 L+₹1.8 L (12.8%)Rejected-AOC OPP RAM MANDIR NALIYA KUTCH 370655 | KACHCHH | GUJARAT | 370655 | ₹15.7 L+₹1.8 L (12.8%) | L-2 | Rejected-AOC Rejected |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
24 Jul 2023, 6:00 pmClosed
GE AF Naliya No 1
GE Air Force Station Naliya No 01
REPAIR REPLACEMENT OF INTERNAL WIRING FITTING AND FIXTURE AND CONNECTED EARTHING ITEMS AT TECH AREA AT AF STN NALIYA
2023_MES_606019_1
8892/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Naliya
As per NIT
7 documents required · 7 mandatory
₹500
Yes
GE AF Naliya No 01
₹30,000
Yes
26 Oct 2023
27 Jun 2023
26 Jul 2023
27 Jun 2023
24 Jul 2023
10 Jul 2023
27 Jun 2023 - 3 Jul 2023
Amount
Taking down copper/aluminum point wiring (light, fan, socket or power) complete and including (fitting and fixture such as switches, socket ,ceiling rose ,pendent ,regulators,light fittings, etc to be measured separetaly). NOTE:- Job including for taking out old gutties,screw,nails,casing caping/conduit etc and making good to disturbed surface of wall ,floor etc including to match with the existing surface.
M & L for point wiring with 1.5 sq mm FRLSH single core PVC insulated unsheathed 1100 V grade with multistranded copper conductor drawn through PVC casing and capping with all accessories fixed to wall /roofs ceiling etc and incl provision of 1.5 sq mm PVC insulated and unsheathed copper conductor as earth continuity conductor and connected to common earth dolly including PVC box ISI marked of suitable size for mounting the switches , socket outlets , fan regulators etc all as s specified and directed for following: One light/Fan point controlled by one switch.
Description all as per srl item No 2.00 here-in-before but One socket 3 pin outlet 5 amp on independent board.
Description all as per srl item No 2.00 here-in-before but One light point controlled by two 2-way switches.
Description all as per srl item No 2.00 here-in-before but One 3 pin socket outlet 5 amp on the same board with other switches.
Description all as per srl item No 2.00 here-in-before but One bell/buzzer point controlled by one push button on the same board with other switches or independent with cable 1.5 sq mm size
Description all as per srl item No 2.00 here-in-before but with copper conductor cable for one 3 pin socket outlet 15 amp independent board with cable 2.5 sq mm and 2.5 sq mm copper cable as earth continuity conductor.
M&L for point wiring for one light/Fan/socket 5Amps point on independent board controlled by one, one way switch complete with 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, FRLSH cable 1100 volts grade ISI marked drawn through and including heavy duty ERW conduit not less than 20 mm dia concealed type , including all accessories like bend, tees, junction boxes etc. including 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, FRLSH cable as a earth wire connected to common earth dolly complete all as specified and directed. Note : Point wiring shall be done from Main DB. Length of point wiring may be beyond 5 mtrs and no extra amount for long point wiring shall be considered.
M&L for sub main wiring with 2 run single core multistranded copper conductor cable, of size 1.5Sqmm, PVC insulated, unsheathed, FRLSH drawn through and including heavy duty ERW steel conduit not less than 20 mm dia with all necessary fitting and including one run single core multistranded copper conductor cable, of size 1.5 Sqmm, PVC insulated, unsheathed, FRLSH as earth wire, fixed on wall / ceiling complete including taking down old sub main wiring. Note: 02 Runs of main cable and one run earth wire with conduit shall be measured as one RM for payment.
M&L for sub main wiring with 2 run single core multistranded copper conductor cable, of size 6Sqmm, PVC insulated, unsheathed, FRLSH drawn through and including heavy duty ERW steel conduit not less than 20 mm dia with all necessary fitting and including one run single core multistranded copper conductor cable, of size 6 Sqmm, PVC insulated, unsheathed, FRLSH as earth wire, fixed on wall / ceiling complete including taking down old sub main wiring. Note: 02 Runs of main cable and one run earth wire with conduit shall be measured as one RM for payment.
S&F in replacement switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and directed
S&F in replacement Flame proof switch socket & plug combined in LM6 cable termination box in LM6,16A, 250V, 2P+earth complete all as specified and directed
Supply and Fixing in replacement LED Light Fittings1x16 Watt flame proof, CMRL certified recommended for gas/vapor group of IIA &IIIB Zone 1 & 2 , IP65 protectection with die cast aluminium housing with resistant toughened glass with, LED tube light fixture driver, holdes, connectors etc and including all accessories, connecting up with flexible copper conductor 1.5 Sqmm 3core covered with flexible metal conduit of suitable size.
Supply and Fixing in replacement LED Light Fittings 2x16 Watt flame proof, CMRL certified recommended for gas/vapor group of IIA &IIIB Zone 1 & 2 , IP65 protectection with die cast aluminium housing with resistant toughened glass with, LED tube light fixture driver, holdes, connectors etc and including all accessories, connecting up with flexible copper conductor 1.5 Sqmm 3core covered with flexible metal conduit of suitable size.
S & F in replacment of switch piano flush type single pole one way 5 amp.
S & F in replacment of switch piano flush type single pole two way 5 amp.
S & F in replacment of ceiling rose three terminal/PVC polycarbonate, isolated body complete all as specified.
S & F in replacment of switch socket combination 2 in 1, 3 pin 5/15 amp flush type. .
S&F switch socket combination 2 in 1,5 amp flush type.
S&F in replacment of socket outlet 2 in 1, 3/5 pin 5 amp multi purpose, flush type.
S&F in replacment of MCB DB SPN 8 ways double door with 240 Volt, 200 amps rated bus bar with all accessories fixed in the wall including taking old DBs any type and cap and making good and match with the existing surface of wall all as specified and directed
All as per item No 21 above but 4 way
S&F in replacment of sheet metal enclosure 4 ways double door triple pole and neutral with 415 Volt, 200 amps rated bus bar with all accessories fixed in the wall including taking old DBs any type and cap and making good and match with the existing surface of wall all as specified and directed
S&F in replacment of vertical type DB ,double door Suitable for isolated neutral bar 4 ways,IP 43 protection, Door earthing,mechenical impact strength IK 08 insulated busbar assembly ,fixed in the wall with suitable nut and bolt including 4 pole MCCB 125 Amp 16 KA fixed in DBs as incommer three phase supply fixed in the wall including taking old DBs any type and cap and making good and match with the existing surface of wall all as specified and directed.
S&F in replacment of MCB TPN 4 pole 100 amp
S&F in replacment of MCB TPN 4 pole 63 amp
S&F in replacement of MCB single pole and neutral 35-63 amps, 240 Volts, Complete all as specified and directed.
S&F in replacement of MCB 6 to 32 amps single pole 240 Volts, Complete all as specified and directed.
S/F in replacement of switch bell push, flush type 5 Amp.
S/F in replacement of bell, AC, 230 Volts single pole.
S&F in replacement of lamp holder, insulated body with back plate batten/angle type for batten fitting complete all as specified & directed.
S&F LED Batten for LED tube light with 01 Nos of LED tube 18 Watt fixed on two Nos of Square Block with twin core copper flexible wire and incl taking down old type tube light fitting etc all as directed.
S&F LED plastic batten for LED tube light with 01 Nos of LED tube 10 Watt fixed on two Nos of Square Block with twin core copper flexible wire and incl taking down old type tube light fitting/holder any type etc all as directed.
S&F in replacement of energy efficient conventional LED Bulk head fitting 10 W IP 65 including twin core copper flexible wire and incl taking down old type fitting/holder any type etc all as directed.
S&F in replacement of LED street light fitting 15 W with pressure die cast housing along with prismatic polymer carbonate diffuser and LED with secondry optic with IP 65 protection, including provision of GI pipe light grade of suitable size bent to the shape fixed in the wall with two nos of clamps,nut,bolts,screw etc and taking down old UNSV street light fitting any type all as directed.
S&F in replacement of fan regulator flush type on the existing phenolic laminated sheet etc as per reqd.
S&F in replacement of LED Post top lantern of 45 watt, warm white made in die cast aluminium housing with decorative clear opal acrylic diffuser and IP 65 protection, including provision of suitable size of GI pipe medium grade and suitable length as required on the site fifed on the existing pillers by welding of four Nos of leg and fixed by using fastner and nut and bolts and neccessary connection with twin core copper cable multistranded 1100 volt grade,all as specified and as directed.
S&F in replacement of 9 Watt LED bolard in rectangular shaped victorian design with opal acrylic diffuser and IP 65 protection,including PCC work for mounting the fittings with suitable size of nut,bolts and connection with two core Copper cable all as specified and as directed.
S&F in replacement of 30W LED recessed 2x2 luminaire fixed in the existing Ciling/roofs white powder coated CRCA housing with LED seanless front frame with flat white transmissionacrylic cover and necessary connection with twin core copper cable of suitable size all as specified and as directed.
S&F in replacement of 15W LED downlight sleek square recessed 1x1 luminaire fixed in the existing Ciling/roofs with aluminium die cast body finish with drop down PC diffuser to drive low glare illumination with optimized heat sink for efficient heat dissipation and necessary connection with twin core copper cable of suitable size all as specified and as directed.
S&F in replacement sub main wiring drawing through PVC casing caping of suitable size with all fittings two run of single core 6 sq mm FRLSH single core PVC insulated unsheathed 1100 V grade with multistranded copper conductor and one run of 6 sq mm FRLS as earth wire of multistranded copper conductor PVC insulated and unsheathed cable of 1100 volts grade including taking down old unserviceable sub main wire any size with casing caping/conduit and all accessories all as directed. Note: Two runs of 6 sqmm cable and 01 run of earth wire shall be measured as 1unit. Length of casing caping shall be measured for payment purpose.
S&F in replacement sub main wiring drawing through PVC casing caping of suitable size with all fittings two run of single core 4 sq mm FRLSH single core PVC insulated unsheathed 1100 V grade with multistranded copper conductor and one run of 4 sq mm FRLS as earth wire of multistranded copper conductor PVC insulated and unsheathed cable of 1100 volts grade including taking down old unserviceable sub main wire any size with casing caping/conduit and all accessories all as directed. Note: Two runs of 6 sqmm cable and 01 run of earth wire shall be measured as 1unit. Length of casing caping shall be measured for payment purpose.
M&L for earthling complete with galvanized GI earth plate electrode of size 600x600x6.00 mm, buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to galvanized earth lead wire 4.0 mm dia by means of bolts, nuts, check nut and galvanized iron or steel including earth work in any type of soil, charcoal salt 15 cm around the earth plate as shown in electrical plate No 3 of SSR part 2009, 20 mm dia watering pipe medium grade 1.50 mtr long GI protection pipe light grade 15 mm dia from earth pit to main board (NOTE:- maximum length of GI protection pipe with each earth shall not be less than 7.5 mtrs) including necessary pit with cover , including testing on complition.
Checking and attending complaints by means of repairing/rectifying the electric defects/faults related to elctrical equipments ,devices,accessories and fixtures maintained by MES .Tightening the loose connections complete all as specified and directed. Note : 1 The electrician deployed by the contractor shall have ITI /05 years expreince certificate in concerned trade.Helper deployed shall be min 8th pass with min 03 years expriance in relevant trade.2. This item covers only cost of labour for attending complaint and taking down of old material. 3. Item to be replaced under this item shall be contractor supply under respective items of this schedule. 4. Complaints noted ''NO Light'' shall be attended imediately up to 2200 hrs without fail,failing which recovery of Rs.240/ per complaint shall be effected from the RARs/ F Bill.5. Minor items as PVC wire of any size as per requirement up to 1.0m length,thimble,electric tape etc shall deemed to be included in the quoted rate of this items.6.The complaints shall be attended & defects shall be rectified within 08 hrs commencing from date and time of notifying the complaint slip failing which a penalty @ Rs.120 per complaint per day shall be leived/imposed on the contractor and recovery shall be made from his dues.7. Contracror shall arrange suitable T&P incl necessary means of transport, ladder and safety measures to make it functional complete all as specified and directed.8. Contractor or his rep will report daily at complaint cell for collection of complaints fromthe concerned JE's incharge,in case after checking& attending the defects, if it is not possible to rectfy the defects within 08 hrs, the facts shall be brought to the notice of Engeer in charge by the contractor/his rep immediately. If Engr -in -chargr is satisfied with contractor's view, no recovery will be made on this account.
Supply only Switch socket combination 6/16 A 250V AC universal with box in polycarbonate complete all as specified and directed.
Supply only switch piano flush button type 5 amps single pole one way complete all as specified and directed.
Supply only socket outlet multipurpose 2/3 pin 5 amps flush button type complete all as specified and directed.
Supply only socket outlet multipurpose 2 in 1, 5 and 15 Amps complete all as specified and directed.
Supply only ceiling fan regulator step type for 1200/1400 mm sweep ceiling fan including connections complete all as specified and directed.
Supply only electric bell Ding-Dong AC 230 Volt SP with brass screws and cup washers all as specified and directed.
Supply only replacement of capaciator 2.50 Mfd, 240 V complete all as specified and directed.
Supply only Hylem sheet 3 mm thick size 9'' x 11'' including cutting of switch,socket complete all as specified
Supply only Hylem sheet 3 mm thick size 8'' x 5'' including cutting of switch,socket complete all as specified
Supply only of MCB TPN 4 pole 100 amp
Supply only MCB TPN 4 pole 63 amp
Supply only MCB single pole and neutral 35-63 amps, 240 Volts, Complete all as specified and directed.
Supply only MCB 6 to 32 amps single pole 240 Volts, Complete all as specified and directed.
Supply only switch bell push, flush type 5 Amp.
Supply only bell, AC, 230 Volts single pole.
Supply only lamp holder, insulated body with back plate batten/angle type for batten fitting complete all as specified & directed.
Supply only moduler switch 1 way 6A 1 module
Supply only moduler bell push 6 A, 1 module
Supply only moduler socket 6 A, 2/3 pin,2 module
Supply only moduler socket 6A/16A, 2/3 pin combined,2 module
Supply only moduler fan regulator 120 W. 2 module
Supply only moduler white cover plate with frame. 1 module
Supply only moduler white cover plate with frame. 2 module
Supply only moduler white cover plate with frame. 3 module
Supply only moduler white cover plate with frame. 4 module
Supply only moduler white cover plate with frame. 6 module
Supply only moduler white cover plate with frame. 8 module
Supply only PVC rectangular block for mounting switches, sockets,fan regulator,etc with 3 mm thick plastic laminated sheet cover of size 100mmx100mmx50mm deep. Including taking down old unserviceable board any type and removing the all unsv swinches sockets etc all as directed. Note: New switchs, sockets,switch sockets mounting on the new board will be me4asured seprately.
Supply only PVC rectangular block for mounting switches, sockets,fan regulator,etc with 3 mm thick plastic laminated sheet cover of size 200mmx150mmx50mm deep. Including taking down old unserviceable board any type and removing the all unsv swinches sockets etc all as directed. Note: New switchs, sockets,switch sockets mounting on the new board will be me4asured seprately.
Supply only PVC rectangular block for mounting switches, sockets,fan regulator,etc with 3 mm thick plastic laminated sheet cover of size 350mmx300mmx50mm deep. Including taking down old unserviceable board any type and removing the all unsv swinches sockets etc all as directed. Note: New switchs, sockets,switch sockets mounting on the new board will be me4asured seprately.
Supply only rigid non metalic PVC conduit including of boxes(Junction/terminal) all tees,bends,elbow,reducer,bell mouth,tubes ends and fixture accessories such as couplers lock nuts saddles pipe hooks etc 25 mm dia.
Supply only LED tube 18/20 watt including taking down old Unsv led tube from the existing fitting all as directed.
Supply only LED driver suitable for 25 Watt post top lantern all as specified and as directed.
Supply only LED lamp suitable for 45 Watt post top lantern all as specified and as directed.
Supply only LED driver suitable for 16 watt garden light all as specified and as directed.
M/s. Shree Shakti Enterprise
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .