Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹16.0 L
EMD Value
₹32,016
Closing Date
1 Dec 2025, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
RNB ELECTRIC DIVISION KASHMIR ENGINEERING COMPLEX
Construction of multi-Purpose sports hall at GDCW Baramulla under PM-USHA B.W.O Electric work
2025_PWDJK_295593_1
NIT No.194/2025-26 Dt/17/11/2025
Open Tender
Electrical Works
Percentage
Baramulla
Please refer Tender documents.
4 documents required · 4 mandatory
₹800
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹32,016
18 Nov 2025
18 Nov 2025
2 Dec 2025
18 Nov 2025
1 Dec 2025
18 Nov 2025
Wiring for Light point/Exhaust fan/Fan/Bell point with (P+N+E) 3x1.5 sq.mm FRLS-H PVC insulated Multi strand Copper conductor single core cable(Group-A) in existing surface/recessed Conduits laid in slabs with 01 No.of 6 Amp Modular Switch,Modular Plate,Cover in front & suitable GI box etc ISO/IEC Certified Havells/ Legrand/ Panasonic/ Anchor roma plus/ Schneider/ eq. Make & shall be approved before execution of work.(Separate Wiring for Inverter Points) including cost of conduits
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections ,modular plate etc. as required,ISO/IEC Certified of Havells/ Legrand/Panasonic/Anchor/Schneider/ eq. Make & shall be approved before execution of work.
Wiring for Power Plug with (P+N+E) 3 x 4 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells/Polycab/Anchor/ eq. make to be approved by EIC) incl. cost of conduits
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required, ISO/IEC Certified Havells/Legrand/ Panasonic/Anchor roma plus/Schneider/ eq. Make & shall be approved before execution of work.
Wiring for 6Amp Plug(Computer Point) with (P+N+E) 3 x 2.5 sq.mm FRLS-H PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells/Polycab/Anchor / eq. make to be approved by EIC) incl. cost of conduits
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including proving and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. , ISO/IEC Certified Havells/Legrand/ Panasonic/Anchor roma plus/Schneider/ eq. Make & shall be approved before execution of work.
Wiring for Sub main Wiring along with earth Wire with the following Sizes of FRLS PVC insulated copper conductor, single core Cable in surface/Recessed medium class PVC conduit (Havells/Polycab/ / eq. make to be approved by EIC) & shall be approved before execution of work.
2x10 sq.mm+ 1x10 sq.mm (P+N+E) for Power point Sub main in One run from Main Panel to Distribution Boards.
2x6 sq.mm+ 1x6 sq.mm (P+N+E) for Lighting/ Sub main in One run from Main Panel to Distribution Boards.
2x4 sq.mm+ 1x4 sq.mm (P+N+E) for Inverter Sub main in One run from Main Panel to Distribution Boards.
Supply/Fixing/Testing and Commissioning of 6Amp to 32Amp Rating SP,240v,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB . DB Complete with connections.(L&T/Siemens/Legrand/Schneider / eq. make to be approved by EIC)
Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/Schneider / eq. make to be approved by EIC)
Supplying and Fixing of MCB 6-Way horizontal typed , sheet steel, Double Door Distribution Board, TPN 415V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ Schneider / eq. make to be approved by EIC) 6 way (4+18)
Supply/Installation/Testing and Commissioning of 18W + LED Surface Mounted Panel (Commerical Type) light luminary fitting round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of three years,which includes replacement of fixtures of Philips/Havell's/Wipro/ / eq. make to be approved by EIC.
Providing & Fixing of IK08 IP-66 protected high power LED 120 Watt flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each. Integrated potted driver as a unique BIS R number having efficiency more than 85% and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 Im/wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector, Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K 355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR:-High Power LED Flood Light Minimum lumen output 6200 Im of Havells/Crompton/Philips / eq. make to be approved by EIC and to be installed on outside block including S/F of suitable size of Gyser bolt.The job further includes replacement warranty of fixture (if damaged/burnt out what so ever reason) for a period of three years reckoned from date of successful commissioning /handing over of site to intending department. Havells/Philips/Wipro make.
Supply/Installation/Testing and Commissioning of 1200 mm sweep, ceiling fan with 03 No. blades, 30 cm long down rod, 02 No. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, etc. complete as required. USHA/Havells/Polycab/Orient Make.(Minium 3-Star)
Supply/Installation/Testing and Commissioning of 450mm Sweep having Iron body Industrial type Exhaust fans with inbuilt thermo cut-off Protection and Noise Level not exceeding 37dB and RPM of 1400 including connection etc USHA/Havells/Crompton Greaves Make.(Min 3-Star)
Supply/Laying/Connecting and Commissioning of 70 sq.mm 3.5-Core XLPE/PVC insulated and steel armored 1.1 KV grade Aluminum Cable of Havells/Polycab/Eq. Make with required size of thimbles dully crimped with hydraulic crimping tool including Providing/Fixing of saddles/clips with making of connection and partially to be laid underground through DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refilling the Trench .(Material to be approved before execution)
ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER ROD EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value.Supply,Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 20mm Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through suitable DWC High Density Poly ethylene Pipe having Corrugation complete job.
Supply/Installation/Testing/Commissioning of BIS Certified 10KVA/120V Solar Inverter Pro PCU inbuilt MPPT Technology(with 2-Year Warranty), 8 No. of 200Ah,12V Tubular battery (with 05 Years Warranty) & Suitable Trolley Support for Inverter resting & resting of Tubular Battery etc Havells/Luminious/EXIDE/ AMRON / eq. make to be approved by EIC.The job includes CMC (reckoned from date of successful commissioning) for a period of Two years including all carriages of materials as involved upto site of work as per directions of EIC. complete job
Supply/Laying of 25/32mm Dia and 2mm thick PVC Conduit of Anchor/Ravindra Blue/Finolex / eq. make to be approved by EIC with other accessories like bends,etc complete to be laid in wall for downs and finishing the surface to its original shape by cement mortar plastering/Wall Putty/Paint etc.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.92 MB
BOQ_956965.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .