Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.9 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹10.0 L+₹10,200 (1.03%)Rejected-AOC B 43 CIVIL LINES 1ST FLOOR NAYAPURA KOTA RAJASTHAN 324001 UDYAM RJ 24 0019224 08ABKPA3675N1Z9 R M | KOTA | RAJASTHAN | 324001 | L2 | Rejected-AOC Accepted | |
| 3 | Rejected-Technical NEAR DFO OFFICE VIDYA NAGAR MEHAM ROAD BHIWANI 127021 | BHIWANI | BHIWANI | HARYANA | 127021 | - | Rejected-Technical Technical not Qulified | |
| 4 | Rejected-Technical | - | Rejected-Technical Technical not Qulified | |
| 5 | Rejected-Technical | - | Rejected-Technical Technical not Qulified |
Tender Value
Refer Docs
EMD Value
₹30,000
Closing Date
29 Sept 2022, 1:00 pmClosed
Superintending Engineer (O and M
Superintending Engineer (O and M) Circle, PTCUL, 26 Civil Lines, Roorkee
WORK OF PREVENTIVE MAINTENANCE (AMC) OF 220/132/33KV EQUIPMENTS AT 220 KV SUBSTATION ROORKEE
2022_PTCUX_48562_1
T13SEOMCR2022 23
Open Tender
Miscellaneous Services
Item Wise
365 days
Roorkee
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
SE O AND M CIRCLE PTCUL ROORKEE
₹30,000
Yes
10 Sept 2023
29 Aug 2022
30 Sept 2022
29 Aug 2022
29 Sept 2022
29 Aug 2022
Amount
Following Work to be carried out for preventive maintenance of 2 No. 160 MVA T/F (220/132 KV) & 2 No. 50 MVA T/F (220/33 KV). 4x2
Checking of Oil level in main & OLTC conservator tank & bushings. Attending minor Oil leakage/ seepage from main body/conservator tank/radiator of transformer by tightening. Tightening of all bushing clamps & replacement of damage/defected clamps & connectors. Rectification of electrical fault of auto/ manual operation of cooling fans by replacement of electrical equipment like contactor, MCB, relay etc. Tightening of neutral & main body earthling. Cleaning & washing of transformer main tank/ radiator etc. Tightening of all electrical connections in Transformer Marshalling Box & apply CRC on all connections/connectors/relays etc. Testing of WTI & OTI and Buchholz relay & PRV. Any other work as per site requirement or as per direction of site incharge.
Following work to be carried out for Preventive maintenance of 220 KV, 220/132 KV & 220/33 KV Isolators. (30x2)
Tightening of clamps and connectors & replace if found damage/defective. Cleaning of porcelain insulators by CTC and checking of damage. Replacement of rusted nut/bolts of Isolator/ hardware fittings. Tightening of male and female contacts and replace if found damage/defective. Apply petroleum jelly between male/female contacts. Tightening of earth link and its jaws. Alignment of isolator and earth link. Lubrication of all moving parts. Testing of drive motor in cubical. Tightening of all connections in Bay Marshalling Box. Apply CRC on all connections in cubical. Any other work as per site requirement or as per direction of site incharge.
Following work to be carried out for Preventive maintenance of 220 KV Bay, 220/132 KV Bay & 220/33 KV Bay Equipments. i.e. CT/PT/CVT/LA/Wave Trap (if installed)(58x2)
Top up of oil after checking of oil level in CT/PT/CVT. Checking of oil leakage and rectification if found. Checking and tightening of clamps & Connectors etc. Replacement of rusted nut/bolts if found damage in hardware fitting. Checking and tightening of equipments earthling. Checking the healthiness of surge arrester. Any other work as per site requirement or as per direction of site Incharge
Providing daily basis without any holiday Services of 02 No. skilled labor for Work of special maintenance on breakdown/Crisis basis/fault tracing & removal on (in switchgear, equipment, machine, panels, junction box, trench gallery,including the preventive maintenance of 110 Volt Battery Set.
M/s Singhal and Co
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .