Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
Refer Docs
EMD Value
₹10,532
Closing Date
27 Oct 2026, 1:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Room No. 108, Purta Bhawan, Salt Lake
Room No. 108, Purta Bhawan, Salt Lake
Proposed Special Court for Magistrate Tribal cases related to MPs/MLAs at Ground floor of Mayukh Bhavan, Salt Lake, Kolkata-91--- Air Conditioning system and allied works
2026_WBPWD_5076453_1
WBPWD/EE/BED/e-NIQ-126/2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
14 days
Mayukh Bhawan
Please refer Tender documents.
6 documents required · 6 mandatory
₹10,532
27 Oct 2026
29 Sept 2026
29 Oct 2026
29 Sept 2026
27 Oct 2026
30 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing, and Commissioning of air-cooled Hi-Wall split type air conditioners of following capacities comprising Indoor and Outdoor Units with factory-charged Rotary/Scroll compressors (R-32/R-410A) including surface/concealed copper refrigerant piping insulated with closed-cell elastomeric nitrile rubber insulation and wrapping tape (up to 3 m), FRLS type copper power cable (up to 3.5 m) with suitable plug top, 3 meters of drain pipe, and wireless remote control with suitable battery. The system shall operate on 230V, 50Hz (±tolerance as per applicable standard), single-phase AC supply, providing cooling, dehumidification, and air circulation functions conforming to IS-1391 (Part-II ) with all amendments, and shall be capable of efficient performance at outdoor ambient temperatures up to 50°C, with a minimum 5- year OEM warranty on both the compressor and PCB. The system shall be installed with S&F appropriate fixing arrangements as per OEM recommendations, including wall openings, mending well the damages and making necessary connections including T&P & labour etc as required complete in all respect as per the direction of EIC.
Cooling Capacity- 3.5 kW (Minimum) , Air Flow Rate:400 CFM (Minimum)Minimum ISEER - 5.0, BEE level - 4-Star(min) | 1 | Nos. | - | - |
| 1.01 | Cooling Capacity- 5.2 kW (Minimum) , Air Flow Rate:600 CFM (Minimum)Minimum ISEER - 5.0, BEE level - 4-Star(min)(Make -Mitsubishi Electric/ Mitsubishi Heavy/ O General (R32)As per choice of E.I.C. | 3 | Nos. | - | - |
| 1.02 | Cooling Capacity- 6.1 kW (Minimum) , Air Flow Rate:800 CFM (Minimum) Minimum ISEER - 5.0, BEE level - 4-Star(min) | 4 | Nos. | - | - |
| 2 | SITC including vaccumiazation and Nitrogen of testing of following nominal size of soft/hard drawn copper refrigerent piping forpackage/VRV/VRF/RAC system, complete with fittings, with adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XLPE class -O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for suction and liquid lines, all accessories as per specification etc. as required.
5/8" (15.88 mm) dia (Soft drawn) Cu. Pipes (As per standard BS864 or ANSIB 16.22) mm incl.19mm thick insulation. | 78 | Mtr | - | - |
| 2.01 | 1/4" (6.4 mm) dia (Soft drawn) Cu. Pipes (As per standard 85864 or ANSIB 16.22) incl. 19 mm thick insulation. | 78 | Mtr | - | - |
| 3 | S&F of additional following items for length exceeding 3.5 mtr for complete installation and commissioning of aboove AC machines.
i) 2.5 sqmm, 3/4 core copper cable (FRLS type).[Make:- Polycab/Havells/Gloster/Finolex/KEI/RR Kabel/As per choice of EIC] | 80 | RM | - | - |
| 4 | Supply and laying PVC Drain Pipe 19mm dia with proper supports & brackets as per direction of EIC.[Make:- Suprime/Oriplast] | 78 | RM | - | - |
| 5 | S & F 12 mm thick, 5ft x 2ft waterproof plywood for installation of split AC Machine by four nos of fastner on the wall and mendoing good damages as per direction of E.I.C. | 8 | each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.72 MB
2911_ii.pdf
Tender Documents • 0.50 MB
BOQ_5170078.xls
BOQ • 0.22 MB
time.pdf
PDF • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .