Executive Engineer (E)
O/o EE(E) PWD EMD M-351, R.No.185, Old Sectt Delhi
RMO Electrical and Mechanical services at Vikas Bhawan-II, Delhi (SH- Replacement of existing damaged / outlived chiller and providing ATC system for chiller i/c allied accessories).
2026_PWD_286063_1
113/2025-26/EMD M-351/EE(E)
Open Tender
Miscellaneous Services
45 days
Vikas Bhawan-II
Please refer Tender documents.
10 documents required · 10 mandatory
₹0
₹1.0 L
11 Feb 2026
3 Feb 2026
11 Feb 2026
3 Feb 2026
11 Feb 2026
3 Feb 2026
Supplying, Installation, Testing and Commissioning of BEE 4 Star Rated following capacity floor-mounted VFD (Variable Frequancy Drive) Operated water cooled screw-type chiller machine complete with single/multi semi-hermatic mono/multi screw type compressor, with independent circuits, water-cooled Shell & Tube type condenser, Shell & Tube horizontal flooded type evaporator with carbon steel shell and seamless copper tubes with 19 mm nitrile rubber insulation i/c suitable foundation/mounting structure made of RCC/MS Structure i/c anticorosive paint, anti vibration pad, power control cable and connection inter connection etc. as per design approved by engineer-in-charge, common base frame, interconnected copper refrigerant piping and wiring, vibration Isolators, gauge panel, automatic safety controls, flow switch at evaporator and condenser and ozone friendly Chlorofluorocarbons (CFC)-free refrigerant gas R- 134A. The refrigerant flow control shall use an electronic expansion valve. The chiller shall be designed for a Water Side working pressure of 150 psig and hydraulically tested at 1.5 times of design pressure . A number of properly spaced baffles shall be provided for maintaining optimum water velocity and heat transfer and the tubes shall be adequately supported. The chiller shall be Building Management System (BMS) compatible The system shall be in confirmation to IS : 16590 and CPWD Specification as amended upto date. BEE Star labeling and CPWD Specification as amended upto date and tested as per IS 16590. Chilled water Leaving Temp. (6.67 0C) Chilled water Entering Temp. (12.2 0C) Evaporator fouling factor = 0.018 m2. 0C/kW Condenser water Entering Temp. (32.2 0C) Condenser water Leaving Temp. (36.4 0C) Suitable for Seismic Zone and Altitude as per location/site. Microprocessor based controller. (Note:- The compressor and machine manufacturer should be of the same make. No third party compressor machine is acceptable).
Condenser Tube Cleaning System Supply, installation, testing and commissioning of completely hydro-mechanical pump less Automatic Tube Cleaning System for suitable for following capacity Water Cooled Centrifugal Chiller system. The Automatic Tube Cleaning System (ATCS) shall have ball trap, ball collector and connecting valves for Auto tube cleaning . Small sponge rubber balls, the diameter of balls is slightly larger than that of inner diameter of condenser tubes, PLC control panel, Injector to store, inject and rinse sponge balls along with suitable pipeline assemblies, check valves, drain valves and motorized on-off valves, Ball trap of suitable size to separate out the contaminated balls from the condenser circuit. The ATCS System shall be operated with Single phase electrical power supply to PLC from which only 24 VAC on/off signals are passed directly to the electrical injection and drain valves in accordance with a predetermined program and it should have integration provision with chiller for auto operation and including suitable size MS pipe & valves for interconnection of ATC System etc complete as required.
Supplying, laying/ fixing, testing and commissioning of following thickness resin bonded fiber glass pipe section insulation having density 80 kg/cum or mineral wool (non combustible) having density of 144 Kg/ cu m duly covered with a layer of 120 gm/sqm polythene sheet (vapour barrier) on existing pipe and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date ) at joints etc. as per specifications and as required.
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 80 kg/cum density resin bonded fiber glass or 144 Kg/ cum density mineral wool (non Combustible) pipe section insulation covered with a layer of 120 gm/sqm polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up to date ) at joints and repairing of damage to building etc. as per specifications and as required. Note: The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
300 mm dia.(75 mm thick insulation)
250mm dia.(75 mm thick insulation)
150mm dia. (50mm thick insulation)
125mm dia.(50mm thick insulation)
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :
200 mm dia
250 mm dia
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required
200 mm dia
250 mm dia
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
50mm dia
65 mm dia
80 mm dia
150 mm dia
Providing, laying, testing & commissioning of 'B' class medium duty G.I. pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
Supply, installation, testing and commissioning of Ceiling Concealed Fan Coil Unit comprising of 3 rows deep chilled water cooling coil, centrifugal blowers, fractional horse power (FHP) motor, synthetic fibre filters, insulated & extended condensate drain pan along with L-type auxiliary tray, casing, coil piping connections, condensate drain piping connections & wiring. Fan coil units shall be suitable for operation on 220 +/- 6% Volts, 50Hz, single phase power supply of following sizes & capacities ic fall ceiling cutting, repairing making and good the same Removal of the existing 8 Nos. Ceiling Concealed Fan Coil Unit (FCU) from their current locations, disconnecting electrical connections, chilled water/condensate drain lines, duct connections, supports, and vibration isolators etc. complete as per CPWD specification and as directed by Engineer-in-charge.
1.5 TR nominal capacity with 600 CFM air quantity.
2.0 TR nominal capacity with 800 CFM air quantity.
3.0 TR nominal capacity with 1200 CFM air quantity.
Supply & fixing of canvas connection made out of fire retardant cloth properly stitched & fixing in suitable size GI frame work having hole for nut bolts in fan coil unit i/c pasting of gasket (glue on both side) on both side i.e discharge of duct tightening of new nut bolts & washer complete etc as required.
Supply & fixing of SS ball valve in the pipe of 25 mm size i/c fixing of accessories elbow extension piece etc for connection complete etc as required.
Supply & fixing of SS ball valve with strainer in the pipe of 25 mm size i/c fixing of accessories elbow extension piece etc for connection complete etc as required.
Supply of two-way IP54 on/off type Control motoric actuator (0 to 10 Volt DC control Signal) with necessary piping and valves.
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
Providing & fixing in position the mercury in glass industrial type thermometers.
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastomeric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
25 mm dia. (19 mm thick insulation)
Supplying & testing of following size Flexible Unarmoured copper cable of 1.1 KV grade in Pipe etc as required.
3 x 1.5 Sq mm
3 x 2.5 Sq mm
Supply, installation, balancing and commissioning of site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
Thickness 0.63 mm sheet
Supplying, fixing, installation, testing and commissioning of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers in confirmation to SMACNA/IS and as per specification complete etc. as required.
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastomeric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm
Credit of following material i/c labour for dismantling the existing installation
70 TR Chiller
Assorted size MS Pipe
Sluice Valve / NRV 200 mm dia
Sluice Valve / NRV 250 mm dia
Butterfly valve 50 / 65 mm dia
Butterfly valve 80 / 150 mm dia
FCU 1.5 / 2.0 / 3.0 TR
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.45 MB
113100TRWaterCooledChillerVikasBhawanII.pdf
Tender Documents • 2.43 MB
BOQ_378655.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid