Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹35.0 LAccepted-AOC 24 824 GOVERDHAN COLONY MAIN BHIND ROAD GOLE KA MANDIR | 1 | Accepted-AOC AOC | |
| 2 | 2₹37.0 L+₹1.6 L (4.50%)Rejected-Finance | 2 | Rejected-Finance NOT L-1 | |
| 3 | 3₹37.2 L+₹1.9 L (5.34%)Rejected-Finance B 39 UPPER GROUND FATEH NAGAR NEW DELHI 110018 | WEST | DELHI | 110018 | 3 | Rejected-Finance NOT L-1 | |
| 4 | 4₹40.4 L+₹5.1 L (14.3%)Rejected-Finance 2 A NARENDRA APPARTMENT CENTRAL JAIL ROAD SUBHASH BRIDGE AHMEDABAD 380027 | AHMEDABAD | AHMEDABAD | GUJARAT | 380027 | 4 | Rejected-Finance NOT L-1 | |
| 5 | 5₹41.1 L+₹5.8 L (16.3%)Rejected-Finance | 5 | Rejected-Finance NOT L-1 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
13 Feb 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE ARMY BHUJ
GE ARMY BHUJ
REPAIR/ REPLACEMENT OF LT CABLES AND ALLIED ITEMS AT MIL STATION BHUJ
2023_MES_575664_1
8977
Open Tender
Civil Works - Others
Item Rate
180 days
ARMY AREA BHUJ
REFER TENDER
6 documents required · 6 mandatory
₹500
GE ARMY BHUJ
₹90,000
Yes
7 May 2023
18 Jan 2023
14 Feb 2023
18 Jan 2023
13 Feb 2023
8 Feb 2023
Amount
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc for laying of cables, erection of poles, struts/ stays etc not exceeding 10 sqm on plan and getting out in soft loose soil.
Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil.
Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point in soils.
M & L for sand filling in trenches for cushioning of LT cables punning after filling complete as specified and as directed. Note: Punned thickness shall only be measured and paid
Supply and lay un-reinforced precast concrete cable cover , class , LV , Type I flat size 250 x 150 x 40 mm laid dry in treches over under ground cables.
S & F GI pipe, light grade, of size 50 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection .
S & F GI pipe, light grade, of size 40 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection .
S & F GI pipe, light grade, of size 80 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection .
Dismantaling of any type and size ACSR conductor complete all as specified and directed by Engr-in-Charge.
Dismantaling of stay assembly including demolation of concrete etc complete all as specified and directed by Engr-in-Charge.
Dismantaling of insulator any size and any type complete all as specified and directed by Engr-in-Charge.
Dismantaling of cross arm of MS chanel or angle sections any type any size etc complete all as specified and directed by Engr-in-Charge.
Disconnecting, taking out, removing old existing unserviceable LT underground cable any size and type etc complete all as specified and directed.
Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 4 core 16 Sqmm laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed.
- ditto- here in before Item 12 but of size 3.5 core 25 Sqmm
- ditto- here in before Item 12 but of size 3.5 core 35 Sqmm
- ditto- here in before Item 12 but of size 3.5 core 50 Sqmm
- ditto- here in before Item 12 but of size 3.5 core 70 Sqmm
- ditto- here in before Item 12 but of size 3.5 core 95 Sqmm
- ditto- here in before Item 12 but of size 3.5 core 300 Sqmm
Material and labour for bring the van mounted full automated underground cable fault locator machine at site for find out HT/LT cable fault in underground completely all as specified and directed by Engineer in Charge. Note: (a) Fault machine,cable & T&P required shall be arranged by the contractor. (b) Cable jointing kit for LT is measured separately
MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 63 Amps 16 KA.
MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 100 Amps 16 KA.
MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 160 Amps 36 KA.
MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 250 Amps 36 KA.
MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 400 Amps 36 KA.
M&L for removing shrub and creeper on electrical pole ,electrical panel ,at substation ,chain link fencing on hardstanding pcc all as specfied and directed by Enginner-in-charge
Supply and erect PCC pole 09 Mtr long 102x152m at top and 102x289 mm at bottom class 10 including necessary Excavation, Earthwork ,PCC and coping work completed.
M&L for cable jointing kit LT 1.1KV straight through joint 185sqmm ,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
M&L for cable jointing kit LT 1.1KV straight through join 150 sqmm ,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
M&L for cable jointing kit LT 1.1KV straight through joint 120sqmm ,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
M&L for cable jointing kit LT 1.1KV straight through joint 95 sqmm ,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
M&L for cable jointing kit LT 1.1KV straight through joint 70 sqmm ,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
M&L for cable jointing kit LT 1.1KV straight through joint 50sqmm ,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
M&L for cable jointing kit LT 1.1KV straight through joint 35sqmm ,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
M&L for cable jointing kit LT 1.1KV straight through joint 25sqmm ,heat shrinkable type with all accessories all as specfied and directed by Enginnee-in-charge.
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following INCLUDING TAKING DOWN :-
Incoming
(a) Copper Bus bar, 500 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 250 A 36 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal magnetic release 415 volts 100 A 25 KA-02
(c) MCCB 4 Pole thermal magnetic release 415 volts 25 A 16 KA-03
(c) MCCB 4 Pole thermal magnetic release 415 volts 25 A 16 KA-02
(c) MCCB 4 Pole thermal magnetic release 415 volts 16 A 10 KA-01
(c) Digital Timer icluding contactor of suitable rating complete - 01 Nos
(h) Spare compartment for 100 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following including taking down :-
Incoming
(a) Copper Bus bar, 200 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 100 A 25KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal magnetic release 415 volts 25 A 16 KA-04
(c) MCCB 4 Pole thermal magnetic release 415 volts 16 A 10 KA-02
(h) Spare compartment for 25 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following including taking down :-
Incoming
(a) Copper Bus bar, 200 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 100 A 25 KA-01
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal magnetic release 415 volts 40 A 16 KA-02
(c) MCCB 4 Pole thermal magnetic release 415 volts 25 A 16 KA-01
(c) MCCB 4 Pole thermal magnetic release 415 volts 16 A 10 KA-02
(h) Spare compartment for 40 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 01 Nos
Supply, installation, testing and commissioning CPRI approved weather and vermin proof LT Panel box factory fabricated out door cubicle type (KIOSK type ) , front and back openable , air vent , totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel doors (covers) on two sides with handles, bottom gland plate and locking arrangement with pad lock consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and civil work and copper bus bar for 3 phase & neutral mounted on epoxy insulator-01 Set including sleeves as per colour coading and connecting the following :-
Incoming
(a) Copper Bus bar,320 Amps TPN -01 set
(b) MCCB 4 Pole thermal magnetic release 415 volts 160 A 35 KA-01
(c) On load change over switch 160 Amps 4 Pole - 01 No
(g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three)
(f) Digital Multifunctional meter - 01 No
Outgoing
(c) MCCB 4 Pole thermal adjustable magnetic release 415 volts 16A 10 KA-08
(d) MCB TPN 415 Volt 10 A 10 KA - 03
(h) Spare compartment for 100 Amps MCCB 4 Pole Thermal adjustable and magnetic adjuistable release - 02 Nos
M&L for three core PVC insulated sheathed(heavy duty) unarmoured copper conductor cable (for phase and neutral) of size 1.5 Sqmm including PVC conduit heavy duty 15 mm size for connection drawing through pole or GI brackets of street light fittings to junction box complete all as directed.
Supply and fixing in replacement old unserveceable cable junction box with new pole mounted thermoplastic cable junction box for street light with IP-65 protection, weather proof with metric knockouts for cable entry for outdoor installation with front door opening system including terminals for one incoming and two outgoing cables of size 16/25 sqmm 4 core, one MCB SP 3 to 6 Amp 240V AC with mounting clamp of flat iron, nut, bolt and washers complete all as specified and directed .
Supply and fix PVC copper cables from bus bar to MCCB inside panal including nuts bolts washer ,drilling holes in to bus bar of following sizes
a)10 sqmm PVC single core
b)16 sqmm PVC single core
c)25 sqmm PVC single core
d)25 sqmm PVC single core
e)50 sqmm PVC single core
Supply and fix onload change over switch with enclosure of following capacity complete.
63 A 4 pole
100 A 4 pole
200 A 4 pole
M&L , earthing complete for machinary / Equipment installed at power house / sub station with galavanised steel earth plate electrode of size 60 cmx 60 cmx 6 mm thick buried directly in ground ( earth pit not less then 2.25 m deep below the normal ground level ) with top edge of the earth plate not less then 1.5m below normal Ground level connected galvanised earth lead wire 4.0mm dia by means of bolts, nuts, washerws and check nuts all shown in electrical plate No.5 of SSR Part- I connected to main board / disribution board complete .Earthing GI lead and GI protection pipe 15 mm dia light grade upto 7.5 m from earth pit connecting to machinary/ equipment, testing point, all as specified and testing on completion all as per directed.
Note :- (i) The unit rate shall also included for earth work in hard /dense soil , PCC type C-I (1:3:6) chamber , PCC 1:2:4 type B-I cover 50 mm thick reinforced with 8 mm dia TMT bars,150 mm c/c both ways, funnel with watering pipe 20 mm dia medium graded , GI protection pipe light grade 15 mm dia and wire mesh complete in addition to items No. 1(a) to (e) of preamble (notes) under sub heading earthing specified on SI page No. 389 of SSR Part - II.
(ii) Earthing lead and GI protection pipe beyond 7.5 mtrs will be measured and paid separatelly if required under appropriate Schedule.
Note :- (i) Earthing shall be tested as specified in casul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On teting after complataion of earthing , if the desired earth resistance is not obatined the earthing wiil be re done by the contractor at his on risk and cost to the entire satisfaction of the Engr - in - charge.
M&L , earthing complete for machinary / Equipment installed at power house / sub station with galavanised steel earth plate electrode of size 60 cmx 60 cmx 6 mm thick buried directly in ground ( earth pit not less then 2.25 m deep below the normal ground level ) with top edge of the earth plate not less then 1.5m below normal Ground level connected galvanised earth strip 32X6 mm by means of bolts, nuts, washerws and check nuts all shown in electrical plate No.5 of SSR Part- I connected to main board / disribution board complete .Earthing GI lead and GI protection pipe 15 mm dia light grade upto 7.5 m from earth pit connecting to machinary/ equipment, testing point, all as specified and testing on completion all as per directed.
Note :- (i) The unit rate shall also included for earth work in hard /dense soil , PCC type C-I (1:3:6) chamber , PCC 1:2:4 type B-I cover 50 mm thick reinforced with 8 mm dia TMT bars,150 mm c/c both ways, funnel with watering pipe 20 mm dia medium graded , GI protection pipe light grade 15 mm dia and wire mesh complete in addition to items No. 1(a) to (e) of preamble (notes) under sub heading earthing specified on SI page No. 389 of SSR Part - II.
(ii) Earthing strip and GI protection pipe beyond 7.5 mtrs will be measured and paid separatelly if required under appropriate Schedule.
Note :- (i) Earthing shall be tested as specified in casul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On teting after complataion of earthing , if the desired earth resistance is not obatined the earthing wiil be re done by the contractor at his on risk and cost to the entire satisfaction of the Engr - in - charge.
SHOBHIT BUILDERS
Abhishek Enterprises
Shree Krushna Supply Corporation
Dighard Electricals
Shreeganesh Construction
Ell Ess Contractor
Jinendra Chemicals
Shree Builders
stage.html
html • 0.07 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .