Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹13.7 LAccepted-AOC SHOP NO 02 DADA COMPLEX NEAR DENA BANK NALIYA TAL ABDASA KUTCH GUJRAT 370 655 | KACHCHH | GUJARAT | 370655 | ₹13.7 L Quoted ₹14.0 L | L-1 | Accepted-AOC Accepted |
| 2 | L-2₹17.1 L+₹3.0 L (21.6%)Rejected-AOC | ₹17.1 L+₹3.0 L (21.6%) | L-2 | Rejected-AOC Rejected |
| 3 | L-3₹21.1 L+₹7.1 L (50.4%)Rejected-AOC C O BHAGYODAY STORES BAZAR CHOWK NALIYA KUTCH 370 655 | KACHCHH | GUJARAT | 370655 | ₹21.1 L+₹7.1 L (50.4%) | L-3 | Rejected-AOC Rejected |
Tender Value
₹24.9 L
EMD Value
₹49,800
Closing Date
11 Nov 2020, 6:00 pmClosed
GE (AF) Naliya NO 01
GE Air Force Station Naliya
Repair Renewal of lightening conductor and earthing infrastructure at AF stn Naliya
2020_MES_386453_1
8718/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Naliya NO 01
As Per NIT
7 documents required · 7 mandatory
₹500
Yes
GE AF Naliya No.01
₹49,800
Yes
29 Dec 2020
14 Oct 2020
13 Nov 2020
14 Oct 2020
11 Nov 2020
28 Oct 2020
14 Oct 2020 - 19 Oct 2020
Amount
Labour only for cleaning the vegetation/surplus soil around the earth pits upto 1.00 mtr all around the pit, cleaning the chamber of the earth pit, replacing the rusted earthing leads/funnel / mesh with new ones etc checking the results of the earthing using earth tester, re-activating the earth pit using suitable measures as required to bring the results within the limits of 1 /2/3/5 ohm complete all as specified & as directed. NOTE : i) All materials required for re-activation of earthing pit will be measured and paid separately under supplied only of respective item of schedule. ii) The resistance test of earth pits to be carried out in dry season only. iii) Contractor has to submit the satisfactory earth test reasult duly countersigned by users fo payment purpose.
Supply only common salt for earth pit.
Supply only Charcoal dust
Supply only magnesium sulphate for earth pt.
M & L in replacement of earthing complete with galvanised steel earth plate electode 600 x 600 x 6 mm thick buried directly in ground earth pit with adequate quantity of charcoal and dust and common salt , not less than 2.25 mtr deep below ground level connected to & including galvanised earth lead wire 4 mm dia drawn through GI protection pipe of size ordered specified for protection of earthing lead from earth electrode to test point/main DB from mechanical injury or tempering by means of nuts and bolt check nuts and washers of galvanised iron sheet all as shown in electrical plate No 3 of SSR Part - I and connected to earthing test point complete including testing, refilling earth and removal of surplus soil upto 50 mtrs, PCC 1:3:6 type CI chamber precast RCC cover 40 mm thick reinforced with 6 mm dia MS bar 3 Nos both way with handle made out of 6 mm dia MS bar water pipe with wire mesh and connecting testing etc complete all as specified and directed.
M & L in replacement of earthing complete with copper plate electrode 600 x 600 x 3.15 mm thick burried directly in ground earth pit not less than 2.25 mtr deep below ground level connected to & inclduing copper strip 20x3 mm by means of nuts and bolt check nuts and washers of galvanised iron sheet, passing through protection pipe of 25 mm dia light grade GI pipe all as shown in electrical plate Nos 3 of SSR Part-I, and connected to earthing test point complete inclduing testing filling of adquate quantity of charcoal dust and common salt inclduing refilling earth and removal of surplus soil upto 50 mtrs apart and PCC 1:3:6 type C1 chamber precast RCC cover 40mm thick nrinforces with 6 mm dia MS bar 3 Nos both way with handle made out of 20 mm dia MS base water pipe with wire mesh, funnel etc and connecting testing etc complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode 60cmx60cm x 6 mm thick buried directly in ground vertically to depth not less than 2.25 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level connected to and including GI strip of 32x6mm as earth lead up to 7.5 mtr long fixed by means of bolts, nuts, check nuts and washers etc. of galvanised iron or steel including provn of HDPE protection pipe light grade of 32/40mm bore and connected to earth strip earthing test point all as shown in electrical plate No.5 of SSR Part-I 2009 and as specified or indicated and testing on completion including necessary excavation & earthwork in any type of soil, PCC (1:3:6) type C1 chamber, precast slab 50mm thick in cement concrete (1:2:4)type B1 (reinforced with welded steel wire fabric (XPM) of weight not less than 4kg/sqm) with frame, funnel with watering pipe of 15mm bore Sch.40, wire mesh and lugs, test point etc. complete. Note: G I strip exceeding 7.5m long shall be measured & paid seperately.
M&L for chemical earthing complete with Copper earth plate electrode 90cmx60cm x 5 mm thick buried directly in ground vertically to depth not less than 3.00 mtr below ground level with top edge of earth plate at a depth not less than 2.25 mtr below normal ground level connected to and including Copper strip of 32x6mm as earth lead up to 7.5 mtr long fixed by means of bolts, nuts, check nuts and washers or brazing etc. of galvanised iron or steel including provn of GI protection pipe light grade of 40mm bore and connected to earth strip earthing test point all as shown in electrical plate No.5 of SSR Part-I 2009 and as specified or indicated and testing on completion including necessary excavation & earthwork in any type of soil, PCC (1:3:6) type C1 chamber, precast slab 50mm thick in cement concrete (1:2:4)type B1 (reinforced with welded steel wire fabric (XPM) of weight not less than 4kg/sqm) with frame, funnel with watering pipe of 15mm bore medium grade, wire mesh and lugs, test point including salt (150KG), Coal dust(100KG) & Magnesium sulphate (150KG) including refilling of earth pit with cultivated soil and removal of surplus soil upto 50mtrs apart etc. complete. Note: Copper strip exceeding 7.5m long shall be measured & paid separately.The earth resistance value less than 1 ohm.Failing to achieve the value the contractor shall be re do the earthing without any extra cost.
Supply and fix in repair Air termination, single point copper rod 12 mm dia and 300 mm long complete all as specified & as directed.
S&F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified & as directed.
Supply and fixing Copper strip 25 x 3.15 mm fixed with saddles, insulators and screws etc for roof conductor and down conductor above ground, including breazing at joints complete all as specified & as directed.
Demolition of existing damaged valve pits and provn of new earth pit chamber of size 30cmx30cmx30cm constructed in PCC (1:2:4) type B1 using 20mm graded aggregate including cast iron frame with hinged pit cover of size 12"x12" having 7 kg weight all as per electrical plate No.3 complete all as specified & as directed.
Supply & fix GI pipe 1.5 RM long medium grade vertically fixed by means of PCC 1:2:4 of size 2x2x1.5 Cubic Feet for mounting of Copper air termination rod complete all as specified & as directed.
Supply and fixing Copper strip 32x6 mm fixed with saddles, insulators and screws etc for roof conductor and down conductor above ground, including breazing at joints complete all as specified & as directed.
SHOBHIT BUILDERS
Krishna Engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .