13 Jul 2021, 6:00 pmClosed
CWE (AF) BHUJ
CWE (AF) BHUJ KHAVDA ROAD BHUJ KACHCHH PIN 370001
REPAIRS TO LG UG CABLES/ OH LINES AND REPAIRS TO DG SETS AT MOTHALA UNDER GE (AF) NALIYA
2021_MES_451552_1
85231/E8
Open Tender
Civil Works
Item Rate
180 days
NALIYA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE (AF) NALIYA
₹29,860
Yes
13 Aug 2021
15 Jun 2021
16 Jul 2021
15 Jun 2021
13 Jul 2021
29 Jun 2021
Amount
Excavation in trenches,in soft/loose soil not exceeding 1.5 m deep and not exceeding 1.5 m in wide for laying of cable,RCC Poles/stays and struts etc and getting out including trimming sides and forming bottom surface all as specified and directed at site.
Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft /loose soil complete all as specified.(Note:-The back fill shall be neatly rounded/levelled over the trench to a sufficient height to allow for settlement to the required level all as specified in clause 18.56.6(a) of SSR-2009)
M & L for sand cushioning to underground cable including punning down of sand in layer complete all as specified and directed by Engr-in-charge. Note :- Punned down thickness shall be measured for payment
Supply and laying factory made unreinforced precast concrete cable cover, class LV type 1, flat size 250mm x 150mm x 40mm laid transverse to cable all as directed by Engr-in-charge.
Re-laying of Precast concrete cable cover suitable for LT cable for protection purpose retrieved from dismantling LT Cable.
Taking out unserviceable LT cables of size upto 16sqmm, any core from excavated trenches, ducts, wall, pole etc including removing cable covers, sand, cable joints, pipes, clamps etc, taking out old serviceable cables, cable covers, etc for reuse and removing unserviceable cables, covers etc. complete all as specified and directed by Engr-In-Charge.
All as per item No.6 above but LT cables of size upto 25 sqmm, any core
All as per item No.6 above but LT cables of size upto 50 sqmm, any core
All as per item No.6 above but LT cables of size upto 70 sqmm, any core
All as per item No.6 above but LT cables of size upto 95 sqmm, any core
All as per item No.6 above but LT cables of size upto 120 to 150 sqmm, any core
All as per item No.6 above but LT cables of size 300 sqmm, any core
Supply and laying in trenches or passing through pipe, fixed to wall/pole and duct etc LT underground electric cable including jointing and testing XLPE insulated armoured heavy duty underground cable with stranded aluminium conductor 1100 volt grade alongwith cable covers for 16sqmm, 4.0 core size all as specified and directed.
All as per item No.13 above but cable of size 25sqmm, 3.5 core
All as per item No.13 above but cable of size 50 sqmm, 3.5 core
All as per item No.13 above but cable of size 70 sqmm, 3.5 core
All as per item No.13 above but cable of size 95 sqmm, 3.5 core
All as per item No.13 above but cable of size 120 sqmm, 3.5 core
Laying only in trenches or passing through pipe, fixed to wall/pole and duct etc LT underground electric cable including jointing and testing XLPE insulated armoured heavy duty underground cable with stranded aluminium conductor 1100 volt grade alongwith cable covers for size 16 sqmm, any core all as specified and directed.
All as per item No.19 above but cable of size 25sqmm, any core
All as per item No.19 above but cable of size 50 sqmm, any core
All as per item No.19 above but cable of size 70 sqmm, any core
All as per item No.19 above but cable of size 95 sqmm, any core
All as per item No.19 above but cable of size 150 sqmm, any core
All as per item No.19 above but cable of size 300 sqmm, any core
Supply and laying galvanised steel tubing 50 mm dia, light grade, IS-1239 marked with all fittings IS marked and laid in trenches under roads in drains, fixed to poles/walls with required size flat iron clamp bolts, nuts and washers, pipes all as per specified and directed.
S & F in replacement MCCB 4 pole, 415 Volts, with adjustable thermal and fixed magnetic setting, in existing electric panel with all necessary connections of capacity 400 Amps, 36 kA all as per specified and directed.
All as per item No.27 Above but of capacity 200 Amps, 36 kA
All as per item No.27 Above but of capacity 125 Amps, 16 kA
All as per item No.27 Above but of capacity 100 Amps, 16 kA
All as per item No.27 Above but of capacity 63 Amps, 16 kA
M&L for servicing / Health Check of Air Circuit Breaker by disconnecting supply, opening complete nuts bolts, as Physical Operation check with Interlocks, Provide Lubrication require, replacing fuse cutout if required, Check Tightness of contacts and Complete, Relay and Control Circuit Test, etc. complete all as specified and directed.
S & F in repair power factor capacitor metalized poly propoline heavy duty for three phase 440 V,50 Hz system for permissible non linear load 15 % including connection from the busbar/MCCB to capacitor with PVC insulated copper conductor of suitable size for capacity 12.5 Kvar complete all as specified and directed. Make: Havells Model No.QHBTMC5012X5 or as approved by GE
All as per item No.33 Above but of size 15 Kvar Make: Havells Model No.QHBTMC5015X0 or as approved by GE
Cutting of worn out aluminium cable terminal lugs from the LT cable, crimping of new aluminium cable core and fixing with transformer/LT Panel terminal studs including cutting/dressing of cable, excavation in any type of soil refilling the trench including sand cushioning and brick protection as directed and specified etc complete all as specified and directed.
M & L for cable jointing kit for 1.1 KV cable for straight through heat shrink type complete with jointing materials and accessories suitable for 3.5/4.0 core XLPE armoured aluminium conductor cable of size 150 to 300 sqmm, 3.5 core complete all as specified and directed.
All as per item No.36 above but of size 120 to 70 sqmm, 3.5 core
All as per item No.36 above but of size 50 to 25 sqmm, 3.5 core
All as per item No.36 above but of size 16sqmm, 4 core
REPAIR OF DG SET OF 40 TO 63 KVA
M & L for servicing of DG sets SITUATED AT SITE of capacity 40 kVA and 63 kVA including replacement of fuel filetrs, oil filters, air filters, air filter element, changing lubricating oil, cleaning of fuel lines, cheking leackage if any, repair the leackage replacement of exhaust main fold gasket, welding with connected items if required etc Complete all as specified and directed
Disconnect the electric connection of DG Sets suitable situated at site and discoupling the DG engine from alternator, Opening of the DG set alternator and taking out worn out parts for repair/replacement work. installation after repair/replacement work reassembling of DG set including testing complete. Note:- Worn out parts which to be replaced shall be measured separately as under.
Supply and fix Battery rectifier unit / Diode plate complete as per manufacture's instructions and as directed.
M&L painting to the entire body of DG set including canopy enclosure by scraping out (and flames if necessary the old paint denting spray painting to the entire body of DG set with minimum two coats of synthetic enamel paint to achieve bright finish of Military green colour over a coat of primer and writing MES/SM No of DG Set all as directed to the capacity of DG Set 40 to 63 KVA
S & F battery charger Alternator Assembly including all fixing clamps/internal wiring etc as directed by Engr-in-charge
S & F AVR of suiable capacity complete as per existing model all as specified and directed.
S & F stop Solenoid switch heavy duty 5 kg/cm2, 12 Volt DC.
Supply and fix in repair copper wire terminal of 75 cm minimum length with copper lead aong with brass teriminals for the connection of DG set to Battery as suitable all as specified and directed.
Supply & Fix in replacement of lead Acid battereies for DG set of capacity 150 AH 12 Volt of Make: Exide/AMARON/ TATA or as directed by EIC.
M&L for Plain cement concrete 1:3:6 type C-1 using 20mm grade aggregrate as in pedestal of poles/ struts copping etc, including and use and waste of necessary form work and finishing exposed face of concrete even and smooth without using extra cement complete all as specified and directed.
Supply and fixing Copper strip 20 x 3 mm fixed with saddles and screws including insulators etc for roof conductor and down conductor above ground, complete all as directed.
M & L for Earthing complete with Copper earth plate electrode 600x600x3.15 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to copper earth strip of 20 x 3 mm (up to 7.5m in length from earth plate) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shwon in electrical plate no 3 of SSR part 1 including Charcoal, Rock salt, necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS bar 8mm dia 150mm c/c reingorcement, watering funnel 32 mm dia light grade for protection of earth electrode 20 mm dia for watering all as speicified and directed and tested on completion. Note:- The unit rate quoted shall deemed to have included for GI protection pipe, Copper earth strip up to 7.5 mtr, GI water pipe, wire mesh , funnel , excavation, RCC pit cover complete all as specified.
S & F of Battery Charger (SMPS type)of 10 Amps for 12 Volt Battery all as directed by EIC Make-Koel Green or equivalent
Servicing and caliberation of FIP (Fuel injection pump) & nozzles including replacement of minor parts like nuts,bolts,washers etc of capacity DG Set 40 to 63 KVA all as directed by EIC.
M & L for taking out Radiator of DG set 40 KVA to 63 KVA for repair,welding,brazing,leak testing & refixing to DG set to its original position and testing complete all as directed.
Supply & Fix AMF Relay suitable for 40 KVA DG Set all as directed by EIC
Supply & Fix 3 pole power Contractor ML-4,70 A,415 V
S & F Radiator up to 63 KVA DG Set all as directed by EIC
Removing excavated soil to a distance n.exc. 50 mtr and depositing where directed at a level n.exc. 1.5m above the starting points.
S&F in replacement of unserviceable ACB any make model from LT Panel (installed inside Sub Station No.03) having capacity 1200 Amps four pole 50 Hz 415 Volts by disconnecting / removing LT cable connection and other connected accessories and making arrangement by addln altration of LT Panel for fixing of new Fixed type ACB without release (4 pole) , LT 415 Volts, 50 Hz AC grade of 1250 Amps rating, 50 KA rupturing capacity with over current and short circuit release conforming to IEC:60947-2 /IS: 13947-2 fixed manual type operation etc. complete all as specified and directed. Model:-IHAFE10120**#, Make-HAVELL's or equivalent as approved by GE
Supply & Fix Microcontroller three phase (3ct sencing)APFC relay IPFC CS 1003, 8 steps incl LCD type with dual colour backlight aux supply 90-550 VAC configure alarm settings, supports intelligent algorithm, alarm indoication on display, programmable fan control, Dual password protection, automatic CTpolarity detection, NTC temp sensor, Power factor measurment range:0.8 lag to 0.8 lead & Automatically switches between various capacitive bank OF MAKE HAVELL'S Cat part no.QHOSBS5N0008 IPFC CS 1003-308-90/550V ACor equivalent of make Siemens / Schneider / L&T all as directed.
THOMAS M. MATTACKAL
Hi-Tech Systems
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .