SE,SWEC,PWD
OFFICE OF THE SUPERINTENDING ENGINEER (P.W.Dte) South-Western Electrical Circle PWD Compound,Midnapore,Paschim Medinipur
SITC of Hybrid roof top solar power generation system at Block A building within the campus of Mahatma Gandhi College, Lalpur, Daldali, Purulia in the District of Purulia.
2026_WBPWD_5078125_1
WBPWD/SE/SWEC/NIQ43/2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
PURULIA
Please refer Tender documents.
3 documents required · 3 mandatory
₹25,052
OFFICE OF THE SE,SWEC,PWD,MIDNAPORE
14 Oct 2026
14 Oct 2026
31 Oct 2026
14 Oct 2026
29 Oct 2026
15 Oct 2026
14 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantle the existing old material like switch board,fan,light fittings etc. | 1 | Job | - | - |
| 2 | Supply and delivery of XLPE Insulated, Cores Laid Up, Thermoplastic Tape Inner Sheathed, Unamoured/ Armoured and Extruded PVC Type ST2 Outer Sheathed As Per IS‐7098 (Part 1) 2011 with Up To Date Amendments, Aluminium armoured cable.
[Make:- Finolex/Havells/RR Kable / Polycab/Gloster]
4 Core 70 Sq.mm | 115 | RM | - | - |
| 2.01 | 4 Core 50 Sq. mm | 670 | RM | - | - |
| 2.02 | 4 Core 150 Sq. mm | 20 | RM | - | - |
| 2.03 | 4 Core 16 Sq. mm | 550 | RM | - | - |
| 3 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire [Make:- Finolex/Havells/RR Kable / Polycab/Gloster] in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC | 366 | RM | - | - |
| 3.01 | 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) | 420 | RM | - | - |
| 4 | Laying of two cables above 35 sqmm and upto 185 sqmm in an underground trench in single tier formation (horizontal), the trench size : 680 mm x 760 mm average depth, with brick protection on the top of each cable 8 (eight) Nos. bricks per Mtr. and 4 (four) Nos. bricks per Mtr. as separator between the bricks and cables and also trench to be filled up with shifted soil, levelling up and restoring surface duly rammed. | 480 | RM | - | - |
| 5 | Laying of two cables upto 35 sqmm in an underground trench in single tier formation (horizontal), the trench size : 680 mm x 760 mm average depth, with brick protection on the top of each cable 8 (eight) Nos. bricks per Mtr. and 4 (four) Nos. bricks per Mtr. as separator between the bricks and cables and also trench to be filled up with shifted soil, levelling up and restoring surface duly rammed | 370 | RM | - | - |
| 6 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : upto 4 Core150 Sq.mm | 4 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
Tendernotice_2.pdf
PDF • 1.59 MB
BOQ_5185059.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .