Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.0 LAccepted-AOC B 39 UPPER GROUND FATEH NAGAR NEW DELHI 110018 | WEST | DELHI | 110018 | L1 | Accepted-AOC Lowest and reasonable | |
| 2 | L2₹36.5 L+₹2.5 L (7.21%)Rejected-Finance WANIAWAD BHUJ KUTCH 370001 | BHUJ | KUTCH | GUJARAT | 370001 | L2 | Rejected-Finance Not Lowest | |
| 3 | Rejected-Technical | - | Rejected-Technical NO in WLR of HQ CESC |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
17 Aug 2021, 6:00 pmClosed
GE Army Bhuj
GE Army Bhuj, Madhapar Road, Bhuj-Kutch, Gujarat- 370 001
REPAIR/REPLACEMENT OF LT DISTRIBUTIONS LINES AND UNSV LT UG CABLE, MCCB, AND OTHER CONNECTED ACCESSORIES IN BHUJ, KHAVDA AND GANDHIDHAM UNDER GE(A) BHUJ
2021_MES_461878_1
8833/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
GE Army Bhuj
As Per Tender
7 documents required · 7 mandatory
₹500
GE Army Bhuj
₹70,000
Yes
8 Sept 2021
22 Jul 2021
19 Aug 2021
22 Jul 2021
17 Aug 2021
31 Jul 2021
Amount
Excavation in trenches in soft / loose soil not exceeting 1.5 Mtr wide and not exceding 1.5 Mtr in depth and getting out for taking out / laying of cables, erection of poles / strut / stays etc and not exceeding 10 sqm on plan complete all as specified and directed.
Returning, filling in the any type of soil including spreading, levelling, watering and ramming in layers not exc. 25 cms complete all as specified and directed.
Removing excavated material of any type of soil not exceeding 50 Mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
Material and labour for sand cushioning in cable trenches over & under the cables, with river washed coarse sand, as per standard practice with proper compaction complete all as specified and directed. (Punned thickness 18 cm shall be considered for payment as per para 19.75 of SSR Part-I).
Supply & Laying un-reinforced precast concrete cable cover type-1 Class IV, size of 250 mm x 150 mm x 40 mm laid dry in trenches for under groung cable protection complete all as specifed and directed.
Manning and operation of external electric complaints for 08 hours on shift basis (each shift not exceeding 08 hours - 0900 Hrs to 1700 Hrs) including sundays and holidays by employing tradesmen (01 Skilled Electrician) for attending complaints pertaining to external electrification distribution system, overhead lines, under ground cable including connected equipment such as transformers, switch gears, LT panel boards, Feeder pillar boxes, street lights incl timers, jumpers, fuse wires, binding of insulators etc installed at the MILITARY STATION OP KHAVDA / BHUJ AREAS. The tradesman shall shall attend complaints as per the complaints lodged in complaint register / job card and obtain signature of users for completion of defectss complete all as specified and all as directerd by the Eng-in-charge. Notes :- i. The replacement of burnt out fuse wire shall be measured and paid for separately under appropriate item of Sch 'A' but the fixing charges of the same shall deem to be included in the quoted rates of this item. ii. The transportation of labour, tools and plants / equipment required to rectify the fault (s) of any nature at site will be the responsibility of the contractor. The quoted rates shall deem to be inclusive of this factor and nothing extra shall be admissible on this account. iii. THe electrician shall be minimum ITI holder / job oriented courses in the respective trade with minimum three years experience in the trade. iv. The alternate tradesman shall be arranged by the contractor during the absence of existing tradesman. v. The tradespersons shall work at any location as directed by the Eng-in-charge. vi. No tradesmen shall leave the installation untill the reliever attends the duty.
Manning and operation of external electric complaints for 08 hours on shift basis (each shift not exceeding 08 hours - 0900 Hrs to 1700 Hrs) including sundays and holidays by employing tradsmen (01 Skilled Electrician) for attending complaints pertaining to external electrification distribution system, overhead lines, under ground cable including connected equipment such as switch gears, LT panel boards, Feeder pillar boxes, street lights incl timers, jumpers, fuse wires, binding of insulators etc installed at the MILITARY STATION 4M DET SIYOT / BHUJ AREAS. The tradesman shall shall attend complaints as per the complaints lodged in complaint register / job card and obtain signature of users for completion of defectss complete all as specified and all as directerd by the Eng-in-charge. Notes :- i. The replacement of burnt out fuse wire shall be measured and paid for separately under appropriate item of Sch 'A' but the fixing charges of the same shall deem to be included in the quoted rates of this item. ii. The transportation of labour, tools and plants / equipment required to rectify the fault (s) of any nature at site will be the responsibility of the contractor. The quoted rates shall deem to be inclusive of this factor and nothing extra shall be admissible on this account. iii. THe electrician shall be minimum ITI holder / job oriented courses in the respective trade with minimum three years experience in the trade. iv. The alternate tradesman shall be arranged by the contractor during the absence of existing tradesman. v. The trades persons shall work at any location as directed by the Eng-in-charge. vi. No tradesmen shall leave the installation untill the reliever attends the duty.
S & F GI pipe, light grade, of size 80 mm dia for cable protection including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed
S & F GI pipe, light grade, of size 50 mm dia for cable protection including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed.
S & F GI pipe, light grade, of size 40 mm dia for cable protection including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed.
Disconnecting, taking out, removing old existing unserviceable LT underground cable and Supplying ,Laying, jointing and testing new XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 10 Sqmm x 2 core laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed
All as per Item No. 11 here in above but of size 4 core 16 Sqmm.
All as per Item No. 11 here in above but of size 3.5 core 25 Sqmm.
All as per Item No. 11 here in above but of size 3.5 core 35 Sqmm.
All as per Item No. 11 here in above but of size 3.5 core 50 Sqmm.
All as per Item No. 11 here in above but of size 3.5 core 70 Sqmm.
All as per Item No. 11 here in above but of size 3.5 core 95 Sqmm.
All as per Item No. 11 here in above but of size 3.5 core 120 Sqmm.
S&F cable jointing kit for 1100 Volts (earthed) grade cable for outdoor straight through heat shrik type joint and taking out the old existing joint kit complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 16 sqmm cable complete all as specified and as directed.
S&F cable jointing kit for 1100 Volts (earthed) grade cable for outdoor straight through heat shrik type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 to 50 sqmm cable complete all as specified and as directed.
S&F cable jointing kit for 1100 Volts (earthed) grade cable for outdoor straight through heat shrik type joint and taking out the old existing joint kit complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 120 sqmm cable complete all as specified and as directed.
S & F for Aluminium Terminals suitable for XLPE UG cable of size 25 Sq mm and taking out the old existing lugs complete all as specified and directed.
S & F for Aluminium Terminals suitable for XLPE UG cable of size 35 Sq mm and taking out the old existing lugs complete all as specified and directed.
S & F for Aluminium Terminals suitable for XLPE UG cable of size 50 Sq mm and taking out the old existing lugs complete all as specified and directed.
S & F for Aluminium Terminals suitable for XLPE UG cable of size 70 Sq mm and taking out the old existing lugs complete all as specified and directed.
S & F for Aluminium Terminals suitable for XLPE UG cable of size 95 Sq mm complete all as specified and directed.
S & F for Aluminium Terminals suitable for XLPE UG cable of size 120 Sq mm and taking out the old existing lugs complete all as specified and directed.
M & L for stainless Steel Nut bolts with double washer suitable sizes and length for Fixing the Aluminium Terminals in the LT Pnael Box and taking out the old existing Nuts,bolts complete all as specified and directed.
S & F for Digital panel mounted Voltmeter 0-500 Volts flush mounted case of suitable sizes fixed in the existing LT panel board with internal wiring connection and taking out the old existing VlotMeter complete all as specified and directed.
S & F for Digital panel mounted Ammeter 0-300 Amps flush mounted case of suitable sizes fixed in the existing LT panel board with internal wiring connection and taking out the old existing Ammeter complete all as specified and directed.
S & F for LED indicator lamps for phase indication for the existing LT panel board with internal wiring connection and taking out the old existing Indicator lamp complete all as specified and directed.
M & L for repair of the existing broken LT panel door for proper welding and fixed with hinges,welding portion tobe painted and matching with the existing LT panel Colour complete all as specified and directed
Supply and fix in repiars the following items and disconnecting,taking out the old unserviceable one, including necessary lugs of any size and capacity wherever required. (a) MCCB Thermal Magnetic release 4 pole 63 Amps 16 KA, 440 Volts
All as per Item No. 33 here in above but MCCB Thermal Magnetic release 4 pole 100 Amps 25 KA, 440 Volts
All as per Item No. 33 here in above but MCCB Thermal Magnetic release 4 pole 160 Amps 36 KA, 440 Volts
All as per Item No. 33 here in above but MCCB Thermal Magnetic release 4 pole 250 Amps 36 KA, 440 Volts
All as per Item No. 33 here in above but MCCB Thermal Magnetic release 4 pole 400 Amps 36 KA, 440 Volts
All as per Item No. 33 here in above but Changeover Switch Off load type 4 Pole 63 Amps in Sheet Metal Enclosure
All as per Item No. 33 here in above but Changeover Switch Off load type 4 Pole 100 Amps in Sheet Metal Enclosure
Trimming / cutting of the tree branches / bushes which falls within a clear distance of 3 meter from all sides from the HT/ LT over head conductor & within line of conductors, and shifting waste to nearby waste depot & cleaning area complete all as specified and directed
Supplying and fixing 1100 Volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended be insulating hangers not more than 1 mtr apart incl 4 mm suspension wire, one twin core flat cable of size 6 Sqmm complete all as specified and directed
Supplying and fixing 1100 Volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed flat twin core cable of size 6 Sqmm complete all as specified and directed
Supplying and fixing 1100 Volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed flat twin core cable of size 10 Sqmm complete all as specified and directed
M&L for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth lead wire 4mm dia, (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 15 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit and 40 mm thick precast RCC cover in 1 : 2 : 4 type B-1 with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle complete all as specified & directed. NOTE: Earth lead wire and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item and additional earth GI earth wire/protection pipe etc. if any required at site shall be measured and paid for separately under appropriate item of Schedule `A’ NOTE - The unit rate shall also include for earth work in any type of soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B1 cover 50mm thick reinforced with 8mm dia TMT bars @ 150mm C/C both ways, funnel with watering pipe
Dismantling of old deteriorated ACSR Conductor, of any size , any type and supply and fix aluminium conductor, steel reinforced (ACSR), of any size, any type, as per existing one and stringing properly on the insulators and binding with aluminium wire, connectors, jumpers etc complete all as specified and directed. Note :- Measurement and payment shall be made by measuring horizontal distance between centres of two adjacent poles and adding 3 % for sag , jointings, jumpers etc.
Supplying, stringing and fixing of continuous GI earth wire of size 4 mm / 3.15mm dia on LT poles as in cradle guards / earth wires etc including binding complete all as specified and directed.
Dismantling and taking down existing unserviceable / serviceable MS work of angle iron or other section as in cross arm, clamps, nuts bolts etc from any type of pole in any position, stacking at site for inspection by Engineer-in-Charge to decide for reuse or depositing complete all as specified and as directed.
Supplying, fabricating, fixing in position cross arms, bracings, supports, clamps and back plates, fabricated from in structural steel section any type /size /shape including nuts bolts washers, welding, bending hot or cold, drilling holes for bolts, in any shape or size as required at site, including painting with two coats aluminium paint over a coat of red oxide primer all as specified and directed.
Dismantling and taking down existing serviceable/ unserviceable / deshaped / worn out LT PCC pole of any shape, size & height including demolition of existing PCC foundation complete all as specified and directed.
Supply, erecting and fixing in true vertical position, Prestressed cement concrete pole 9 mtr long confirming to IS-1678 (latest) with minimum cross sectional area 102 mm x 152 mm at top and 102 mm x 289 mm at bottom , class - 10 with and Including all necessary excavation & earth work in any type of soil for foundation of poles, PCC 1:3:6 type (C-2) (using 40 mm graded stone aggregate ) in foundations of size 1.20 m X 0.60 m X 1.65 m below GL, PCC 1:2:4 type (B- 1 )(using 20 mm graded stone aggregate) in plinth block(coping) of size 600 X 600 X 300 mm above GL , removing surplus soil to a distance n. exc. 50 m & depositing where directed, including necessary form work and and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30cm in between 2 bands and numbering of poles, and numbering of the poles shall be done with synthetic enameled painted letter of shape & size complete( M&L)all as specified and directed. (Note -SSR part I clause No.19.5 & 19.52 and other relevant clauses of SSR refers for execution of work and poles shall be procured directly from the manufacturer mentioned in tender documents.)
Unbinding of the ACSR conductor from the insulator on pole, restringing the conductors, tightening LT over head line, connector, jumper, screw nuts, bolts and binding to the insulators using required size aluminum binding wire complete all as directed.
S&F PVC insulated spacers, 12mm dia flexible type suitable for making / turning to any shape and size and suitable for 2 conductor runs including disconnecting, dismantling and taking down existing unserviceable spacers of any description and in any position from the LT electric overhead lines of any height complete all as specified and directed. NOTE : The spacer shall be of best quality and as per the sample kept in GE office.
S&F PVC insulated spacers, 12mm dia flexible type suitable for making / turning to any shape and size and suitable for 4 conductor runs including disconnecting, dismantling and taking down existing unserviceable spacers of any description and in any position from the LT electric overhead lines of any height complete all as specified and directed. NOTE : The spacer shall be of best quality and as per the sample kept in GE office.
Preparation of PCC/Steel tubular Poles not more than 8 mtr height from ground level for painting by cement based paint/aluminium paint incl surfaces of steel / MS cross arms, channels, clamps, street light brackets and GI protection pipes etc (any nos) which are fitted on LT single PCC pole, by scrapping and applying two coats of aluminium paint over a coat of red oxide primer and marking pole number on the same pole with yellow paint in black painted suitable back ground at a height of two metre above ground level & with 5 cm large bold letters also 2" wide colour strips painted with two coats of synthetic enamelled paint up to the height of 1.5 m from coping of pole all as specified and directed.
S&F pin type porcelain, vitreous, white, brown or green insulators, including one galvanized mild steel spindle two galvanised iron washers and one galvanised iron nut, 100mm height and 65mm dia suitable for working pressure upto and including 1100 volts grade for LT lines fixed on poles complete all as specified and as directed.
S&F Shackle type 75mm height and 90mm dia insulator, porcelain, vitreous, white, brown or green including galvanised mild steel strap 31mm X 3mm, insulator bolts 12mm dia with suitable washers and nut, suitable for working pressure upto & including 1100 volts fixed on LT poles complete all as specified and directed.
Dismantling of old unserviceable stay assembly, and Supply and fix Stay assembly complete with all accessories as shown in electrical plate no. 1 of SSR Part - I ,1991, using stay rod 16 mm dla including stay wire. Note :- Excavation , earth work , foundation concrete ,loop insulator, stay clamps, for the new stay shall be measured and paid separately under respective item of schedule
Testing of lightning conductor earthing with the help of earth tester in presence of users representative and recording the earth results in test register of each sub depot and MES register duly signed by OC of sub depot jointly signed by MES and users rap complete all as directed by EIC. Note :- The retreived materials have been mentioned in the Sch of credit in the tender documents in pdf form. The amount of Sch of credit will be deducted offline from the amount of BOQ at the time of acceptance.
M/s Bombay Novelty Stores
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .