Loading…
Loading…
Tender Value
₹1.1 Cr
EMD Value
₹1.1 L
Closing Date
16 Jul 2026, 7:00 pm
Similar tender results from the same govt authority in the past 3 years.
Executive Engineer, Electric (R&B) Division, Bhuj
Providing and Erecting Road light with pole for Road Safety under bhuj electrical sub division, Dist-Kachchh.
317413
No 03 of 2026-27
Open
Electrical
Kutch
7 documents required · 7 mandatory
₹3,600
EXECUTIVE ENGINEER ,ELECTRICAL(ROAD AND BUILDING) DIVISION,BHUJ
₹1.1 L
25 Jun 2026
25 Jun 2026
25 Jun 2026
16 Jul 2026
25 Jun 2026
Name of Work :- Providing and Erecting Road light with pole for Road Safety under bhuj electrical sub
division, Dist-Kachchh.
Quantities Estimated Rate
may be more or Description of Item.
No. In Figures In Words according
1 94 Mtr. providing and erecting Mains with ISI marked, 1.5KV grade 56.56 Rupees Fifty Six
electrolyte multi stranded, annealed copper conductor with heat And Paise Fifty
resistant PVC insulated conforms to IS 694, IEC - 227 erected in Six Only
existing pipe of following size (Specifically for control panel, relays,
power switchgears, motor starters & control wiring) with required
size of copper lugs, nuts and bolts if required.
(e) One wire 6.00 sq. mm
2 34 Mtr. (g) One wire 16.00 sq. mm 142.41 Rupees One
3 3390 Mtr. Supplying and erecting Flexible PVC insulated multi strand multi 46.46 Rupees Forty Six
core 1.1 kv grade ISI marked copper wires of following size to be And Paise Forty
erected as directed. Six Only
(e) 1.50 Sq.mm 3 core round PVC sheathed
4 389 Ea. Supplying and erecting LED street light / Flood light fittings with 6566.01 Rupees Six
High power White LEDs wattage of 3 Watt and above assembled on Thousand Five
single MCPCB, efficiency more than 130 lm/w and corrosion free Hundred Sixty Six
High pressure die cast aluminum housing with smooth finish powder And Paise One
coated and heat sink extruded aluminium with diffuser and Only
Polycarbonate optics/ lenses, with toughened glass with company
mark/name engraved or embossed 160 to 270 V,Power Factor more
than 0.95, THD < 10 %, CCT 3000 K to 5700K,Uniformity ratio
>0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency
> 85 %.( fittings required LM-79 & LM-80 certificates)(NOTE:
Below description have shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select any wattage capacity
between the ranges shown.)
(A) Street Light (IP-65), Surge protection -4KV integral and ,Light
must have 440VAC line supply with over-voltage protection.
(iv) above 90 to 120 watts
5 12 Ea. (B) Flood Light (IP-65), Surge protection -4KV integral and ,Light 10818.11 Rupees Ten
must have 440VAC line supply with over-voltage protection. Thousand Eight
(vii) above 200 to 250 watts Hundred Eighteen
Cat-lll And Paise Eleven
6 19 Ea. Providing and erecting Approved make Four pole moulded case 6173.12 Rupees Six
circuit breaker having breaking capacity ICU of 25 KA. at 415 Thousand One
V,having normal current rating up to 25 A to 100A. with Fixed Hundred Seventy
thermal & magnetic release suitable to work on A.C. supply 50 c/s. Three And Paise
with all internal connections, spreader tinned copper & complete Twelve Only
erected in existing 16 G.M.S. housing.
ICS=100% of ICU only
7 7.6 Rn.Mtr Supplying and erecting triple pole & neutral 440V / 500V panel 1961.42 Rupees One
mounting Copper Busbars with four equal Nos. of electrolyte bus Thousand Nine
having current density not more than 1.6 Amp. / sq.mm (Rated Hundred Sixty
current / cross section area) duly wrapped with colour insulating tape One And Paise
for phase sequence of following current carrying capacity, erected Forty Two Only
with necessary bus bar supports /insulators, main cable socket to each
bar, erected in existing cubical panel with necessary connections.
(A) Suitable for 100 Amp. Capacity
8 401 Ea. providing and erecting Miniature circuit breaker single pole 0.5A to 270.68 Rupees Two
2A system and having breaking capacity 10 KA to be erected in Hundred Seventy
existing box. confirming to IS 8828/1996 with ISI Mark And Paise Sixty
Cat.III Eight Only
9 47 Ea. Providing & erecting 415V MCB Four Pole Switch for Lighting Load 578.73 Rupees Five
(B curve) having 10KA breaking capacity & confirms to IS :8828 in Hundred Seventy
existing box having following capacity Eight And Paise
(a) 6 to 32 Amp. Seventy Three
10 42 Kg Providing and erecting HOT deep Galvanised iron strip wire 8 to 16 77.77 Rupees Seventy
SWG. Seven And Paise
11 21 Ea. Supplying & erecting earth pit of minimum bore dia.150mm size 4591.46 Rupees Four
approved make Earthing Electrode consisting Pipe-in-Pipe Thousand Five
Technology as per IS 3043-1987 made of corrosion free hot dipped Hundred Ninety
G.I.Pipes having Outer pipe dia of 50mm having 80-200 Micron One And Paise
galvanising, Inner pipe dia of 25 mm having 200-250 Micron Forty Six Only
galvanising, connection terminal dia of 12mm with constant ohmic
value surrounded by highly conductive compound with high charge
dissipation suitable for following type of applications with chamber
and heavy duty cover. (A)(approved make OEM has to submit test
certificate including value of earth resistance of installation duly
stamped and signed by agency and officer Incharge has to ensure the
value of earthing resistane mentioned in test Certificate) & having
back filling compound of (B) Inner chemical (CCM Compound)-
Resistivity:- 0.2 ohm / meter testing as per IEC 62561-2017, Voltage
drop:- < 1 volt at no load & dry form, Sulphar content:- <2%(C) Back
fill Compound :- Earthing compound should be capable to retain
moisture for long time Necessary test report must be submitted by
(a) For Electrical Installation up to 440V in normal soil
Length of pipe - 1 Mtr
Back filling compound - 1 Nos Bag of 15 Kg.
12 200 Kg Providing , erecting , fabricating the M.S. structure as per 77.77 Rupees Seventy
requirement on site incorporating proper size of M.S. Seven And Paise
angles,square,round, flats, bars, channels, sections complete with Seventy Seven
cutting, welding, grinding & finishing duly painted with one coat of Only
red oxide with erection on site as per direction of engineer in charge
with necessary grouting, cementing, plastering & finishing complete.
13 720 Mtr. Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable 183.82 Rupees One
multistrand Aluminium conductor for 1.1 KV. to be laid on wall Hundred Eighty
with necessary clamps or in existing trench / pipe of following size Three And Paise
of cables Eighty Two Only
(A) 3 1/2 core 25 Sq. mm ( 16 Sq. mm 1/2 core)
14 9008 Mtr. Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable 153.52 Rupees One
multistrand Aluminium conductor for 1.1 KV. to be laid on wall Hundred Fifty
with necessary clamps or in existing trench / pipe of following size Three And Paise
of cables Fifty Two Only
(A) 4 core 16 Sq. mm
15 9200 Mtr. Making trench in soft soil of suitable width of 90 cm deep for laying 55.55 Rupees Fifty Five
cable or locating the fault all over the run and back filling the same And Paise Fifty
and making the surface as normal ground. Five Only
16 625 Ea. Providing and, fixing heavy duty flange type brass cable gland with 47.47 Rupees Forty
rubber ring for PVC insulated armoured cable complete with out Seven And Paise
going tails, insulating tape etc for following size of cables. Forty Seven Only
(D) 2 to 4 core 16 Sq. mm
17 38 Ea. (E) 2 to 4 core 25 Sq. mm 51.51 Rupees Fifty One
And Paise Fifty
18 2500 Ea. Solder less crimping type Aluminium lugs conforming to IS suitable 15.15 Rupees Fifteen
for cable of following size evenly crimped with high pressure tool & And Paise Fifteen
connected to switchgear terminals with brass/cadmium plated nut Only
bolts in an approved manner.
19 294 Ea. Supply of approved make FRP Pole having following specifications: 16143.84 Rupees Sixteen
FRP Light Pole made by CNC filament winding machine using Thousand One
thermoset resin polyester/epoxy resin system) having minimum 62% Hundred Forty
glass content. The pole should be in one piece and tapered round in Three And Paise
shape, having smooth finish and should be totally free from corrosion Eighty Four Only
as well as non conductive & shock proof Pole should be provided
with FRP Anchor Base and it should be heavy duty, or MS Material
duly painted with Epoxy paint.
Pole should be flame retardant as per IS 6746. Resin used shall be
UV resistance and pigmented. A highly weather resistant
polyurethane coating shall be applied to the pole after applying
suitable primer system that ensures proper adhesion of the paint.
Minimum coating thickness shall be 80 to 100 micron. Deflection of
the pole shall not exceed more than 10% of the length of pole for the
given load“ Pole should be generally made as per the dimensional
data, performance criteria and some interchangeability features of
poles as per standard ANSI C 136.20 latest version or ASTM D
4923/01 including cable termination box with necessary accessories .
The size of pole and type of installation with foundation as per
manufacturer details and site requirement are as below .
(1) Suitable for base plate mounting single arm Bracket.
[J] Overall length of 7 Mtr.Average Thickness: 7.5mm. Top/ Bottom
OD Dia A/F 89/183 mm ± 2mm approx. approx. Weight of Pole
kg approx. (Without Base) Anchor Base (Size 300X300 & 18mm
20 294 Ea. Providing FRP/GRP arm bracket of having 15˚ arm with 50 mm OD 1900.82 Rupees One
pipe *5 mm thk,1000mm long from pole centre Thousand Nine
(A) Single arm bracket Hundred And
Paise Eighty Two
21 19 Ea. Supplying & erecting IP 55 grade following size section pillar 16691.26 Rupees Sixteen
fabricated from joint less M.S. Sheet with angle iron legs made from Thousand Six
jointless M.S. Angle with cable clamps to be buried in ground to have Hundred Ninety
appropriate erection to work uniform until erected with cement One And Paise
concrete foundation and 45 cm high bricks work finishing with Twenty Six Only
plaster etc. hinged double door internally supported on both side,
with internal and outside looking arrangement with look and keys in
duplicate 35 x 35 x 5 mm M.S. Angle of Two Nos. one is welded and
other with nut and bolt for erecting Bakelite sheet. Painting the
Section Pillar inside and out side with three tank powder coated
paint. section pillar roof should be without joint with water leakage
proof & tested as per IP 55 test & followed by IS 2147 of
(A) 150 X 90 X 75 cm section pillar fabricated from 14 Gauge MS
Sheet with angle iron legs 95 cm long made from 40 X 40 X 6 mm
thick MS angle.
22 19 Sq.mtr Supplying and erecting HYLAM sheet on existing angle iron 771.64 Rupees Seven
frame.for following thickness Hundred Seventy
(B) 4mm One And Paise
Sixty Four Only
23 19 Ea. Supplying & erecting approved make Digital time switch having 3168.37 Rupees Three
lithium cell 6 years operative and operate battery backup 1 channel Thousand One
day clock with 14 memory programme, suitable to operate on 240V + Hundred Sixty
5%, 16A with, floating contacts Minimum switching setup time 1 Eight And Paise
minimum & LCD display. Also comprised permanent ON/OFF Thirty Seven Only
switching. Programming switches & housed in fire proof
thermoplastic enclosure & transparent cover erected as required with
necessary connection erected as directed.
24 19 Ea. Supplying & erecting power contactor ,AC3 duty for time switch 857.49 Rupees Eight
complete erected as per direction Cat III Hundred Fifty
(C) 4 pole 440V 16 Amp. Seven And Paise
Forty Nine Only
25 2 Ea. Supplying, erecting, testing, commissioning approved make M.S. 150688.97 Rupees One
Polygonal High Mast Pole having following general Specification. Lakh(s) Fifty
(a) Polygonal Section fabricated from M.S. Plate confirms BSEN Thousand Six
10025 & Hot deep galvanized minimum 65/86 micron (as per IS Hundred Eighty
2629 /1985) Lantern carriage with ring and rubber lines for erection Eight And Paise
of luminaries of suitable site. Ninety Seven Only
(b) Maximum telescopic section not more than four
(c) Double drum gear pipe motorized winch with 6mm dia S.S. Rod
(For 16 mtr and above size)
(d) Approved make L.E.D. aviation light = 1 No. Lightening arrestor
= 1 No. with necessary wiring of 2.5 sq.mm 5 core ISI copper cable
(e) Bottom most section suitable for mounting reversible motor and
switchgears having door not more than 1400mm x 300mm with
waterproof gasket & hinges & locking arrangement.
(f) Pole structure comprises suitable size of reversible motor, cable
and necessary switchgears with control panel.
(g) bottom section shall have suitable size of thickness supports ribs
foundation bolts nuts etc.
(h) Item not comprises the cost of lanterns.
(i) Necessary Cement Concrete foundation as per IS including testing
& commissioning of the entire structure for following size of High
[2] High Mast 14 Mtr. TOP A/F 105 Mm, BOTTOM A/F 400 Mm,
No. of Sec. No. - 1, Bottom Thickness - 3 mm, Size Base Plate -
dia.520 mm x 16 mm thick, Foundation Bolt Size M24 x 850 mm,
Qty - 8 Nos., Suitable for mounting Fitting of Light - 6 Nos.
26 57 Ea. Supplying and erecting approved make suitable panel indicator LED 43.43 Rupees Forty
type lamp, lens cover, complete erected with necessary connections. Three And Paise
Forty Three Only
In Words : Rupees One Crore Thirteen Lakh(s) Forty Seven Thousand Nine Hundred Twenty Two And Paise Eighty Seven
Note : This Estimate has been prepared on the new SOR which is exclusive of GST hence GST additional will be paid to
the agency as per existing guidelines.
I/We am/are willing to carry out the work at ____________% above/below (in Figures)__________________________
percent Above / below (in words) the estimated rates mentioned above amount of my\our tender works out as under :-
Estimated amount put to Tender Rs._________________
Deduct _____% below Rs._________________
(-)Less For Dismantle Material Rs._________________
Net Amount Rs._________________
Estimated amount put to Tender Rs. _________________
(-)Less For Dismantle Material Rs. _______________
Net Amount Rs. _________________
A I/We hereby declare that I/we have visited the site and fully acquainted my self / our selves with the local situation regarding
material,labour and other factors pertaining to the work before submitting this tender.
B I/We hereby declare that I/we carefully studied the conditions of contract, detailed technical specifications and other tender
documents of this work and agree to execute the same accordingly.
C Any Excess in Tender Item/Extra Item if Needs to be Execute. Contractors has to carry out on the instruction of Competant
Authority on Tender Submitted rate, No Excuse will be Accepted. Hence Contactors are Requested to quote the rate considering
this condition.
D Contractors are requested to quote the Tender by considering that payment will be made after availabilty of grant. Contractor
has to start the work immediately after issue of Work Order and as per instruction of Engineer in-Charge irrespective of
availability of grant.
E This Estimate has been prepared on the new SOR which is exclusive of GST hence GST additional will be paid to the agency as
per existing guidelines.
(Signature of the Contractor) Deputy Executive Engineer
Electrical R&B Sub Division
Executive Engineer
Electrical R&B Division
Note 1 Please strike out whichever is not applicable.
2 In the case of tendered amount being quoted incorrectly the quoted pered percentage Below/Above will be considered
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
SCH B.pdf
Bhuj Road Saftey Special Condition.pdf
SBD BHUJ.pdf
Download all tender documents and submit your bid