Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.3 LAccepted-AOC B 39 UPPER GROUND FATEH NAGAR NEW DELHI 110018 | WEST | DELHI | 110018 | L1 | Accepted-AOC LOWEST BID | |
| 2 | L2₹39.4 L+₹1.3 L (3.32%)Rejected-Finance | L2 | Rejected-Finance HIGHER BID | |
| 3 | Rejected-Technical | - | Rejected-Technical NOT RECOMMENDED DUE TO NOT ENLISTING IN APPROPRIATE CATEGORY OF TENDER |
| Sl No | Description | Qty | Unit | Abhishek Enterprises L1 | Hi-Tech Systems L2 |
|---|---|---|---|---|---|
| 1.00 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc for laying of cables, erection of poles, struts/ stays etc not exceeding 10 sqm on plan and getting out in soft/ loose soil complete all as specified and directed. | 812.25 | CUM | 190 ₹1,54,327.5 Lowest | 250 ₹2,03,062.5 |
| 2.00 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth in hard/dense soil for laying of cable/ GI pipe and getting out complete all as specified and directed. | 206.55 | Cum | 190 ₹39,244.5 Lowest | 300 ₹61,965 |
| 3.00 | Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil complete all as specified and directed. | 717.92 | CUM | 90 ₹64,612.8 Lowest | 110 ₹78,971.2 |
| 4.00 | Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point in soils complete all as specified and directed. | 300.89 | CUM | 70 ₹21,062.3 Lowest | 110 ₹33,097.9 |
| 5.00 | M & L for sand filling in trenches for cushioning of LT cables punning after filling complete as specified and as directed.
(Note: Punned thickness shall only be measured and paid.) | 138.51 | CUM | 750 ₹1,03,882.5 Lowest | 1,550 ₹2,14,690.5 |
| 6.00 | Supply and lay un-reinforced precast concrete cable cover , class, LV , Type I flat size 250 x 150 x 40 mm laid dry in treches over under ground cables complete all as specified and directed. | 15,566.67 | EACH | 20 ₹3,11,333.4 Lowest | 21 ₹3,26,900.07 |
| 7.00 | S & F GI pipe, light grade, of size 40 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe for cable protection complete all as specified and directed. | 100 | RM | 450 ₹45,000 | 400 ₹40,000 Lowest |
| 8.00 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 10 Sqmm, 2 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. | 150 | RM | 150 ₹22,500 Lowest | 150 ₹22,500 Lowest |
| 9.00 | All as per Item No.08 but of Size 4 core 16 Sqmm complete all as specified and directed. | 1,700 | RM | 185 ₹3,14,500 Lowest | 190 ₹3,23,000 |
| 10.00 | All as per Item No.08 but of size 4 core 25 Sqmm complete all as specified and directed. | 600 | RM | 250 ₹1,50,000 | 240 ₹1,44,000 Lowest |
Tender Value
₹41.5 L
EMD Value
₹83,044
Closing Date
16 Jul 2025, 6:00 pmClosed
GE ARMY BHUJ
BHUJ
CERTAIN REPAIR REPLACEMENT OF LT DISTRIBUTIONS LINES AND UNSV LT UG CABLE SWITCH GEARS OTHER CONNECTED WORKS AT BHUJ AND GANDHIDHAM AND REPAIR MAINTANENCE OF CENTRAL AC PLANT AT MIL STN BHUJ UNDER GE ARMY BHUJ
2025_MES_715435_1
8324
Open Tender
Civil Works
Item Rate
270 days
GE ARMY BHUJ
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GE ARMY BHUJ
₹83,044
Yes
9 Oct 2025
19 Jun 2025
18 Jul 2025
19 Jun 2025
16 Jul 2025
2 Jul 2025
Amount
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc for laying of cables, erection of poles, struts/ stays etc not exceeding 10 sqm on plan and getting out in soft/ loose soil complete all as specified and directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth in hard/dense soil for laying of cable/ GI pipe and getting out complete all as specified and directed.
Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil complete all as specified and directed.
Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point in soils complete all as specified and directed.
M & L for sand filling in trenches for cushioning of LT cables punning after filling complete as specified and as directed. (Note: Punned thickness shall only be measured and paid.)
Supply and lay un-reinforced precast concrete cable cover , class, LV , Type I flat size 250 x 150 x 40 mm laid dry in treches over under ground cables complete all as specified and directed.
S & F GI pipe, light grade, of size 40 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe for cable protection complete all as specified and directed.
Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 10 Sqmm, 2 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed.
All as per Item No.08 but of Size 4 core 16 Sqmm complete all as specified and directed.
All as per Item No.08 but of size 4 core 25 Sqmm complete all as specified and directed.
All as per Item No.08 but of size 3.5 core 50 Sqmm complete all as specified and directed.
All as per Item No.08 but of size 3.5 core 70 Sqmm complete all as specified and directed.
All as per Item No.08 here in above but of size 3.5 core 185 Sqmm complete all as specified and directed.
M&L for Disconnecting, taking out, removing old existing unserviceable LT underground cable of any size complete all as specified and directed.
Material and labour for bring the van mounted full automated underground cable fault locator machine at site for find out HT/LT cable fault in underground completel all as specified and directed. (Note: (a) Fault machine,cable & T&P required shall be arranged by the contractor. (b) Cable jointing kit for LT is measured separately)
M&L for refreshing of incomming and all outgoing XLPE cable of any size including excavation for removing cable loop , refreshing of exsiting all cable by removing insulation ,including removing old damaged lugs and fixing of suitable size lugs, PVC conncetor,dressing of all cables . nuts ,bolts,washer to all incomming and outgoing MCCB , insulating all bare conductor with insulating cable of suitable colour complete all as specified and directed. (Note: Lugs and insulation tap will be measured as separate item.)
M&L for restraining of HT/LT Over head aluminium conductor of any size including taking down aluminium conductor and refixing the same conductor to insulator including aluminium binding works for connceting insulator and conductor , tighting of pin insulator , MS channel refixing of outgoing conductor ,removing all old unservicable tapping from pole complete all as specfied and directed.
Supply and Fix Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50mm height, 65mm dia for 550 volts grade complete all as specified and directed.
Supply and Fix shackle/ disc type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50mm height, 65mm dia for 550 volts grade complete all as specified and directed.
Supply and fix in repiars the following items and disconnecting,taking out the old unserviceable one, including necessary replacemnet of lugs ,nuts,bolts lugs , cutting existing CRCA sheet of any size and capacity wherever reqd :-
MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 63 Amps 16 KA.
MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 100 Amps 16 KA.
MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 125 Amps 16 KA.
MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 160 Amps 36 KA.
MCCB Thermal Magnetic release,Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 200 Amps 36 KA.
MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 250 Amps 36 KA.
MCCB Thermal Magnetic release Ics=100% of Icu, Adjustable over load 0.8 to 1 In,Adjustable Short circuit current 6-10 In , 4 pole 400 Amps 36 KA.
Supply install testing,commissioning of CRI tested Copper earthing electrode of length 3 metres, 40mm dia and back fill compound of 50kgs ,and conductive gel to retain moisture should be filled layer wise and inter connceted by exothermic brazing & copper strip of size 32x6mm should be suppllied and fix upto testpoint protected by GI pipe of size 50mm dia up to test point including disconnection of old earth strip and fix to new chemical earthing, PCC earth pit of standared size as per SSR part-1 and submmision of earth results and painting of Date of test , value obtain at site complete all specified and as directed. (Note :- (i) Earthing shall be tested as specified in casul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On testing after completion of earthing , if the desired earth resistance is not obatined the earthing wiil be re done by the contractor at his own risk and cost to the entire satisfaction of the Engr - in - charge.)
Material and labour for dry clean river sand for cushioning of cable in trenches for cable protection including spreading, leveling and hand punning as specified in SSR Part-I complete all as specified and directed. (Note :- Only compacted thickness of sand will be measured and paid separately.)
Supplying, install and errect in true vertical positionpressed concrete poles of 9.00 mtr long having 102mm x 152mm at top and 102mm x 289mm at bottom, class 10 poles complete bolts, nuts & screws as specified type, painting and marking alternate white and black strip 30cm height, painting pole number, letters/figures by black paint complete all as specified and directed.
Supply and fix thermolpastic cable Junction Box of size 250 x 200 x 100 mm with locking arrangement suitable for aluminium bus bar (04 Nos.) fixed on porecelain base insulator & 01 No MCB SP, 06 Amps with suitable size of cable glands & MS clamps nuts, bolts & washess etc complete.
M&L for PCC 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) in foundation, filling and mass concrete for poles/struts etc including necessary formwork as required complete all as specified and directed.
M&L for PCC 1:2:4 type B-1 (using 20 mm graded aggregates) as in copings, kneelers, apex stones, bed plates, kerbs etc., water troughs and the like including weathering, slightly rounded for chamfered angles and throating including necessary form work complete all as specified and as directed.
M&L for refreshing of incomming and all outgoing XLPE cable at panels /DBs of any size, disconnection of cable , including excavation for taking out cable from loop, refreshing of exsiting all cables by removing damaged insulation portion, providing insulation using best quality insulation tape ,cleaning of panel inside and ouside using vaccum cleaner, including removing old damaged lugs/ thimble with new one as per existing size, MS nuts ,bolts,washer to all incomming and outgoing MCCB as sepcfied and directed by Engineer-in-charge.
M&L for repair of LT panel doors using 75 mm SS hinges, SS latch, including welding work all as specified and directed by Enginner-in-charge.
M&L for spray painting of LT panel inside and outside surface, including surface prepration by scrubbing of existing paint, and applying two coat of synthtic enamel paint over one coat of red oxide, colour of paint & pattern as per exsiting all as specfied and directed by Enginner-in-charge.
S & F GI pipe, light grade, of size 50 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm complete all as specified and as directed.
Cutting/ removing of hurbs, shrubs, upto 80mm dia grith of bushes from ground level and grass in ihe entire area of installation / Pump house area and deposited outside 100 Mtrs from Pump House, complete all as specified and directed by Engineer-in-Charge. Note : All cutting tools shall be provided by contractor.
M&L for comprehensive maintenance, periodical inspection, servicing / calibration of 01 Nos Air conditioning plants having 3X52 TR Air cooled chiller & 01 X AHUs of capacity , 30000 CFM, Hot water geneerator including and calibration of all the sensor, gauges connected to the system, checking of refrigerant gas pressure, capillary tube, coils as per AC plant, checking functioning of all motorised actuator/ control valve in supply and return duct damper connected to AHU, LT panel installed at Bhuj Mil Stn, by OEM service professional for smooth and efficient functioning complete all as specified and as directed. (Note :- Contractor shall submit the serviceability report.)
Material and labour for disconnecting condenser of capacity 52TR for descaling & plugging them & providing of 15 mm tee out let for local circulation of mild acid solution in the condenser (separate container and small pump set to circulate diluted acid solution to be used) pH value of solution to be circulated & to be kept 4 and checking frequently i.e. every one hour during the operation Scalgun WS solution to be used for descaling purpose after 2 to 3 hours of cleaning if ph value remains less than 7 flush with fresh water mixed with sodium carbonate tubes and cleaning with nylon brush after closing the end covers, circulating diluted acid solution as specified above & pH value to be maintained as above & flushing the same with fresh water including recharging of stored refrigerant up to required pressure complete all as specified & directed.
Pumping down the existing refrigerant from the condensor and carrying out the leak test of plant with the pressure of Nitrogen gas and monoitoring for 24hrs asses leakages by brazing & replacement of necessary gasket wherever required including copper tubes of suitable size vacumizing of the plant by vaccum pump finally reharging of existing refrigerant gas to the plant and topping up of refrigerant if required to maintain the standard pressure etc complete including testing of the plant for smooth functioning complete all as specified & directed. (Note: Refrigerant required for topping up will be measured and paid separately under relevant items)
M&L for identification of leakage location of refrigerant gas by soap bubble test or opening of condensor coil and inserting it whole into Water tank thereafter repairing the copper tube / condenser valves by brazing and making all threaded joint leak proof by sealent, doing vaccum and pressure testing by nitrogen gas and Charging of refrigerant gas again complete all as specified and directed.( Refrigent R407C will be supply only under respective item of Sch'A' Note:- 1.All T&P, Nitrogen cylinder, vaccum pump,welding cylinder etc will be provided by contractor and their charge include in the quoted rate) 2. The job include brazing are considered for whole job, small leakege related to thread shall be considered in quoted rate.)
M& L for replacing the Hot water generator tank heating elements of 6000 W after flushing the system of suction, discharge, liquid line and all valves and making hot water pump functional with proper necessary servicing by using CTC chemical and making operational complete all as specified and as directed.
M&L for repair of (micro computer control) microprocessor based PLC power supply card / compressor card with RAM (control system with mother board) with suitable cord installed in 52 TR chiller unit of make Blue star model XWC4S-052AR2 having 4 Nos danfoss compressor model No SZ185S4RC for controlling temperature, compressor cut off/on, sensor input-output interface, solenoid valve & expansion valve controller, electrical fuse realy card as per installed on site complete all as specified and as directed.
Supply,installation, commissioning and testing of induced draft top discharge counterflow type FRP Cooling Tower 110 TR capacity (Rectangular ) with FRP body and base,water spray headers/cooling tower fills,fan with 415V, 5HP moter,960 RPM, LPM 1672, supporting base frames as per manufacturer's standarad instructions, including making PCC foundations which is sufficient to hold weight of Running cooling tower of 100 TR capacity including water pipe conncetion complete all as specified and directed.
Supplying of refrigerant R407C gas as per standard of UNEP or ISHRAE complete all as specified and as directed.
Supply and fix in replacement thermal Expansion valve with capillary tube of capacity 52 TR, make Blue star model XWC4S-052AR2 for R407 refrigerant gas installed in 52 TR chiller unit as per installed on site complete all as specified and as directed.
Supply and fix in replacement solenoid valve along with operating coil as per installed in 52 TR chiller unit complete all as specified and as directed.
Supply and fix in replacement electronic High Pressure and Low Pressure transducer / transmitter of range 0 to 10 bar with glanded cable upto 5m as per installed in 52 TR chiller unit complete all as specified and as directed.
Supply and fixing in replacement Power contactor 3 Pole, AC3, 415 Volts for 30kW/40HP or 65 Amps with 2 NO+2NC auxiliary contacts, model No NCI 4011 of make CHNT or equivalent complete all as specified and as directed(Chiller unit).
Supply and fixing in replacement Power contactor 3 Pole, AC3, 415 Volts 9.3KW or 18 Amps with 2 NO+2NC auxiliary contacts, top, side of model No MNX 18 & MNX-A1 & MNX -A12S-2 of make L&T or equivalent complete all as specified and as directed( DOL starter ).
Supply and fixing in replacement electronic timer relay for star delta timer with time range 3-120sec, voltage 240VAC of make L&T(GIC) or equivalent complete all as specified and as directed.
Supply and fixing in replacement electronic phase sequence & loss relay for time for ON delay 5 sec & OFF delay 100msec with Phase asymmetry (5% to 15% variable) of make L&T (GIC) or equivalent complete all as specified and as directed.
Supply and fixing in replacement thermal overload relay with thermal protection range 12-18 with tripping class 10A model No MN 2 of make L&T or equivalent complete all as specified and as directed.
Supply and fixing in replacement Power contactor 3 Pole, AC3, 415 Volts with 2 NO+2NC auxiliary contacts, top of model No MI 25 & MNX-A1 & MNX -A2 of make L&T or equivalent complete all as specified and as directed(for DOL starter ).
Supply and fixing in replacement Power contactor 3 Pole, AC3, 415 Volts for 4KW or 9 Amps with 1NO+1NC auxiliary contacts, model No 3TF30 of make Siemens or equivalent complete all as specified and as directed.
Supply and fixing in replacement Auxiliary Contact block 3 Pole, With2NO+2NC contacts, model No LAEN22 of make Schneider or equivalent complete all as specified and as directed.
Supply and fixing in replacement Control relay 3 Pole, AC3, 415 Volts with 2NO+2NC auxiliary contacts, model No CAE22 easy pact TVS of make Schneider or equivalent complete all as specified and as directed.
Supply and fixing in replacement Single Pole MCB, 230V,C 6A to 32A for Compressor as existing model No xC60 of make Schneider or equivalent complete all as specified and as directed.
Supply and fix in replacement current transformer of capacity 5 VA single phase having CT ratio 60/5 having class 1, 50 Hz as per existing installed on site complete all as specified and as directed.
Supply and fix in replacement water pressure gauge meter stainless steel body 100 mm dia,filled with glycerine having upto 7 bar range to be fix in 80 / 100 mm bore MS pipe complete all as specified and as directed. Make :- Baumer or equivalent as approved by GE. Note :- Welding / drilling / threading work for fixing of meter is included in the unit quoted rate of this item.
Supply and laying in replacement MS pipe of 150mm bore Heavy Class (ISI marked) with all fittings including necessary cutting, bending in required shape, welding work inluding nuts, bolts, washers , thick 3mm rubber gasket etc, laid in floors or fixed to walls and ceiling etc. complete all as specified and as directed.
Supply and laying in replacement MS pipe of 100mm bore Heavy Class (ISI marked) with all fittings including necessary cutting, bending in required shape, welding work, MS flange inluding nuts, bolts, washers , thick 3mm rubber gasket etc, laid in floors or fixed to walls and ceiling etc. complete all as specified and as directed.
Supply and fixing Cast Iron butterfly valve of size 150 mm dia, Class PN 1.6, stainless steel disc, wafer type, lever operated, ISI marked, with flanges, nuts, bolts, gasket and washers, suitable for flanged pipe connection including taking down existing unserviceable valve, complete all as specified and as directed.
Descriptions all as per Srl item No '60' above but of 100 mm dia complete all as specified & directed.
Descriptions all as per Srl item No '60' above but of 80 mm dia complete all as specified & directed.
Descriptions all as per Srl item No '60' above but of 50 mm dia complete all as specified & directed.
Supply and fixing Check Valve (NRV) of size 150mm bore, cast iron body, as per IS 5312 (ISI marked), heavy duty, class ‘PN-1.6’, gun metal seat, both ends flanged and drilled, including nuts, bolts, washer and neoprene rubber gasket joint complete all as specified and as directed including dismantling & taking out old unserviceable non return valve of 80mm bore complete all as specified and as directed.
Descriptions all as per Srl item No '64' above but of 100 mm dia, dual plate complete all as specified & directed.
S&F cast iron "Y" strainer with SS 304 Screen of size 150 mm bore, pressure rating PN 1.6, fixed in between MS flanged pipe, fixed in repairs, complete all as specified and as directed.
Descriptions all as per Srl item No '66' above but of 100 mm dia, dual plate complete all as specified & directed.
Supply,laying, jointing, testing and commissioning in replacement of LT underground cable of size 3 core 4 sqmm , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches/fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as directed and specified.
Descriptions all as per Srl item No '68' above but of size 3 core 6 Sqmm complete all as specified and as directed.
M&L for taking down / disconnecting of motor of capacity 3 HP monoblock pump ,2900RPM,415V by removing all electrical connection from panel/ starter/ foundation and condensor, transport from site to workshop and back after repairing including all required material such as bearings, terminals, rewinding with super enameled copper wire of existing gauge, varnishing etc, re-installing the same and testing including painting and writing of MES /SM No complete all as specified and as directed.
M&L for taking down / disconnecting of motor of capacity 5 HP monoblock pump,2900RPM,415V by removing all electrical connection from panel/ starter/ foundation and coupling, transport from site to workshop and back after repairing including all required material such as bearings, terminals, rewinding with super enameled copper wire of existing gauge, varnishing etc, re-installing the same and testing including painting and writing of MES /SM No complete all as specified and as directed.
M&L for taking down / disconnecting of motor of capacity 7.5 HP monoblock pump,,2900RPM,415V by removing all electrical connection from foundation and coupling, transport from site to workshop and back after repairing including all required material such as bearings, terminals, rewinding with super enameled copper wire of existing gauge, varnishing etc, re-installing the same and testing including painting and writing of MES /SM No complete all as specified and as directed.
Over hauling of electric motor & Monoblock pump set after removing from the base plate, disconnecting from pipe line, dismantling the motor pump set, replacing unserviceable gland packing, gun metal bush bearing water seal applying grease, motor bearing , connectors etc. complete and reassembling the motor pump set connecting with pipe line reconnection of electric supply, including buts bolts, gaskets etc. complete testing of pumps for smooth functioning with following capacity of pumps and motors:-
(a) 3 HP Hot water pump
(b) 5 HP Chiller Water Pump
(c) 7.5 HP Condenser Water Pump
M & L for duct insulation, Cleaning the surface of the duct to be insulated, painting the surface of the duct with aluminium paint and fixed tightly Nitrile rubber 25mm thick with applying adhesive compound on the surface of duct sheet and sealed properly, cover with aluminum foil paper laminated with minimum over lap 25 mm complete all as specified and directed.
M & L for pipe insulation, cleaning the pipe surface with steel wire brush, apply one coat of zinc chromate paint and allowed to dry, apply two coats of cold setting adhesive compound on around surface of pipe, stick expanded Nitrile 50 mm thick or nitrile sheets tightly pressed, wrapped with one layer of aluminium cladding complete all as specified and directed.
Supply/Fixing in repair/replacement of corroded steel water tubing, galvanised, heavy grade with all fittings in such as nipple, union, socket, elbow, bends &,laid in trenches, with all fitting including taking down existing rusted pipes for the following sizes complete all as directed and specified
(a) 40 mm bore
(b) 50 mm bore
Supply & installation of PVC expansion tank with Flexible NBR clad closed cell elastomeric thermal insulation foam self adhesive 50 mm thickness having 25kg/m3 density, 0.031 W/m-K thermal conductivity, environment freindly, ASTM E 84 and Class 0 BS 476 part 6& 7 approved of cap 1000 ltrs complete all as specified and directed.
Supply and fix in replacemnt of mono block pump graphite glands packing of suitable thickness as per exisiting all as directed and specified
Supply and fix in repair Mono block pump of capacity 5HP, 7.8LPS, 30meters head CII ,2900RPM, 5 HP, KDS-538+ model, including foundation, MS frame ,removing old pumpset anti vibration pad complete all as specfied and directed
Supply and fix in repair Mono block pump of capacity 7.5HP, 15.4LPS, 24meters head CII ,2900RPM, 7.5 HP, KDS-830+ model, including foundation, MS frame , anti vibration pad, removing old pumpset complete all as specfied and directed
NOTE APPLICABLE FOR ALL ITEMS :- If rate quoted for similar/identical items in same part of Sch ‘A’ is at variance, the lowest rate quoted shall only be considered for payment to the contractor.
Hi-Tech Systems (BID ID -3351989)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .