Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹14.2 LAccepted-AOC 13 86 189 SN COLONY RC PURAM HYDERABAD TELANGANA 502032 INDIA | HYDERABAD | HYDERABAD | TELANGANA | 502032 | ₹14.2 L | 1 | Accepted-AOC accepted |
| 2 | 2₹14.6 L+₹40,873 (2.88%)Rejected-Finance 10 4 B 272 EAST MARREDPALLY SECUNDERABAD 500026 TELANGANA INDIA | HYDERABAD | TELANGANA | 500026 | ₹14.6 L+₹40,873 (2.88%) | 2 | Rejected-Finance L2 |
| 3 | Rejected-Technical MADHYAVEEDHI YELLAPUVANIPALEM VISAKHAPATNAM 530027 ANDHRA PRADESH INDIA | VISAKHAPATANAM | ANDHRA PRADESH | 530027 | - | - | Rejected-Technical Disqualified |
Tender Value
₹13.6 L
EMD Value
₹27,300
Closing Date
14 Aug 2026, 12:00 pmClosed
MandS / PandC dept.
BHEL R.C.Puram
Electrical Works for Shifting of Inter-connection point for 1.5MW Solar Power Plant from TSTRANSCO Grid to Internal Grid
2026_BHEL_63610_1
MandS/PandC/2026/33
Open Tender
Miscellaneous Services
Works
90 days
BHEL R.C.Puram
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹27,300
Yes
22 Sept 2026
4 Aug 2026
14 Aug 2026
4 Aug 2026
14 Aug 2026
4 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Shifting, Assembly, Erection, Testing and Commissioning of 11KV, Indoor type Vacuum Circuit Breakers (VCBs). The VCBs shall be erected on the trenches by providing MS material. The job includes but not limited to the following: 1) Conducting primary injection, secondary injection tests and testing of relays mounted on VCB panels. Approx. Size: 820(L) x 2355(W) x 2700(H) mm and Wt: 1500kgs each. | |||||
| 2 | Dismantling of existing BVM-12 VCBs. The job includes but not limited to:
a) Removal of covers,
b) Disconnection of all the power and control cables
c) Removal of earth connection
d) Dismantling and removal from existing location
e) Shifting of the VCBs to scrap yard or suitable location as per the instruction of site engineer | - | Nos | 1 | - |
| 3Shifting, Assembly, Erection, Testing & Commissioning of 2MVA, 33/11KV, outdoor, oil immersed, power transformer. The job includes shifting of the transformer from stores, assembly of transformer. The transformer shall be placed on foundation (foundation in BHEL scope) with MS Channel. The transformer is to be shifted with in the factory from storage location to the site. The job includes oil filling, filtration, BDV test, providing assistance in protection checks and routine test etc as per IS: 2026, connection of oil drain through BHEL free issued MS Pipe and Flange to the nearest soak pit. The approximate weight with oil is 11T and dimensions are 3850 X 2680 X 2630 mm & Oil Qty: 1750 litres. | |||||
| 4Disconnection and dismantling of 33KV cables at 132/33-11KV TGTRANSCO RC Puram Substation. The job includes route tracing of the cable, thorough identification, and disconnection of cable. Necessary power shutdown will be arranged by BHEL. It is to be noted that there may be other underground cables belonging to TGSPDCL/TGTRANSCO in the route of the cables that are to be dismantled. Hence, the contractor has to maintain extra precaution while excavation. In case of any damage of the existing cables of TGSPDCL/TGTRANSCO, the contractor has to bear the cost for repair | |||||
| 5Rerouting of 33KV Cables: The job includes laying of 3C X 400 sq.mm 33KV (UE), Armoured XLPE insulated Aluminium cable from TGTRANSCO substation to inside the factory up to 2MVA Transformer. The cable is to be laid underground, shall be neatly dressed. | |||||
| 6 | Shifting and laying of the following HT power cable. The job includes Dressing & Tagging, Fixing of free issued trefoil clamps for Single Core cable at 1mt interval etc:
3C X 95 sq.mm, 11KV (UE), Aluminum, XLPE | - | Mtrs | 1 | - |
| 7Supply of End Termination Kits for 3C X 400 sq.mm, 33KV(UE), XLPE armoured aluminium cable | |||||
| 8Shifting and execution of end terminations for the following cables. The job includes, but not limited to, making holes of sufficient size in the gland plates, adjusting the cables in the trench, relaying and adjustment of cable for suitable length for facilitating entry into VCBs/Transformer and providing mechanical support for the cables, sealing of cable entries with wall putty, tagging of cables. Supply of wall putty for plugging holes in the cable entry and cable tags are in contractor's scope. The tools required for the work are in contractors's scope. | |||||
| 8.01 | 3C X 400 sq.mm, 33KV (UE), Aluminium, XLPE | - | Nos | - | - |
| 8.02 | 3C X 95 sq.mm, 11KV (UE), Aluminum, XLPE | - | Nos | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.43 MB
Scope.pdf
Tender Documents • 0.10 MB
TechnoCommercial-bid.pdf
Tender Documents • 0.42 MB
BOQ_68964.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .