| 1 | L1₹12.0 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹12.5 L+₹19,755.47 (1.60%)Rejected-AOC A 16 SHIV LOK COLONY RAJPUR ROAD DEHRADUN 248 008 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248008 | L2 | Rejected-AOC L2 | |
| 3 | L3₹12.9 L+₹59,227.10 (4.81%)Rejected-AOC 67 NIRANJANPUR SAHARANPUR ROAD PO MAJRA DEHRADUN UK 248001 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | L3 | Rejected-AOC L3 |
Tender Value
₹12 L
EMD Value
₹24,000
Closing Date
17 Jul 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE 871 EWS
GE 871 EWS
COMPREHENSIVE MAINTENANCE OF MISC EM SERVICE TO ELECTRICAL NETWORK SYSTEM AT HARSIL, SUKHI AND TEKLA UNDER GE 871 EWS.
2021_MES_443441_2
8587/E8
Open Tender
Civil Works
Works
270 days
HARSHIL
AS PER TENDER
7 documents required · 7 mandatory
₹500
GE 871 EWS
₹24,000
Yes
31 Jul 2021
18 Jun 2021
19 Jul 2021
18 Jun 2021
17 Jul 2021
3 Jul 2021
18 Jun 2021 - 2 Jul 2021
60 days
Amount
Excavation in trenches nexc. 1.5 metre wide and nexc 1.5 metre in depth for laying of underground cable and getting out in hard dense soil all as specified and directed.
Excavation in trenches nexc 1.5 m wide and depth exc 1.5 metre but nexc 3.0 metre and getting out in hard dense soil all as specified and directed.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 mtr in depth and getting out in hard rock by using mechanical machinary all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick in soil all as specified and directed
Removing excavated soil to a distance nexc 50 metre and depositing where directed at a level nexc 1.5 metre above the starting point all as specified and directed.
M&L local sand dry, filling in trenches around under ground cable complete all as specified and directed. Note: for the purpose of payment only punned thickness will be measured.
M&L for providing new sub class 'B' bricks, old size, well burnt laid flat dry for protection of under ground cable width equal to length of bricks all as specified and directed.
Supply and fixing in repairs, laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 50 sqmm 3.5 core all as specified & directed. Make XLPE cable : Polycab/Finolex/Universal.
All as per Item No 8 here-in-before but of size 35 Sqmm 3.5 core. Make : Polycab/Finolex/Universal.
All as per Item No 8 here-in-before but of size 25 Sqmm 4 core. Make : Polycab/Finolex/Universal.
All as per Item No 8 here-in-before but of size 16 Sqmm 4 core. Make : Polycab/Finolex/Universal.
All as per Item No 8 here-in-before but of size 16 Sqmm 2 core. Make : Polycab/Finolex/Universal.
All as per Item No 8 here-in-before but of size 10 Sqmm 2 core. Make : Polycab/Finolex/Universal.
Supply and fix in repairs light grade galvanised mild steel pipe 40mm bore with all fittings, laid under roads crossing, drain, paths, fixed to poles/ walls with suitable mild steel clamps, bolts, nuts and washers for cable proction all as specified & directed. Make :- Jindal/TATA/Prakash surya. Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule
All as per Item No 14 here-in-before but of size 32 mm bore. Make :- Jindal/TATA/Prakash surya.
All as per Item No 14 here-in-before but of size 25 mm bore. Make :- Jindal/TATA/Prakash surya.
Supply and fix in repairs of 1100 Volts grade heavy duty cable PVC insulated aluminum conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm suspension wire, one twin core cable flat or circular of size of aluminum conductor 10 sqmm 2 core flat stranded conductor all as specified and directed. Make :Polycab/Finolex/Universal.
All as per Item No 17 here-in-before but of size 16 sqmm 2 core. Make :Polycab/Finolex/Universal.
Supply and fix in repairs, errecting of steel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long) including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" wide all as specified and directed. Make : India Co. Ltd Jamshedpur/Fabrico(India) Pvt Ltd Meerut/National Tubing Co. Kanpur. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
M&LPCC 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) lean concrete below foundation of poles including necessary form work and finishing the exposed surface even and smooth with out using extra cement all as specified and directed.
M&L PCC 1:3:6, type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete including necessary form work and finishing the exposed surface even and smooth with out using extra cement all as specified and directed.
M&L PCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) for coping of poles including necessary form work and finishing the exposed surface of concrete even and smooth with out using extra cement all as specified and directed.
Supply and fix in repairs, commissioning of LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP 65/66 protection and impact resistance of IK-07 with 10KV built-in surge protection device all as specified and directed. Make :- Phillips/Bajaj/Crompton Greaves. Note :-Rates quated by contractor are deemed to be inclusive of pvc haevy duty conduit mounted with clamp with pole along with 3 core 1.5 sqmm PVC insulated PVC sheathed copper multistranded conductor ISI marked from MCB box to street light.
Supply and fix in repairs, commissioning of LED street light fitting 60 Watt, 230 V, AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP 65/66 protection and impact resistance of IK-07 with 10KV built-in surge protection device all as specified and directed. Make :- Phillips/Bajaj/Crompton Greaves. Note-Rates quated by contractor are deemed to be inclusive of pvc haevy duty conduit mounted with clamp with pole along with 3 core 1.5 sqmm PVC insulated PVC sheathed copper multistranded conductor ISI marked from MCB box to street light
Supply and fix in repairs mild steel cross arms, bracings, supports, clamps, and back plates fabricated from structural steel sections as ordered including necessory nuts, bolts, washers , welding, bending, cold or hot , drilling holes for bolts , in any shape or size as indicated or directed with and including preparations of new steel surfaces & applying two coats of aluminium paint over one coat of red oxide Zinc chrome primer all as specified and directed.
Supply and fix in repairs pin type insulator prcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100mm height, 65mm dia for 1100 volt grade all as specified and directed.. Make : BHEL/BPCL/JAYSHREE.
Supply and fix in repairs insulator shackle type porcelain vitreous, white brown or green 100mm height and 65mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nut for conductor working pressure 1100 volt grade all as specified and directed.. Make : BHEL/BPCL/JAYSHREE.
M&L earthing complete with using galvanized mild steel earth plate (electrode) 600 mmx 600 mmx 6 mm thick buried directly in ground, earth pit not less than 2.25 metre deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all round the plate using 32X6 mm GI earth strip as earth lead moulded and riveted to earth plate at one end and connected to main equipment at switch/control board at another end, GI earth lead incased in and including 50 mm dia GI ‘light grade’ pipe from upper end of earth plate upto equipment with & including 20 mm dia bore GI pipe ‘light grade’ as water pipe from earth chamber to upper edge of the earth plate, GI funnel with wire mesh fixed on water pipe and provision of PCC 1:2:4 type B1(using 20 mm graded crushed stone aggregate) as in pits chamber and RCC pit cover 50 mm thick of precast RCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) duly reinforced with mild steel round bars 6 mm dia @ 150 mm c/c both ways with 10 mm dia mild steel bars as in lifting handles with and including necessary excavation & earth work including laying the GI pipe concealed in floor/wall all as per plate No. 3 of SSR Part I all as specified and directed and testing on completion..
M & L in replacement for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level, connected to galvanized steel earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel, all as shown in Electrical Plate No 3 of SSR Part - I, including necessary excavation and earth work, P.C.C (1:3:6) type C-I with 50 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 15 cm C/C both ways and suitable handle of 10 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel and 20 mm bore galvanized iron watering pipe (light grade), wire mesh, aluminium lugs, complete in all respect, GI earth wire protected by 15 mm bore (medium grade) galvanized iron pipe and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion complete all as specified and as directed by the Engineer-in-Charge. NOTE :- GI earth wire and protection pipe beyond 7.5 mtr will be measured and paid separately.
Lopping/prooning of tree branches upto the extend to obtain clearance all around the LT / HT over head lines conductor upto 3 metre from furthest conductor on pole including removing of cut branches and cleaning of site complete all as directed. Note :- (a). The trees branches etc will be left as it is and will not be carried away by the contractor/DEL as the wood belongs to CEO/DEO and they will be responsible to lift the wood. (b). Prooning of all tree branches up to 6 inches girth in one tree shall be measured as one Job. (c). Contractor will employ sufficient labour to complete the job with in time as directed. (d). Contractor will be responsible for any type of mis-happening/accident while prooning the trees. (e). Contractors supervisor will take proper shut down from MES installation before starting the work and clear it before resuming power supply . However full assistance will be provided by MES staff. (f). The contractor will provide proper tools and safety devices to his staff for prooning of trees.
M&L for Re-streching of loose over head ACSR conductor of any type/GI wire and repair of the broken conductors and adding new length (if required) in place of old and burnt conductor of any size on existing poles with proper sagging including winding with winding wire (Old conductor shall be reused wherever required for repairing broken length of conductor all as specified and directed. Note:- Five lines together will be measured as one span from pole to pole.
M&L painting to poles (9/11 metre long) including cross arms, 'V' brackets, 'D' clamps, nuts, bolts, complete including painting with five strips of 30cm each black and white paint in alternate strips from the base of pole upto 1.5 metres height, spray painting with two coat of synthetic enamel paint of first quality silver paint over a coat of red oxide primer after and including complete removal of old paint by scratching, rubbing all as specified and directed.
Supply, fixing in replacement, connecting and testing MCCBs in existing LT panel box/feeder pillar boxes (KIOSK) of capacity 400 Amps 4 pole breaking capacity 36 KA with thermal as well as magnetic balance adjustable type all as specified and directed. Make : L&T/SCHNEIDER/SIEMENS.
All as per Item No 37 here in before but 250 Amps and 36 KA. Make : L&T/SCHNEIDER/SIEMENS.
All as per Item No 37 here in before but 200 Amps and 36 KA. Make : L&T/SCHNEIDER/SIEMENS.
All as per Item No 37 here in before but 160 Amps and 36 KA. Make : L&T/SCHNEIDER/SIEMENS.
Repairing of existing unserviceable PCC coping of LT/HT pole by breaking completely and material and labour for PCC 1:2:4 type B1 (using 20mm graded crushed stone aggregate of size 600X600X300mm including form work and plastering and two coats of white wash all as specified and directed.
Supply and fix in repairs bracket made out of GI tubing single piece not wleded bended at proper angle of size 40mm dia, light grade 1.5 metre long including painting with aluminium paint over one coat of red oxide primer to the bracket etc complete including 1.0 sqmm 3.0 core flexible copper cable in PVC conduit with clamp from juction box to connecter of street light fitting all as specified and directed..
Supply and fix in repairs MS clamp (suitable for holding street light bracket on steel/PCC pole) made out of 40 mm wide 6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia -3 Nos with flat washer (3mm thick) -02 No for each including painting with aluminium paint over one coat of red oxide to the M.S clamps all as specified and directed..
Supply and fix in repairs of pole box size 450 x 300 x 200 mm fabricated out of 2 mm thick MS sheet having 4 Nos aluminium busbar of suitable size with 1 No. MCB SP 6 Amps front openable hinged cover outdoor type weather proof suitable for mounting on steel pole including fixing MS clamp 02 Nos with nuts, bolts and washers all as specified and directed. Make : HPL/ C&S/ Gourav.
Supply and fix in repairs broken earth pit of size 300x300x300 mm made of PCC 1:2:4 type B1 (using 20 mm graded crushed stone aggregate) reinforced with 8 mm dia TMT bars @ 150 mm centre to centre both ways with handle made out of 10 mm dia MS bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers etc as required at site with testing all as specified and directed.
Supply and fix in repairs of old unserviceable lugs after cutting the worn out /faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugs including crimping with crimping tools in the existing LT cable 3.5 core upto 50 Sqmm including necessary connection all as specified and directed.
All as per item No 46 above but aluminium lugs of size 70 to 120 Sq mm.
Supply and fix in repairs aluminium strip 25x3.15mm with saddles and fixing screws, insulators rawal plugs etc for conductor for roof and fixed on wall upto test point all as specified and directed.
Supply and fix in repairs wooden block heavy weight of size 30x30x30 cm with hole of 20 cm for fixing of air termination rod of any size including all as specified and directed.
Supply and fix in replacement of single pointed air termination Aluminium rod 12mm dia, 300 mm long all as specified and directed.
Supply and fix in repairs test point terminal block made of gun metal or phosphorous bronge 75x75x25mm of 6mm thickness drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head brass screws including box of size 90 x 90 x 90mm made of 1.6mm plain sheet and screwed to wall for protection of test point all as specified and directed.
Material and labour for spreading/laying 40 mm size crushed stone aggregate, evenly in power house yard all as specified and directed.
M&L in repairs danger notice plate for HT pole of size 25cm x 20cm of 1.6 mm thick mild steel sheet vitreous enarnelled white with letters figures and conventional skull and bones "DANGER" (English & Hindi) in signal red colour and fixed with MS clamps made of 25mm x 3mm MS flat iron bolts, nuts including two coat of aluminium paint over a coat of red oxide primer all as specified and directed.
Maintenance of power house comprises painting the yard with one coat of synthetic enamel paint after preperation of old steel surfaces as required and writing the designation of equipments in english alphabets/letters as specified and mainly the following:- (i) Iron gate - 01 No, (ii) Rolling shutter - 01 Nos, (iii) LT Panel Board-1 Nos, (iv) Capacitor Panel-1 Nos, (v) Chain link fencing, (vi) Transformer -02 Nos, (vii) ACB all as specified and directed.
M&L LT straight throw joint kit for 95 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
M&L LT straight throw joint kit for 70 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
M&L LT straight throw joint kit for 50 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
M&L LT straight throw joint kit for 35 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
M&L LT straight throw joint kit for 25 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
M&L LT End joint kit for 95 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
M&L LT End joint kit for 70 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
M&L LT End joint kit for 50 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
M&L LT End joint kit for 35 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
M&L LT End joint kit for 25 Sqmm size all as specified and directed. Make : Raychem/Birla-3M/Perreli/Denson.
Supply and Lay in repairs un-reinforced precast concrete cable covers, class LV, type-I, flat of size 250mm x 150mm x 40mm laid across in trenches for cable protection all as specified and directed.
Supply and fix in repairs stay by tightening of stay wire after untying the conductor spans from the poles to make correct tensions and maintain verticality of poles, including re-jointing the conductors in position with new binding wire all as specified and directed.
Supply and fix in repairs out door type Busbar Chambers of size 60x60x60 cm (Feeder piller box) fabricated by MS Sheet of size 3.14 mm gauge mounting on angle iron frame suitable for 415 Volts, 3 phase, 4 wire AC as specified and with and including aluminium bus bar of capacity 315 amp installed on porcelain insulators. The Busbar Chambers shall be dust proof, vermin proof, and 40 x 40 x 6 mm angle iron frame work, front opening with locking arrangement duly painted with two coats of grey enamel paint over a coat of red oxide primer on the outside and two coats of red oxide primer in the inside all as specified and directed. Make : HPL/ C&S/ Gourav.
Supply and laying in repacement, synthetic rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of size 2m x 1m all as specified and directed.
Supply and fix in repairs cable separator heavy duty made of plastic with PVC clamps heavy duty three phase separator all as specified and directed.
Amit Engineering
Bedi Refrigeration Works
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .