Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.0 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹37 L+₹1,480 (0.04%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹44.9 L+₹8.0 L (21.5%)Rejected-Finance NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L3 | Rejected-Finance NOT LOWEST | |
| 4 | Rejected-Technical | - | Rejected-Technical NOT RECOMMENDED DUE TO SHORTFALL OF DOCUMENTS | |
| 5 | Rejected-Technical 164 HIRANI NAGAR OPP SIDDHI VINAYAK TEMPLE MADHAPAR KUTCH 370 020 | KACHCHH | GUJARAT | 370020 | - | Rejected-Technical NOT RECOMMENDED |
Tender Value
Refer Docs
EMD Value
₹79,960
Closing Date
21 May 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) BHUJ
CWE (AF) BHUJ KHAVDA ROAD BHUJ KACHCHH 370001
PROVN OF POWER SUPPLY TO NFS BUILDING AT NALIYA AND MOTHALA AT AF STN NALIYA
2021_MES_425143_3
85227/E8
Open Tender
Civil Works
Item Rate
180 days
NALIYA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE (AF) NALIYA
₹79,960
Yes
23 Jul 2021
4 May 2021
24 May 2021
4 May 2021
21 May 2021
4 May 2021
60 days
Amount
Supply, installation, testing and commissioning of 11 KV, 630 Amps, Non- Extensible Outdoor Fixed Type (IP54), SF6 Gas Insulated RMU (Ring main unit CCV+M) comprising of 01 No. 630 Amps motorised fixed-type Vacuum Circuit Breaker module, inside robotically welded stainless steel 304 (Non Ferrite Non Megnetic Grade) tank having min. thickness 3+0.5 mm with IP 67 Degree of Protection and enhanced BIL of 125kVp internally to manage voltage surges and Air Insulated Metering Module of Class - 1. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions & complete with all accessories. The RMU shall be type tested for Internal arc test of 21kA/1 sec as per IEC62271-200. RMU shall have on-site-repairability features such as site replacable bushing/coupling/mechanism and gas refilling at site. The earthing busbar shall be provided inside each cable compartment for soilid earthing of Cable sheilds. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standard fitting as required at site. (Make: ABB/Siemens/Schneider)
(a) 01 No. VCB module consisting of following accessories:- (i) 11kV, 630A fixed-type Vaccum Circuit Breaker module for making and breaking of fault current alongwith disconnector+Earth Switch of full making capacity (ii) Short time current - 21KA/ 3 sec, Making Capacity - 52kAp (iii) Stored Enegry mechanism for moterised operation, associated closing/tripping coils, integrated non-removable spring-charging perating handle and ON/OFF push buttons mechanically latched to the mechanism Interlocked, arc-proof Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable with double-door arrangement (IP54+IP3X) safety interlocked to prevent access to cable termination in live-condition (iv) Right angle boots (push on type) (v) Numerical based self-powered OC+EF Protection Relay, providing OverCurrent (min. setting 20%), Earth-Fault (min. setting: 10%)
(vi) 03 Nos. CT (50 Amps ) for protection, Secondary of 1A, Burden-2.5VA, epoxy insulated, Ring Core CTs for protection (Acc.Cl.5P10), installed away from bushings to prevent saturation of core. (vii) 03 Nos. CT (50 Amps ) for metering, Secondary of 1A, Burden-2.5VA, epoxy insulated, Ring Core CTs for protection (Acc.Cl.1), installed away from bushings to prevent saturation of core. Suitable site replacable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes. (viii) Arc proof cable covers with self Interlocking mechanism between doors, earth switch, disconnector & VCB (ix) Capacitive voltage indication fixed type system (x) Mechanical Indications for breaker ON, OFF, EARTH, TRIP, Spring Charged-Discharged Multifunction Meter, Acc. Class - 1. (xi) Capacitive voltage indication fixed type VPIS 9-15 kV
(c) Necessay interclocking arrangement for safety and operations (d) One No. Operationg Handle for Manual Operation and one no. Manometer (e) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (f) Above switchgear shall confirm to all relevant IEC/IS Standards. (g) Vacuum interrupter should be of same make as RMU (h) Cable bushing should be replacable at site. (i) Minimum 5 modules except metering module should accommodate in one tank to avoid multiple coupling at site. (j) PCC foundation 45 cm above ground level or as per OEM recommendation all as directed by Engr-In-Charge.
All as per Item No.1 above but RMU (CCVV+M) indoor type Non-extensible comprising of 2 VCB module complete all as specified and directed by Engr-In-Charge.
Excavation in trenches n.exc. 1.5m wide and n.exc 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc. 10sqm on plan and n.exc. 1.5m in depth and getting out in soft/loose soil complete all as specified and directed by Engineer-in-Charge.
Returning filling in soil and including spreading leveling watering and well ramming in layers n.exc. 25 cm thick
Removing excavated soil to a distance n.exc. 50 mtr and depositing where directed at a level n.exc. 1.5m above the starting points.
M&L for sand cushioning for UG cables using dry sand; gently punning down all as directed and specified. Note: For measurement purpose punned thickness shall be considered.
M & L for unreinforced precast concrete cable covers CLASS HV type I, flat size 300 x 180 x 40 mm laid transverse to cable.
S&F GI tubing light grade for encasing cables for mechanical protection, laid under plinth/floors/ roads/ path /culverts or fixed on walls/on poles by means of MS FI clamps with necessary bolts, nuts and washers all as specified of size 100 mm bore all as specified and directed by Engr-In-Charge
Taking out Serviceable HT cables from excavated trenches, ducts, wall, pole etc including removing cable covers, sand, cable joints, pipes, clamps etc, taking out old serviceable cables for reuse , covers etc, for the sizes of cables 95 / 120 Sqmm all as specified and directed by Engr-In-Charge
Relaying / rerouting the serviceable HT 11 KV 3 core 95/120 sqmm of size cable in trenches/fixed to poles/wall, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable( HT ), all as specified and directed by Engr-In-Charge. Note: Excavation, earthwork, cable joints, sand coushing & cable cover will be measured and paid separately if required
S & F HT 11 KV 3 core 95 Sqmm cable in trenches/fixed to poles/wall, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable( HT), heavy duty with aluminium conductor, 11000 volts (earthed) grade 95 Sqmm x 3 core all as specified and directed by Engr-In-Charge. Note: Excavation, earthwork, cable joints, sand coushing & cable cover will be measured and paid separately if required
Supply, jointing and testing of cable joint kit of 11 KV grade cable for indoor cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 50-95 sqmm, complete all as specified and directed by Engr-In-Charge
Supply ,jointing and testing of cable joint kit of 11 KV grade cable for outdoor cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 50-95 sqmm, complete all as specified and directed by Engr-In-Charge
Supply ,jointing and testing of cable joint kit of 11 KV grade cable for straight through cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 50-95 sqmm, complete all as specified and directed by Engr-In-Charge
M&L for Earthing complete with Copper earth plate electrode 600x600x3.15 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to copper earth strip of 20 x 3.15 mm (up to 7.5m in length from earth plate) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shwon in electrical plate no 3 of SSR part 1 including Charcoal, Rock salt, necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS bar 8mm dia 150mm c/c reingorcement, watering funnel 32 mm dia light grade for protection of earth electrode 20 mm dia for watering all as speicified and directed and tested on completion. Note:- The unit rate quoted shall deemed to have included for GI protection pipe, Copper earth strip up to 7.5m, GI water pipe, wire mesh, funnel, excavation, RCC pit cover complete all as specified.
Supply, installation, commissioning and testing of transformer of 100 KVA, step down outdoor type complete with standard fittings, HT 11 KV 3 Phase LT 433 Volts, 3 phase 4 wire corrugated off circuit tape links of rating + 7.5 to -7.5% @ 2.5% by means of hand operated off load tap changing gear transformer copper wound, double wound, oil immersed naturaly cooled with external cooling tubes core type delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol Dy-11 (vector group with neutral brought on secondary side (LV side) and having tapping at +/-2.5% /+/ -5% and +/-7.5% to be changed the maximum temperature rises should not exceed 45 degee centigrade in oil and 55 degree centigrade in HV/LV winding ring measured by resistance after continuous full load run in ambient temp as per IS-11171 per transformer, IS-3639 for fitting & accessories, IS-2099 for high voltage porcelian bushings and the transformer shall be comprised with the following standard fitting with off load tappings on HT side to vary secondary voltage within limit all as per IS-2026 of capacity up to of following including all necessary PCC foundation/block masonary platform as directed by OEM:-
(i) Pressure release valve (ii) Thermometer pocket on tank over (iii) Oil temperature indicator with 2 contacts alarm & trip (iv) Rating plate with terminal marking (v) Two earthing terminals on tank and cover to facilate fixing of GI earth strip. (vi) Oil level guage (vii) Oil drain filter valve Note: (i) The transformer will have its initial oil filling to appropriate level (cost of oil including testing with desired electric strenght deemed to be included in quoted rate). (ii) The cost of foundation (civil work) shall deemed to be included in quoted rate for NFS Mothala & Naliya
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core all as specified and directed by Engr-In-Charge
Supply, fabricate, test and commissioning of LT electrical out door distribution panel board floor mounted cubical type dust proof, weather proof, vermin proof, astehically desiggned, having at least IP-54 degree of ingress protection, fabricated from 3mm thick CRCA sheet with front and rear opening including bus bar chamber, continuous GI strip earth bus bar 4 strips of Copper bus bar suitable Amps capacity, insulated color sleeves, procelain/epoxy insulators, rail channels cable alloy, danger notice board including over angle iron frame of size 40 x 40 x 6mm, 30 cm grouted in ground floor and 30 cm above GL including necessary excavation, foundation, PCC etc complete with locking arrangement duly powder coated painted of approved color connecting incoming & outgoing cable connection with suitable lugs, nuts, bolts, washers and cable joints, prewired complete with PVC insulated fire retardant copper conductor cable complete including:-
Sukhi Electricals
Anil Builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .