| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.4 LAccepted-Finance | L1 | Accepted-Finance L1 rate is accepted | |
| 2 | L2₹44.1 L+₹7.7 L (21.2%)Rejected-Finance BANGALORE KARNATAKA 560094 UDYAM KR 03 0017089 | BENGALURU URBAN | KARNATAKA | 560094 | L2 | Rejected-Finance L2 bid is rejected | |
| 3 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Others-Experience certificate was not attached. Also Copy of ESI/EPF registration, copy of memorandum of association, mandate form for ECS/EFT, certificate for tender form, copy of original power of attorney and duly filled bid form were not submitted. | |
| 4 | Not Admitted-Fee/PreQual/Technical 38 1067 NEAR POORNATHRAYEESA TEMPLE TRIPUNITHURA P O ERNAKULAM 682301 ERNAKULAM ERNAKULAM KERALA 682301 | ERNAKULAM | KERALA | 682301 | - | Not Admitted-Fee/PreQual/Technical Others-Signed NIT document was not submitted online. Also copy of original power of attorney was not submitted |
Tender Value
Refer Docs
EMD Value
₹77,097
Closing Date
19 Sept 2022, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
AGM Admin
O/o GM BSNL Kollam
MAINTAINANCE OF EA SETS AT VARIOUS TELEPHONE EXCHANGES AND BTS SITES UNDER KOLLAM BA FOR A PERIOD OF ONE YEAR (2022-23)
2022_BSNL_126951_1
MM Tender/EA MNTCE/KLM-BA/2022-23/04
Open Tender
Miscellaneous Services
Works
365 days
KOLLAM BA
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
AO Cash
₹77,097
Yes
31 Dec 2022
29 Aug 2022
20 Sept 2022
29 Aug 2022
19 Sept 2022
29 Aug 2022
29 Aug 2022 - 2 Sept 2022
Amount
PART A Providing periodical preventive maintenance of E/A sets of following capacities as per the BSNL standard maintenance scope & conditions attached.The work includes checking of all physical/functional parameters of EA set,checking of control panel(including AMF system control pannels also)and associated accessories,cleaning the EA set,oil level checking,checking and topping up of coolant and battery water, supplying and fixing of damaged fan belts/charging alternator belts/diesel flexible hoses/radiator hoses/diesel level indication tube etc,applying petroleum jelly on battery terminals,cleaning of air filter assembly, arrangement of spare battery/starting motor(for the period the existing one is being repaired/replaced) etc as required. (Periodic preventive maintenance site visit shall be done ONCE IN THREE months however breakdown situations of the EA set shall be promptly attended and cleared as and when reported as per the terms and conditions of the agreement) Note-Supplying and fixing of major spares are not included under the scope of this item and are included as part C SPARES/CONSUMABLES of this schedule.
up to 10 KVA
Above 10 KVA and up to 15 KVA
Above 15 KVA and up to 30 KVA
Above 30 KVA and up to 40 KVA
Above 40 KVA and up to 63 KVA
Above 63 KVA and up to 100 KVA
Above 100 KVA and up to 160 KVA
Above 160 KVA and up to 250 KVA
Above 250 KVA and up to 300 KVA
Above 350 KVA and up to 400 KVA
PART B Carrying out oil servicing of following capacity EA set i/c draining the existing lub oil and supplying and filling of superior quality and suitable grade for the engine lub oil (15 W 40), replacing of fuel filters, lub oil filters etc complete as per the maintenance schedule, terms and conditions and specifications attached.
up to 10 KVA
Above 10 KVA and up to 15 KVA
Above 15 KVA and up to 30 KVA
Above 30 KVA and up to 40 KVA
Above 40 KVA and up to 63 KVA
Above 63 KVA and up to 100 KVA
Above 100 KVA and up to 160 KVA
Above 160 KVA and up to 250 KVA
Above 250 KVA and up to 300 KVA
Above 350 KVA and up to 400 KVA
Note:-The servicing of the EA sets has to be done once in a year or 500 hours as per direction of Engineer in charge.
PART B Replacement of faulty batteries which are life expired (3 years or more) with new fully charged semi sealed battery of automotive duty of the following capacities (BSNL approved make and Batteries shall have replacement warranty for a minimum period of 24 months).
NOTE:_ Faulty Batteries whose life has exceeded 3 years only are included in the scope of the above item. Faulty battery of less than 3 years shall be replaced by the maintenance contractor free of cost.
PART C:- SPARES AND COSUMABLES
Replacement of faulty Microprocessor based AMF Controller with new one suitable for the required capacity single/ three phase EA sets compatible for Water/Air cooled Engine in the existing AMF control panel including disconnecting and dismantling the faulty one, including providing and fixing all accessories , making necessary wiring arrangements including functional testing and commissioning as per site conditions and specifications attached.(Make:BSNL Approved Make and model only shall be provided)
Replacement of faulty contactor coil of suitable voltage rating for the existing Contactor of up to 63A i/c dismantling the item, giving connection / interconnections including testing and commissioning as reqd.(Make:M/s L& T / Schneider Electric/ Siemens/Telemecanique)
Repairing of faulty starting motor including replacement of major spares/rewinding of armature/field etc including dismantling baking / heating varnishing refixing etc of EA sets upto upto 63 KVA etc as reqd
Repairing of faulty starting motor including replacement of major spares/rewinding of armature/field etc including dismantling baking / heating varnishing refixing etc of EA sets above 63 KVA upto 125 KVA etc as reqd
Repairing of faulty starting motor including replacement of major spares/rewinding of armature/field etc including dismantling baking / heating varnishing refixing etc of EA sets above 125 KVA upto 400 KVA etc as reqd
Replacement of faulty Battery charger unit with new one, SMPS based ,Horizontal mounting type, input voltage 170-260 V AC,50 Hz ,Output 12 V DC @ 10 A suitable for Battery including mounting, making connections ,testing and commissioning as required.
Replacement of faulty Battery charger unit with new one, SMPS based ,Horizontal mounting type, input voltage 170-260 V AC,50 Hz ,Output 24 V DC ,20 A suitable for Battery including mounting, making connections , testing and commissioning as required.
S/F of the following spares for the E/A set for the smooth functioning of the system i/c checking the items and replacing the faulty one. giving necessary connections testing and commissioning etc as reqd.
LVM relay
START/STOP push button
START/STOP relay
Electronic hour meter
Fuel gauge
12V ,Stop solenoid
24V ,Stop solenoid
32 Amps ," c " series ,TP , MCB
32 Amps ," c " series ,4P , MCB
32 Amps ," c " series , DP , MCB
10 Amps ," c " series , DP , MCB
63A ,4P ,3way + off, Rotory Changeover switch
Add on block (2NO+ 2NC)
Diesel Metalic braided flexible pipe lenth above 1 Mtr.
Copper sockets of battey cable
LLOP senser
HCT senser
12 V /24 V OEN/Ply relay plug in type
Electronic AVR suitable for EA set up to 63 KVA
Electronic AVR suitable for EA set above 63 KVA
4 Pole , 415 V , 40 A Power contactor
4 Pole , 415 V ,63 A Power contactor
63A ,4P,MCCB ,30KA breaking capacity .(Make L&T/SS)
Blower fan bearing
Mechanical interlock for 2 Nos, 32/63A, 4 Pole contactors
Arresting the leakage of the exhaust line i/c dismantling the same from flange , welding , re-fixing etc complete as required
S/F residential type silencer suitable for 7.5/15KVA EA set i/c providing new necessary brackets for fixing , welding ,dismantling the existing faulty one etc complete as required .
Supplying and fixing 65/75mm dia 30 cm lenth mettalic flexible bellows i/c cutting the existing exhaust line welding ,fixing etc complete as required .
Supplying and fixing rubber type AVM pad suitable for 7.5 /15 KVA Engine Alternator by lifting /raising the engine from base , dismatling the faulty one ,fixing ,testing, comissioning etc complete as required.(Make : Polybond/s.s make )(Make : Polybond/ss make)(Rate per Each)
Supplying and fixing rubber type AVM pad suitable for 30 to 63 KVA Engine Alternator by lifting /raising the engine from base , dismatling the faulty one ,fixing ,testing,comissioning etc complete as required.(Make : Polybond/s.s make )(Make : Polybond/ss make)(Rate per Each)
Supplying and fixing rubber type coupling of EA set upto 63KVA i/c dismantling the faulty one as required .
Reparing of existing AMF controller with help of respective OEM ,to and fro transpoation ,giving connection ,testing etc as required
Repairing of existing 12V/24V Volt battery charger (Any model or make), refixing, connections,testing commissioning etc as required .
Repairing/servicing of fuel injector of EA sets upto 63KVA capacity including dismantling,to and fro transportaion, refixing testing commissioning etc as reqd.(rate per injector)
Dismantling of existing 88/130/150/180 AH lead acid battery ,re-charging the battery by replacing the acid ,to and fro transportation ,re-fixing the same as required .
Supplying and Fixing 380mm sweep heavy duty fresh air fan in the existing DG set canopy upto 15 KVA i/c providing necessary clamping arrangement ,nuts ,bolts ,giving connection etc complete as required .(Make : Almonard /s.s make )
Rewinding of 250/380mm sweep heavy duty fresh air fan /exhaust fan in the existing DG set canopy i/c to and fro transpoatation ,fixing etc as required .
Supplying and laying 4x16 Sq: mm aluminum conductor armoured cable in surface /pipe /loose in panel as required .
Supplying and laying 4x10 Sq: mm aluminum conductor armoured cable in surface /pipe /loose in panel as required .
Supplying and filling 15 W40 engine oil suitable for various capacity engine as required.
Arresting oil leakage of EA sets(upto 15 KVA) by minor repairing works like replacement of side gaskets,head cover gaskets and front oil seal etc comp as reqd.
Arresting oil leakage of EA sets(above 15KVA to 63KVA) by minor repairing works like replacement of side gaskets,head cover gaskets and front oil seal etc comp as reqd.
Repairing/servicing of fuel lift pump of 15KVA to 63 KVA capacity range EA sets including dismantling refixing testing commissioning as reqd.
Supplying and fixing fuel lift pump suitable for 15 KVA to 63KVA i/c dismanling the faulty one ,fixing the new one ,testing etc as required including testing commissioning as reqd.
Repairing and servicing of Radiator including dismantling,transportation between workshop and site,necessary welding and bypassing of damaged fins/tubes etc refixing testing commissioning as reqd.(above 15KVA to 63KVA)
Servicing of radiator including dismantling,cleaning at site itself with water and cleaning agent,refixing testing commissioning etc as reqd.(For 15KVA EA sets)
Servicing of radiator including dismantling,cleaning at site itself with water and cleaning agent,refixing testing commissioning etc as reqd.(above 15KVA to 63KVA)
Repairing/servicing of fuel injection pump of EA sets(upto 3 cylinder models) including dismantling,to and fro transportaion, refixing testing commissioning etc as reqd.
Repairing/servicing of fuel injection pump of EA sets(4 to 6 cylinder model) including dismantling,to and fro transportaion, refixing testing commissioning etc as reqd.
Providing Trolley mounted EA set of following capacities on daily rental basis on emergency situation as per direction of officer in charge including transportation connections with suitable size cable testing etc as reqd.(diesel will be arranged by department)
up to 30 KVA EA set
> 30 KVA to 63 KVA EA set
Attending to roof leak of DG canopy by fixing tar sheet on roof, after cleaning the surface and applying one coat of anti-corrosive paint etc as reqd.
Supplying and fixing 20mm class C MS pipe suitable for diesel fuel line i/c cutting , welding . Grinding including cutting floor and replacing the damaged line , painting, making good the damages etc as reqd.
Supplying and fixing water pump suitable for DG set Radiatotr i/c dismanling the faulty one ,fixing the new one ,testing etc as required .
30 to 63 KVA
Servicing of the existing diesel tank of the RTU EA set i/c dismantling , cleaning the tank , and re-fixing etc as required .
Supplying and fixing hand fuel pump testing etc as required .
Supplying wrapping fixing 8/10mm asbestoes rope around the exhaust line for heat insulation as required
Dolar Systems and Services Pvt Ltd
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .