Loading…
Loading…
Tender Value
₹94.5 L
EMD Value
₹1.9 L
Closing Date
21 Oct 2026, 3:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
MAINTENANC
15 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V = Advertised value of the tender in crores of Rupees N = Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The tenderer shall possess a valid Electrical Contractor License, issued by any State Government or Union Territory Administration, authorizing execution of electrical works up to 650 V. The contractor shall have in his employment or shall engage a person holding a valid certificate of competency issued by any State Government or Union Territory Administration for supervision of electrical works up to 650 V.Offers not accompanied by a valid Electrical Contractor License and requisite Supervisor competency for works up to 650 V shall be summarily rejected.
Similar Nature of Work: Supply, installation, testing and commissioning of LT/HT electrical GS assets ORSupply, installation, testing and commissioning of electrification or rewiring of building/workshop. ORSupply, installation, testing and commissioning of Yard/circulating area/street lighting/tunnel/facade lighting. ORSupply, installation, testing and commissioning of high-mast lighting. ORSupply, installation, testing and commissioning of glow signages. ORSupply, installation, testing and commissioning of LT/HT electrical GS sub-station with at least 50% capacity of proposed sub-station ORRepair/overhauling of LT/HT electrical GS assets including LT/HT sub-stations.
49 conditions · 8 needing a document upload
The tenderer shall clearly specify whether the tender is submitted on his own (Proprietary Firm) or on behalf of a Partnership Firm / Company / Joint Venture (JV) / Registered Society /Registered Trust / Hindu Undivided Family (HUF) /Limited Liability Partnership (LLP) etc., and corresponding documents shall be submitted by the tenderer as per the composition of the Firm.
The Bid Security shall be deposited either in cash through e payment gateway or submitted as Bank Guarantee bond from a scheduled commercial bank of India or as mentioned in tender documents. The Bank Guarantee bond shall be as per Annexure- VIA of GCC and shall be valid for a period of 90 days beyond thebid validity period. Non-submission of scanned copy of Bank Guarantee with the bid on e-tendering portal (IREPS) and/or non- submission of original Bank Guarantee within the specified period shall lead to summary rejection of bid. The original Bank Guarantee should be delivered in person to the official nominated as indicated in the tender document within 5 working days of deadline of submission of bids.
Eligibility criteria: Eligibility criteria shall be mandatorily incumbent upon the tenderer to identify, state and submit the supporting documents duly self attested/digitally signed by which they/he is qualifying the Qualifying Criteria mentioned in the Tender Document.
Tender Form (First sheet, Second sheet) of The GCC April 2022.
Certificate format (Affidavit) which available as Annexure - V in Mandatory documents. A facility has already created for online submission of Annexure V of GCC in IREPS module; uploading of physically signed Annexure V by tenderer has been discontinued
The tenderer shall clearly specify whether the tender is submitted on his own (Proprietary Firm) or on behalf of a Partnership Firm / Company / Joint Venture (JV) / Registered Society /Registered Trust / Hindu Undivided Family (HUF) /Limited Liability Partnership (LLP) etc.
The corresponding documents shall be submitted by the tenderer as per the composition of the Firm: Sole Proprietorship Firm: (i) All documents in terms of Para 10 of the Tender Form (Second Sheet) above. HUF: (i) A copy of a notarized affidavit on Stamp Paper declaring that he who is submitting the tender onbehalf of HUF is in the position of 'Karta' of Hindu Undivided Family (HUF) and he has the authority, power and consent given by other members to act on behalf of HUF. (ii) All other documents in terms of Para 10 of the Tender Form (Second Sheet) above. Partnership Firm: (i) All documents as mentionedin para18 of the Tender Form (Second Sheet). Company registered under Companies Act2013: (i) The copies of MOA (Memorandum of Association) / AOA (Articles of Association) of the company (ii) A copy of Certificate of Incorporation (iii) A copy of Authorization/Power of Attorney issued by the Company(backed by the resolution of Board of Directors) in favour of the individual to sign the tender on behalf of the company and create liability against the company. (iv) All other documents in terms Para 10 of the Tender Form (Second Sheet) above. LLP (Limited Liability Partnership): (i) A copy of LLP Agreement (ii) A copy of Certificate of Incorporation (iii) A copy of Power of Attorney/Authorization issued by the LLP in favour of the individual to sign the tender on behalf of the LLP and create liability against the LLP. (iv) An undertaking by all partners of the LLP that they are not blacklisted or debarred by Railways or any other Ministry / Department of the Govt. of India from participation in tenders/contracts as on the date of submission of bids, either in their individual capacity or in any firm/LLP or JV in which they were/are partners/members. Concealment / wrong information in regard to above shall make the contract liable for determination under Clause 62 of the Standard General Conditions of Contract. (v) All other documents in terms of Para10 of the Tender Form (Second Sheet). Registered Society & Registered Trust: (i) A copy of Certificate of Registration (ii) A copy of Memorandum of Association of Society/Trust Deed (iii) A copy of Power of Attorney in favour of the individual to sign the tender documents andcreate liability against the Society/Trust.(iv) A copy of Rules & Regulations of the Society (v) All other documents in terms of Para 10 of the Tender Form (Second Sheet) above.
The tenderer shall be required to submit the Bid Security with the tender for the due performance with the stipulation to keep the offer open till such date as per Clause No.5 of PART -1 of The GCC, April 2022.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Guntakal- Upgradation of Running Room building by providing all specified facilities with 60 bed capacity with Air conditioning - Electrical arrangements.
GTL-EM-48-2026-27~SCOR
GTL-EM-48-2026-27
Open
Works - General
9 Months
Anantapur, Andhra Pradesh
₹0
₹1.9 L
28 Sept 2026
28 Sept 2026
7 Oct 2026
159 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 94,49,627.91 | ||
| — | Breakup | for details. | — | ||
| Supplying and fixing of 20mm size of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.(DSR-2025-item no-1.21.1) | — | — | — | 75,500 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 25 mm size of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required..(DSR-2025-item no-1.21.2) | — | — | — | 1,68,000 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 32 mm size of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.(DSR-2025-item no-1.21.3) | — | — | — | 62,700 | |
| — | Breakup | for details. | — | ||
| Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.- Group- C(DSR-2025- item no-1.10.3)( consignee inspection) | — | — | — | 5,96,400 | |
| — | Breakup | for details. | — | ||
| Wiring for circuit/ submain wiring along with earth wire with (2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire sizes) of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required.(DSR-2025-item no-1.14.2) | — | — | — | 3,11,000 | |
| — | Breakup | for details. | — | ||
| Wiring for circuit/ submain wiring along with earth wire with (2 X 4 sq. mm + 1 X 4 sq. mm earth wire sizes) of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required.(DSR-2025-item no-1.14.3) | — | — | — | 3,73,000 | |
| — | Breakup | for details. | — | ||
| Wiring for circuit/ submain wiring along with earth wire with (2 X 6 sq. mm + 1 X 6 sq. mm earth wire sizes) of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required.(DSR-2025-item no-1.14.4) | — | — | — | 1,44,600 | |
| — | Breakup | for details. | — | ||
| Supply, laying, connecting and commissioning of 4 core 6 Sq.mm. 1100 PVC (FRLS) insulated and PVC round sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt, Conforming to IS 694 : 2010 | — | — | — | 2,54,555 | |
| — | Breakup | for details. | — | ||
| Supply, laying, connecting and commissioning of 4 core 10 sq.mm. PVC (FRLS) insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt, Conforming to IS 694 : 2010 | — | — | — | 1,79,872 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 5/6 A modular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(DSR-2025-item no-1.24.1) | — | — | — | 12,100 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 15/16 A modular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(DSR-2025-item no- 1.24.3) | — | — | — | 8,800 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 3 pin 5/6 A modular socket outlet on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(DSR-2025- item no-1.24.4) | — | — | — | 13,600 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 6 pin 15/16 A modular socket outlet on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(DSR-2025- item no-1.24.5) | — | — | — | 10,950 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 2 Module (75mmX75mm), GI box along with modular base & cover plate for modular switches in recess etc. as required.(DSR-2025-item no-1.27.1) | — | — | — | 17,700 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 4 Module (125mmX75mm), GI box along with modular base & cover plate for modular switches in recess etc. as required.(DSR-2025-item no-1.27.3) | — | — | — | 20,050 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 8 Module (125mmX125mm), GI box along with modular base & cover plate for modular switches in recess etc. as required.(DSR-2025-item no-1.27.5) | — | — | — | 31,020 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 12 Module (200mmX150mm), GI box along with modular base & cover plate for modular switches in recess etc. as required.(DSR-2025-item no-1.27.6) | — | — | — | 30,700 | |
| — | Breakup | for details. | — | ||
| supply and fixing fo 16 A combined unit with conealed metal box with 4M cover Plate+ 16 A Socket + 16 A Magnus plug top equivalent to model no: AA 4 068 of GM Make (glossy white) for AC points. | — | — | — | 20,229 | |
| — | Breakup | for details. | — | ||
| "LED Down lighter (COB Type) (System lumen efficacy >=120 lm/Watt )Supplying, Installation, Testing & Commissioning of 22 watt LED Recessed/surface Down lighter (Round / square/ Rectangular) COB Type of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.>=0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. ""complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >=120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector.(DSR-2025-item no-8.5.5)" | — | — | — | 2,25,900 | |
| — | Breakup | for details. | — | ||
| "LED Batten light (System lumen efficacy >=120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of 4 Feet, 40 watt LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.>=0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 6500°K(As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >= 120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) (DSR-2025-item no-8.10.4)" | — | — | — | 38,950 | |
| — | Breakup | for details. | — | ||
| Supply and Fixing of 4 feet 20W LED tube light with Radar motion sensor. The fittings have to be fixed on the wall / Ceiling / FOB with suitable clamps. CCT 5700 K -6200 K Luminious flux : 1400-1600 Lpm , Input Voltage : 100-240 V , 50 Hz Power factor > 0.9, SMD LED 3014:117 Pcs , BEAM angle :180, CRI>71. Ingress protection: IP20, base : Aluminium alloy housing cover : Forged , PVC lamp holder : PC /ABS , Action distance : phase 3 to 6 m .Suitable Box type fittings for LED lamps has to be supplied by the contractor. | — | — | — | 32,620 | |
| — | Breakup | for details. | — | ||
| Supply erection testing and commissioning of 2 feet-8 w sensor based tube set (set includes sensor LED tube, Housing, 1 Mtr Cable ) wattage :16 W @max, 3w dim , CCT5700 K -6200 K Luminious flux : 1400-1600Lpm , Input Voltage : 100-240 V, 50 Hz Power factor > 0.9, SMD LED 3014:117 Pcs, BEAM angale :180, CRI>71. Ingressprotection: IP20, Base : Aluminium alloy cover : Forged , PVC lamp holder : PC /ABS, Action distance : phase 3 to 6 m with 120.(2) Supply of Housing for fixing LED tube. Make : Nano, Bright solar, ECP lightingsolutions, Procorp earntech pvt ltd, solar innovation & system. LED make Nichia, CREE, Osram, Seoulsemi, samsung, Brgelux. | — | — | — | 28,684.26 | |
| — | Breakup | for details. | — | ||
| Supply, fixing and commissioning of Foot lamp 4 watt LED 4modular with 4 modular concealed box with enclosure for night light with necessary accessories complete or equivalent make. | — | — | — | 22,980 | |
| — | Breakup | for details. | — | ||
| Supply, fixing, connecting and comissioning of Bedside Flexible Gooseneck Arm Reading Light, 3watt conforming to IS:16101 of model no.48042 of Philps make or it's equivalentwith all necessary accessories complete. Make:Havells, Bajaj, Syska, Halonix,Philips. | — | — | — | 61,140 | |
| — | Breakup | for details. | — | ||
| Supply and Erection of LINNET Aesthetically designed linear mirror LED light 7W Provided with a high output PMMA diffuser for glare free light conforming to IS:10322 or its latest amendment, of model no. LCL-07-CDL of Crompton make or it's equavalent with all necessary accessories complete. | — | — | — | 15,792 | |
| — | Breakup | for details. | — | ||
| Supply and fixing of Make:Dyson,Dryflow,D-flow,Turboforce. | — | — | — | 14,375 | |
| — | Breakup | for details. | — | ||
| Supply and fixing of Pesto Flash insect killer 230V, 50Hz with 02 Nos of Ultra Violet Lamps, Make:PCL,Havells,Phillips | — | — | — | 6,900 | |
| — | Breakup | for details. | — | ||
| Supply of self contained drinking water cooler of capacity 150 Lrs cooling capacity and 150 Ltrs storage capacity, confirm to IS: 1475 (part-i) 2001 suitable for operation on 230 Volts +10%, 50 Hz single phase AC supply with latest amendments etc. Make: Usha/Blue star/Volts only | — | — | — | 91,158 | |
| — | Breakup | for details. | — | ||
| Supply and erection of 10 W LED bollard light with IP66 to ensure sustainble performance in all section and aesthetics with foundation and all connected accessories complete. | — | — | — | 1,50,797.5 | |
| — | Breakup | for details. | — | ||
| "Brush Less Direct Current (BLDC) Fan with RemoteSupply, Installation, Testing and Commissioning of ceiling fan with 1200mm Sweep, service value >=6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum), Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades,30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. (DSR-2025-item no-9.1.3)" | — | — | — | 2,01,740 | |
| — | Breakup | for details. | — | ||
| Supply and fixing of 300m Heavy Duty Exhaust fans as per IS:2312:1967 or latest including necessary plastering, Massinory work and clamps nuts bolts etc. | — | — | — | 14,050 | |
| — | Breakup | for details. | — | ||
| Supply and fixing of BLDC star 200 mm 20W 1600 RPM Exhaust fans including necessary plastering, Massinory work and clamps nuts bolts etc. | — | — | — | 36,840 | |
| — | Breakup | for details. | — | ||
| Supply and fixing of BLDC Air circulators 400 mm sweep with 1500 RPM 32W Equivalent to EFFICIO + model of Atomberg Make including necessary plastering, Massinory work and clamps nuts bolts etc... | — | — | — | 48,100 | |
| — | Breakup | for details. | — | ||
| Supply, Transportaion, Erection & commissioning of 5mtr long hot dip galvanised Octagonal pole (IS 875) with 130mm bottom A/F & 70mm top A/F made up of 3mm thick HT sheet (S 355 JO steel plate for shaft), along with base plate IS 2062 of size 200x200x12mm, M16x600 long J type EN8 grade foundation bolts, 1000mm long single/ Double arm bracket Including the Supply of Suitable bolts with Bakelite Sheet with MCB ( for mounting inside the base compartment of pole ) including Erection & commissioning of 5 mtr. octagonal pole including RCC concrete foundation & plinth in hard soil including excavation of soil, tamping of concrete, grounting and supply of other required materials and accessories complete. | — | — | — | 91,868 | |
| — | Breakup | for details. | — | ||
| Service connection to the fitting from the junction box of 5 mtrs Octogonal pole by means of PVC insulated copper conductor of 3 core 1.5 Sq mm with necessary lugs at the juction box and necessary termination at the luminaire complete. | — | — | — | 1,825 | |
| — | Breakup | for details. | — | ||
| "LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >=120 <135 lm/Watt)Supplying, installation, Testing & Commissioning of 50 Watt Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.>=0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >=120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). (DSR-2025-item no-8.13.10)" | — | — | — | 19,340 | |
| — | Breakup | for details. | — | ||
| Supply and fixing of the gate lamp in aluminum die cast with modern artistic design and white PC diffuser suitable for retrofit LED of model no: LHFOAQE1NZ5K7X5 of Havells make or its equivalent in reputed makes | — | — | — | 4,020 | |
| — | Breakup | for details. | — | ||
| "LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy >=120 and <135 lm/Watt).Supplying, Installation, Testing & Commissioning of 100 Watt Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.>=0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >=120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). (DSR-2025-item no-8.16.3)" | — | — | — | 17,269 | |
| — | Breakup | for details. | — | ||
| Supply, Transportation and fixing of storage / Pressure type Vertical / Horizontal 230/250V Single phase 2000watts ISI mark 5 Star rated water heater with SS/MS Glass lined tank and ABS plastic body of 15 Ltrs capacity to withstand up to 6.5 bar of water pressure conforming to IS:2082/93 including all standard accessories and dead weight pressure reducing valve on out let side, including cost of 2 Nos nylon / PVC / Metallic hose pipe, testing and all labour charges etc., complete. Makes: Crompton model No. solarium plus SWH 725, Class 1 rated or its equivalent make of Make Bajaj,AO Smith,Venus,V-Guard. | — | — | — | 1,44,960 | |
| — | Breakup | for details. | — | ||
| Supply and fixing of ON Delay/Interval timer in above junction box of Supply Voltage - 20-240VAC, 50/60Hz Model - 800XU | — | — | — | 9,248 | |
| — | Breakup | for details. | — | ||
| supply and fixing of 3 Pole AC Power Contactor 25 Amp 1 NO 1NC AC 3 PH 415 V Coil Voltage 110 V AC Aux. | — | — | — | 15,536 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 12 way , Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).(DSR-2025-item no-2.3.3) | — | — | — | 34,452 | |
| — | Breakup | for details. | — | ||
| Supply and erection of 32A, C-curve 3P MCBs with 10KA breaking capacity with all necessary accessories complete. | — | — | — | 17,064 | |
| — | Breakup | for details. | — | ||
| Supply and Erection of B curve 16 SP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection as per IS/IEC 60898 - 1 with its latest amendments including all connected accessories. | — | — | — | 22,080 | |
| — | Breakup | for details. | — | ||
| Supply fixing connecting and comissioning of 18 way SPN Distribution board 12 module of model no. 5076 04 with metal door of legrand make or equivalent make comprising of the following switchgear of make with all connecting accessories complete. | — | — | — | 8,349.6 | |
| — | Breakup | for details. | — | ||
| Supply and erection of 63A, C-curve 3P MCBs with 10KA breaking capacity with all necessary accessories complete. | — | — | — | 68,607 | |
| — | Breakup | for details. | — | ||
| Supply and Erection of B curve 32 SP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection as per IS/IEC 60898 - 1 with its latest amendments including all connected accessories. | — | — | — | 6,440 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing of 12 way (4 + 36), Double door, surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) (DSR-2025-item no-2.5.3) | — | — | — | 67,560 | |
| — | Breakup | for details. | — | ||
| Supply and Erection of B curve 10A SP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection as per IS/IEC 60898 - 1 with its latest amendments including all connected accessories. | — | — | — | 6,900 | |
| — | Breakup | for details. | — | ||
| Supply and Erection of B curve 20A SP MCBs of Rated Short-Circuit Breaking Capacity 10kA of IP 20 Protection as per IS/IEC 60898 - 1 with its latest amendments including all connected accessories. | — | — | — | 4,600 | |
| — | Breakup | for details. | — | ||
| Supply, fixing and connecting of 2pole 2 module 16A Lexic RCBOs conforming to IS 12640-2(2008) or latest as advised by the site supervisor with all necessary accessories complete. | — | — | — | 50,967 | |
| — | Breakup | for details. | — | ||
| Supply and fixing of 32 A Electromechanical 4P RCBO 30 mA sensitivity as per in accordance with IS 12640-2(2008) or latest with necessary connections and all accessores complete. | — | — | — | 65,971.5 | |
| — | Breakup | for details. | — | ||
| Supply, fixing, testing and commissioning of RCBO 63A, Four pole, 30mA as per in accordance with IS 12640-2(2008) or latest with all necessary accessories complete as advised by the site supervisor. | — | — | — | 52,976 | |
| — | Breakup | for details. | — | ||
| Supply, Laying, Testing and Termination of 4 core 120 sqmm XLPE insulated underground armoured aluminium cable with heat resistant insulation as per IS 7098(Part 1)1988 with latest amendments and with necassary lugs and terminations. | — | — | — | 4,29,270 | |
| — | Breakup | for details. | — | ||
| Supply fixing, of HDPE pipe of 75 mm outer dia of PE-100,PN6 class as per IS 4984- 2016 or latest amendment with suitable couplings and clamps for cable laying with all necessary accessories complete. | — | — | — | 90,500 | |
| — | Breakup | for details. | — | ||
| Supply, Laying, Testing and Termination of 1.1 KV Grade 4 core 50 sqmm XLPE insulated PVC sheathed Aluminium armoured cable as per IS 7098(Part 1)1988 with latest amendments and with necassary lugs and terminations. | — | — | — | 1,72,340 | |
| — | Breakup | for details. | — | ||
| "Supply and laying of HDPE pipe of PE-80 grade in PN-4 size 2"" inner dia and outer dia 63 mm and wall thickness minimum 2.5mm, maximum 2.8 mm with 'T' joints, bolts, elbows etc. including all other connected accessories.Make: M/s. Sudhakar/NagarjunaPolymers/Nandi/ Narmada/KC polymer " | — | — | — | 55,000 | |
| — | Breakup | for details. | — | ||
| Supply, Laying, Testing and Termination of 1.1 KV Grade 4 core 16 sqmm XLPE insulated PVC sheathed Aluminium armoured cable as per IS 7098(Part 1)1988 with latest amendments and with necassary lugs and terminations. | — | — | — | 28,496 | |
| — | Breakup | for details. | — | ||
| Supply and Erection of HDPE pipe of 40 mm of PE 63 grade, PN8 as per IS 4984-2016 with latest amendments and with suitable couplings and clamps for cable laying with all necessary accessories complete. | — | — | — | 19,000 | |
| — | Breakup | for details. | — | ||
| Supply and laying of 8 SWG GI wire with 40GSM ZinC coated, conforming to IS:280- 2006 or latest, it is to be laid with armourd cable for earth continuity. | — | — | — | 12,000 | |
| — | Breakup | for details. | — | ||
| Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.(DSR-2025-item no-5.15) | — | — | — | 57,400 | |
| — | Breakup | for details. | — | ||
| Supply, Erection and connecting of Cable Junction Boxes IP 55 / IP 65 with metric knockouts for cable entry Cable junction boxes of model no. K 9255 of Hensel make or equivalent make conforming to IS:13573/92,IEC 60947-3 with necessary terminals suitable for cables upto 25 Sq mm and all necessary accessories complete. | — | — | — | 7,080 | |
| — | Breakup | for details. | — | ||
| Supply, Erection and connecting of Cable Junction Boxes IP 65 with metric knockouts for cable entry Cable junction boxes of model no. K 7004 of Hensel make or equivalent make conforming to IS:13573/92,IEC 60947-3 with necessary terminals suitable for cables upto 70Sq mm and all necessary accessories complete. | — | — | — | 88,780 | |
| — | Breakup | for details. | — | ||
| Supply, Erection and connecting of Cable Junction Boxes IP 55 / IP 65 with metric knockouts for cable entry Cable junction boxes of model no. K 1204 of Hensel make or equivalent make with necessary terminals suitable for cables upto 150Sq mm and all necessary accessories complete. | — | — | — | 96,480 | |
| — | Breakup | for details. | — | ||
| Excavation for cable trenches of depth upto 1.2 m in All kinds of soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres. (DSR-2025-item no-2.6.1) | — | — | — | 42,600 | |
| — | Breakup | for details. | — | ||
| Filling available excavated earth (excluding rock) in trenches, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer without ramming and watering, lead up to 50 metres.(DSR-2025-item no-15.3) | — | — | — | 33,360 | |
| — | Breakup | for details. | — | ||
| Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. (DSR-2025-item no-10.1) | — | — | — | 5,980 | |
| — | Breakup | for details. | — | ||
| Excavation of cable trench of size 400mm x 1 mtr deep track X-ing/Road X-ing and making good of the same to its original form and shape completely including all connected materials and works to the satisfaction of Railways site Engineer and also as per R.B JPO no: No.2003/Tele/RCIL/I Pt.IX dated 24.06.2013.. .The exact route of the HT/LT cable is to be decided in consultation with Engineer in charge. | — | — | — | 19,146.5 | |
| — | Breakup | for details. | — | ||
| Excavation of cable trench in cement concrete bed flooring by using power drill to a depth of 1.0 Mtr and a width of 0.3mtr. After laying the pipe and refilling the trench with excavated earth and undertaking cement concrete bed flooring to its original shape as was prevailing earlier to the satisfaction of Railways site Engineer and also as per R.B JPO no: No.2003/Tele/RCIL/I Pt.IX dated 24.06.2013.The exact route of the HT/LT cable is to be decided in consultation with Engineer in charge. | — | — | — | 44,676 | |
| — | Breakup | for details. | — | ||
| Design, manufacture, display and installation of wall /hanging / floor mounting type LED illuminated sign / direction boards in fl a t shape. All the specifications are as per Standard Signages at Stations On Indian Railways- April-2023 or its latest amendment.The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage. | — | — | — | 72,275 | |
| — | Breakup | for details. | — | ||
| Supply and fixing of HOTEL KEY FOB SWITCH 32Amp DP Switch with indicator (LED) operated by key FOB, 240V (Key FOB included) equivalent to model no: AA 2 074 of GM make | — | — | — | 15,204 | |
| — | Breakup | for details. | — | ||
| Supplying, Installation, Testing and commissioning of Astronomical time switch of (3 output(1output per phase) and suitable for three phase supply) configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required.(DSR-2025-item no-7.4.1) | — | — | — | 11,161 | |
| — | Breakup | for details. | — | ||
| "Software for Building Management System :Supplying Installation Testing Commissioning of Necessary Software (UL listed) Packages containing Building Management with Capability of Collection, Storage, Processing and Controlling all the Data. Software shall support Open Standard Protocols like XML, BACnet, Modbus, Lon works etc. and without the use of Proprietary Protocols, with Enterprise Level Database Like MS SQL complete Lifetime Licenced & capable to collect, store & access all points from Fire Alarm Systems, IT Systems, Automation Systems, HVAC System, Lift, Energy management, Water Management System, etc. to create & monitor historical & event data, event management data, alarm management data & reporting data, Email Alerts for Critical alarms for all the systems. The scope includes additional software required by BMS software (to enable a standard Web browser) to be resident on the DDC/client machine (manufacture-specific browsers shall not be acceptable). User log-on identification and password shall be required & a minimum three-layered security system(User interface Level, Application Level and Data Base Level) to be deployed for safety. The supplied computer software shall employ objectoriented technology (OOT) for representation of all data and control devices within the system. This data shall reside on a server for all database access (Systems requiring proprietary database and user interface programs shall not be acceptable). All components and controllers supplied under this contract shall be true "peer-to-peer" communicating devices (Components or controllers requiring "polling" by a Master / Global / Host to pass data shall NOT be acceptable). Physical connection of BACnet/MOD BUS devices shall be via Ethernet at all levels. The License must be provided by default. The BMS software shall be complete in all respect to cater the following different numbers of points managed in the installation..(DSR-2025-item no-42.5)" | — | — | — | 97,377 | |
| — | Breakup | for details. | — | ||
| Supplying, Installation, Testing & Commissioning of 6 HP to 8 HP Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s), minimum two compressors (with individual separate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condenser fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 0C. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 5.4, Capacity > 40 and <70 ISEER 5.5, Capacity > 70 ISEER 5.6 for ECSBC Building) For Cooling or Heating or Both. (DSR-2025-item no- 31.1.3) | — | — | — | 11,73,032 | |
| — | Breakup | for details. | — | ||
| "Supplying, Installation, Testing and Commissioning of minimum 1.6TR capacity High wall type Indoor unit equipped with and comfort washable synthetic media prefilter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drain pan, necessary accessories etc., suitable for operation on 230 V ± 10%, 50 Hz, single phase AC supply, complete as required. The Indoor units must shut downupon receiving a singal from the BMS System/Fire Singnals. The system shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27 0C DB and 19 0C WB temperature. (Make will be same as of Outdoor) (DSR-2025-item no-31.8.5)" | — | — | — | 6,60,810 | |
| — | Breakup | for details. | — | ||
| Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : | — | — | — | 16,53,740 | |
| — | Breakup | for details. | — | ||
| Provision of Foundation/Platform for installation of LT panels/DG set. | — | — | — | 19,489.55 | |
| — | Breakup | for details. | — | ||
| Supply Installation Testing and commissioning of free-standing floor/Wall mounted dust and vermin proof panel of IP 43 rating for LT Distribution panel made out of CRCA sheet, required hardware, cleaning with 7 tank process duly painted by two coats of zinc/red oxide primer followed by Powder coated / epoxy / PU painted with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable, gland plate M.S. base channel, hinged door with locking arrangement for equipment/switchgear. The thickness of sheet shall not be less than 1.6mm up to 600mm length/ width of any compartment and be 2.0mm above 600mm. The load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartments having bolted type doors with detachable extension type structure. (only outer area on all sides shall be measured and panel to be fabricated from CPRI approved fabricator). The Panel should have bus bar of capacity 600 A tinned copper bus bar as per IS 613 ( for essential and non- essential feeders) and following switchgear. (1)Supply and installation of on-load changeover switch of 250A of Havells model no.: IHCNFE0250 or its euivalent Conforms to IS/IEC:60947-3 - 1 No's (2) Supplyandinstallationof250A4PMCCB,36KA,Microprocessor basedadjustablewithLSIGprotectioncommuncationcapable conform to IEC 60947-2orit'sequivalent with extended ROM, spreaderlinks(2sets)ofmodelno: IHQT2EF50250 of havells or its equivalent with all required accessorires complete - 1 No's (3) Supply and installation of 160A 4P MCCB,36KA, Microprocessor based adjustable with LSIG protection communcation capable conform toIEC60947-2 or it's equivalent with extended ROM, spreader links(2sets) of model no: IHQT2EF50160 of havells or its equivalent with all required accessories complete-4 Nos.(4) Supply and installation of DPX3 160 thermal magnetic based release ; Icu = 36K A; 100A 4 Pole MCCB conform to IEC 60947-2 of model no.HQT2EC50100 of Havells make or it's equired accessorires complete-4 4No's. (5) Supply and erection of LT 3 Phase Digital Multifunction energy meter with 3 lines LCD display for measuring all the parameters( Voltage/ Current/ Power/Frequency/power factor /kw/kwh/ kvar/kvarh) on existing box panel board including connections complete. - 1 No's (6) Supply and erection of LED indicator lamps on the existing box panel board - 2 Sets. The panel should conform to RDSO letter no: RDSO- EEMOLKO(GENE)/4/2026 dated 21-07-26. | — | — | — | 4,37,015 | |
| — | Breakup | for details. | — | ||
| Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.(DSR-2025-item no-5.2) | — | — | — | 76,580 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Technicalspecifications--9-26.pdf
ATTACHMENT
HVACSpecification23-236_1.pdf
ATTACHMENT
FirepreventionGuideline.pdf
ATTACHMENT
CEGETechnicalCircular07-04-2022_compressed.pdf
ATTACHMENT
ListofLikelySuppliers.pdf
ATTACHMENT
GCC_April-2022WithCorrectionSlips._compressed.pdf
ATTACHMENT
RlyBd-JPO-DiggingofCables2013-Re-Circulatedin2022-LATEST.pdf
ATTACHMENT
EarthingSpecificationMFEandOther.pdf
ATTACHMENT
RITESInspection.pdf
ATTACHMENT
NITIREPSWorks48.pdf
ATTACHMENT
UPLOADGENSPEC_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .