Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹90.4 LAdmitted-Finance OFFICE NO 101 MALAN PLAZA NEXT TO ESSAR PETROL PUMP NEAR GODAMBLE CORNER RAHATNI PIMPRI DP ROAD RAHATANI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | ₹90.4 L | L1 | Admitted-Finance |
| 2 | L2₹99.7 LAdmitted-Finance | ₹99.7 L | L2 | Admitted-Finance |
| 3 | Rejected-Technical | - | - | Rejected-Technical Valid Registration Certificate not submitted |
| 4 | Rejected-Technical | - | - | Rejected-Technical EMD not submitted |
| 5 | Rejected-Technical | - | - | Rejected-Technical EMD not submitted |
| Sl No | Description | Qty | Unit | HARIOM ENTERPRISES L2 | Niksun Electro Infra PVT LTD L1 |
|---|---|---|---|---|---|
| 1.00 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Soft/loose soil; for electric cable laying in trench size of 6000 L X 0.3 W X 0.6 mtr deep. All as specified in SSR Part-I and as directed by Engg-In-Charge. | 1,080 | CuM | 383 ₹4.1 L | 635 ₹6.9 L |
| 2.00 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Hard/ dense soil; for electric cable laying in trench size of 6000 L X 0.3 W X 0.3 mtr deep. All as specified in SSR Part-I and as directed by Engg-In-Charge. | 540 | CuM | 675 ₹3.6 L | 1,060 ₹5.7 L |
| 3.00 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Hard Rock; for electric cable laying in trench size of 6000 L X 0.3 W X 0.1 mtr deep. All as specified in SSR Part-I and as directed by Engg-In-Charge. | 180 | CuM | 2,483 ₹4.5 L | 1,670 ₹3.0 L |
| 4.00 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm. All as specified in SSR Part-I and as directed by Engg-In-Charge | 1,800 | CuM | 139 ₹2.5 L | 85 ₹1.5 L |
| 5.00 | M & L for XLPE insulated heavy duty electric cable with alluminium conductor,1100 volt grade,cross-sectional area 120 Sq MM, 3 1/2 core. All as approved and directed by Engg- in-Charge. (Sample should be got approved from Engg-In-Charge before using at site) (Make: Finolex, Havells, Polycab) | 1,000 | RM | 825 ₹8.3 L | 847 ₹8.5 L |
| 6.00 | M & L for XLPE insulated heavy duty electric cable with alluminium conductor,1100 volt grade,cross-sectional area 70 Sq MM,3 1/2 core. All as approved and directed by Engg- in-Charge. (Sample should be got approved from Engg-In-Charge before using at site) (Make: Finolex, Havells, Polycab) | 2,000 | RM | 550 ₹11 L | 574 ₹11.5 L |
| 7.00 | M & L for XLPE insulated heavy duty electric cable with alluminium conductor,1100 volt grade,cross-sectional area
50 Sq MM,3 1/2 core. All as approved and directed by Engg- in-Charge. (Sample should be got approved from Engg-In-Charge before using at site) (Make: Finolex, Havells, Polycab) | 3,400 | RM | 450 ₹15.3 L | 450 ₹15.3 L |
| 8.00 | M & L for XLPE insulated heavy duty electric cable with aluminium conductor,1100 volt grade,cross-sectional area 16 Sq MM, 4 core. All as approved and directed by Engg- in-Charge. (Sample should be got approved from Engg-In-Charge before using at site)
(Make: Finolex, Havells, Polycab) | 6,000 | RM | 225 ₹13.5 L | 244 ₹14.6 L |
| 9.00 | Supply of Modular Bricks;common burnt clay building bricks; sub-class 'A' designation 75 for laying in trench. All as specified in SSR Part-I and as directed by Engg-In-Charge.
( 1 Unit=1000 Nos.) | 46 | Unit | 12,000 ₹5.5 L | 10,000 ₹4.6 L |
| 10.00 | Supply and laying of Reinforced concrete pipes, Bore 150 mm class NP2 laid in trench complete All as specified in SSR Part-I and as directed by Engg-In-Charge. | 75 | RM | 475 ₹35,625 | 365 ₹27,375 |
Tender Value
₹79.7 L
EMD Value
₹1.4 L
Closing Date
27 Oct 2025, 12:15 pmClosed
CGM OFDR
ORDNANCE FACTORY DEHUROAD PUNE
Installation of 115 x 90 watt LED on cantilever arm over existing poles along perimeter wall and poles electrical for illumination of outer perimeter at OFDR
2025_MIL_251260_1
GM/OFDR/B/R/709/2025-26
Open Tender
Electrical Works
120 days
OFDR
Kindly refer to tender document
3 documents required · 3 mandatory
₹0
₹1.4 L
Yes
3 Jan 2026
6 Oct 2025
28 Oct 2025
6 Oct 2025
27 Oct 2025
6 Oct 2025
Amount
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Soft/loose soil; for electric cable laying in trench size of 6000 L X 0.3 W X 0.6 mtr deep. All as specified in SSR Part-I and as directed by Engg-In-Charge.
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Hard/ dense soil; for electric cable laying in trench size of 6000 L X 0.3 W X 0.3 mtr deep. All as specified in SSR Part-I and as directed by Engg-In-Charge.
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Hard Rock; for electric cable laying in trench size of 6000 L X 0.3 W X 0.1 mtr deep. All as specified in SSR Part-I and as directed by Engg-In-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm. All as specified in SSR Part-I and as directed by Engg-In-Charge
M & L for XLPE insulated heavy duty electric cable with alluminium conductor,1100 volt grade,cross-sectional area 120 Sq MM, 3 1/2 core. All as approved and directed by Engg- in-Charge. (Sample should be got approved from Engg-In-Charge before using at site) (Make: Finolex, Havells, Polycab)
M & L for XLPE insulated heavy duty electric cable with alluminium conductor,1100 volt grade,cross-sectional area 70 Sq MM,3 1/2 core. All as approved and directed by Engg- in-Charge. (Sample should be got approved from Engg-In-Charge before using at site) (Make: Finolex, Havells, Polycab)
M & L for XLPE insulated heavy duty electric cable with alluminium conductor,1100 volt grade,cross-sectional area 50 Sq MM,3 1/2 core. All as approved and directed by Engg- in-Charge. (Sample should be got approved from Engg-In-Charge before using at site) (Make: Finolex, Havells, Polycab)
M & L for XLPE insulated heavy duty electric cable with aluminium conductor,1100 volt grade,cross-sectional area 16 Sq MM, 4 core. All as approved and directed by Engg- in-Charge. (Sample should be got approved from Engg-In-Charge before using at site) (Make: Finolex, Havells, Polycab)
Supply of Modular Bricks;common burnt clay building bricks; sub-class 'A' designation 75 for laying in trench. All as specified in SSR Part-I and as directed by Engg-In-Charge. ( 1 Unit=1000 Nos.)
Supply and laying of Reinforced concrete pipes, Bore 150 mm class NP2 laid in trench complete All as specified in SSR Part-I and as directed by Engg-In-Charge.
Supply and laying of HDPE Corrugated pipe of 100 mm dia for passing cable thorugh it wherever cables crossing over nallah at various location on the route and fixing the pipe on the wall with saddle etc complete. All as approved and directed by Engg-In-Charge. (Sample should be got approved from Engg-In-Charge before using at site)
Supply and Fixing of Hot Dip galvanaised type 3 MTR arm with bracket on existing pole with suitable arragemnet for fixing of Light fitting and should have suitable arrangement for raotating the arm as and when required or for maintenance purpose alongwith required mechanically strong support to cater the load and all weather conditions including required hardware nut, bolts, washers etc complete. All as approved and directed by Engg-In-Charge. (Sample should be got approved from Engg-In-Charge before using at site)
Supply and fixing LED street light fitting 90 Watt,230 V AC outdoor type with high pressure die cast aluminum housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics should have system efficacy 90lm/w or above and LED efficacy 120lm/w complete with IP 65/66 protection complete.Suitable for pole mounting (Make: Orient,Havells,Bajaj, Crompton,Eveready) All as specified in SSR Part-I and as directed by Engg-In-Charge.
Supply, Fixing,connection and commissioning of Feeder Pillar made of MS sheet of gauge 14 minimum,SIZE 1000h X1000w X500d mm with suitable frame work, stand alone type comforming to IP 65 ( According to index of protection for enclosures of electrical equipment as per IS 2147/1962) complete with 2 coat of oil primer and 2 coat of powder coat painting of approved colour. Feeder Pillar should be of all weather proof type and easy to maintenance with internal lighting. Double shutter, with proper locking arrangement, proper insulation to live part, proper ventilation, identification for wires and distribution MCBs, Provision for Double earthing, Danger board of standard size and feeder pillar name plate as directed. Feeder pillar should be mounted on a MS frame of size not less than 1 M Height of MS Angle 45X5 mm Minimum. Indication lamps for 3 phase incoming supply should be provided on feeder Pillar. Feeder Pillar should consisting of following items and all arrangement for accomodating the same. 1) 200 Amp MCCB 3 phase, 4 pole - 1 No 2) 100 Amp MCCB 3 phase, 4pole - 1 No 3) 63 Amp MCB 3 phase, 4pole - 2 No 4) 32 Amp MCB SPN ( 2 pole) - 2 No (MCB/MCCB make : -Havells, Anchor, Legrand,L&T,Schneider) 5) 5 A swich socket combined on wooden board 6) Lamp Holder with switch control (Sample should be got approved from Engg-In-Charge before using at site)
Supply, Fixing,connection and commissioning of Feeder Pillar made of MS sheet of gauge 14 minimum,SIZE 1000h X1000w X500d mm with suitable frame work, stand alone type comforming to IP 65 ( According to index of protection for enclosures of electrical equipment as per IS 2147/1962) complete with 2 coat of oil primer and 2 coat of powder coat painting of approved colour. Feeder Pillar should be of all weather proof type and easy to maintenance with internal lighting. Double shutter, with proper locking arrangement, proper insulation to live part, proper ventilation, identification for wires and distribution MCBs, Provision for Double earthing, Danger board of standard size and feeder pillar name plate as directed. Feeder pillar should be mounted on a MS frame of size not less than 1 M Height of MS Angle 45X5 mm Minimum. Indication lamps for 3 phase incoming supply should be provided on feeder Pillar. Feeder Pillar should consisting of following items and all arrangement for accomodating the same. 1) 100 Amp MCCB 3 phase, 4pole - 1 No 2) 63 Amp MCB 3 phase, 4pole - 2 No 3) 32 Amp MCB Single phase+neutral 2 pole - 2 No 4) 5 A swich socket combined on wooden board (MCB/MCCB Make: Havells, Anchor, Legrand,L&T,Schneider) 5) 5 A swich socket combined on wooden board 6) Lamp Holder with switch control (Sample should be got approved from Engg-In-Charge before using at site)
Supply, Fixing,connection and commissioning of Feeder Pillar made of MS sheet of gauge 14 minimum,SIZE 700h X 740w X320d mm with suitable frame work, stand alone type comforming to IP 65 ( According to index of protection for enclosures of electrical equipment as per IS 2147/1962) complete with 2 coat of oil primer and 2 coat of powder coat painting of approved colour. Feeder Pillar should be of all weather proof type and easy to maintenance with internal lighting. Double shutter, with proper locking arrangement, proper insulation to live part, proper ventilation, identification for wires and distribution MCBs, Provision for Double earthing, Danger board of standard size and feeder pillar name plate as directed. Feeder pillar should be mounted on a MS frame of size not less than 1 M Height of MS Angle 45X5 mm Minimum. Indication lamps for 3 phase incoming supply should be provided on feeder Pillar. Feeder Pillar should consisting of following items and all arrangement for accomodating the same. 1) 63 Amp MCB 3 phase, 4pole - 3 No 2) 32 Amp MCB SPN (2 pole) - 2 No 3) 5 A swich socket combined on wooden board 4) Lamp Holder with switch control (MCB/MCCB make : Havells, Anchor, Legrand,L&T,Schneider) 5) 5 A swich socket combined on wooden board 6) Lamp Holder with switch control (Sample should be got approved from Engg-In-Charge before using at site)
Supply and fixing of Flange type cable gland of brass, strong grip and corrosion resistant, high compressive strength, excellent brass finish, suitable for fixing 3.5 core, Aluminium conductor armoured cable 120 Sqmm size for termination in the paenl/FP/Junction box. etc complete. All as directed by Engg-In-Charge.
Supply and fixing of Flange type cable gland of brass, strong grip and corrosion resistant, high compressive strength, excellent brass finish, suitable for fixing 3.5 core, Alluminium conductor armoured cable 70/50 Sqmm size for termination in the panel/FP/Junction box. etc complete. All as directed by Engg-In-Charge.
Supply and fixing of Flange type cable gland of brass, strong grip and corrosion resistant, high compressive strength, excellent brass finish, suitable for fixing 4 core, Alluminium conductor armoured cable 16 Sqmm size for termination in the panel/FP/Junction box. etc complete. All as directed by Engg-In-Charge.
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single pole and current carrying capacity 5 to 32 AMP, in the MCB DB/ junction box Complete with connection testing and commissioning. All as approved and directed by Engg-In-Charge. (MCB Make: Havells, Anchor, Legrand,L&T,Schneider) (Sample should be got approved before using at site.)
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated alluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed 6 Sqmm twin core cable flat type for Connection from MCB to Street light fitiing. All as specified in SSR Part-I and as directed by Engg-In-Charge. (Sample should be got approved before using at site.)
Excavating over areas exceeding 1.5 m and not exceeding 2.5m in Hard Dense Soil & getting out and returning, filling in, including spreading levelling watering and well ramming in layers not exc 25 cm etc complete. All as specified in SSR Part-I and as directed by Engg-In-Charge (Overall Size for one pit 1 X 1 X 2.5 M).
Excavating over areas not exceeding 1.5 m in Hard rock & getting out and returning, filling in, including spreading levelling watering and well ramming in layers not exc 25 cm etc complete. All as specified in SSR Part-I and as directed by Engg-In-Charge.
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth strip 25 x 4 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion. All as specified in SSR Part-I and as directed by Engg-In-Charge.
M&L for Type B2 C.C. 1:2:4 40 mm graded aggregate) in foundation, filling and mass concrete including compaction curing complete. All as specified in SSR Part-I and as directed by Engg-In-Charge.
M & L for formwork to sides of concrete foundations, sides of soffits and similar work, vertical or batter for flat finished surfaces. All as specified in SSR Part-I and as directed by Engg-In-Charge.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25x4 mm galvanised iron strip. All as approved and directed by Engg-In-Charge
S & F for Funnel size 1/2" dia, with GI perforated pipe of 1.5 m length for watering purpose with copper lugs etc complete.All as approved and directed by Engg- in-Charge
S & F for M.S. plates (plain or chequered) Fe 410-W (Gde-E-250) quality-A as per IS 1730 (PART-I) 1989 6 mm thick forming holes etc complete. (Size of plate 300mm X 300mm for one pit). All as specified in SSR Part-I and as directed by Engg-In-Charge.
Supply of M.S. rod square bars Fe 410-W (Gde-E-250) quality-A for preparation of earth pit flag. All as specified in SSR Part-I and as directed by Engg-In-Charge.
S & F for M.S. plates Fe 410-W(Gde-E-250) quality - A plain 2 mm thick black sheet for preparation of earth pit flag marker cutting into size ( 0.15 M X 0.10M for one pit) complete. All as specified in SSR Part-I and as directed by Engg-In-Charge.
Rough excavation not exceeding 1.5 M deep and getting out in Soft Loose Soil etc complete. All as Specified in SSR Part-I and as directed by Engg-In-Charge.
M & L for Cement Concrete Type 2 C2 1:3:6 (40 mm graded aggregate) in foundations, filling and mass concrete etc complete. All as Specified in SSR Part-I and as directed by Engg-In-Charge.
M & L for Hardcore of gauge not exceeding 63 mm, broken stone or boulder deposited, spread and levelled in layers not exceeding 15 Cm thock, watered and rammed to true surface. All as Specified in SSR Part-I and as directed by Engg-In-Charge.
HARIOM ENTERPRISES (BID ID -919984)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid