Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.5 CrAdmitted-Finance 245 2 RAJPUR ROAD OPPOSITE HOTEL MADHUBAN DEHRADUN | ₹2.5 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.5 CrAdmitted-Finance | ₹2.5 Cr | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Modern Electric Company L1 | SAINKO SYSTEMS L2 |
|---|---|---|---|---|---|
| 1.00Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. | |||||
| 2.00 | Group A | 1,039 | Point | 1,223 ₹12.7 L | 1,230 ₹12.8 L |
| 3.00Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. | |||||
| 4.00 | Group A | 445 | Point | 764 ₹3.4 L | 800 ₹3.6 L |
| 5.00 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. | 30 | Point | 1,947 ₹58,410 | 1,950 ₹58,500 |
| 6.00 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. | 10,098 | Mtr | 426 ₹43.0 L | 450 ₹45.4 L |
| 7.00Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. | |||||
| 8.00 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. | 6,095 | Metre | 363 ₹22.1 L | 370 ₹22.6 L |
| 9.00 | 2 x 6 sq.mm. + 1 x 6 sq.mm. Earth wire | 3,600 | Metre | 579 ₹20.8 L | 580 ₹20.9 L |
| 10.00 | 2 x 10 sq.mm. + 1 x 6 sq.mm. Earth wire | 1,650 | Metre | 698 ₹11.5 L | 700 ₹11.6 L |
Tender Value
₹2.5 Cr
EMD Value
₹5.0 L
Closing Date
1 Jan 2026, 3:00 pmClosed
GM CIVIL BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
Electrification and Allied works at Residence Quarter in DJ Dehradun
2025_BRID3_90088_1
2677/BRIDCUL/1019/25 Dated 17.12.2025
Open Tender
Miscellaneous Services
450 days
Dehradun
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹5.0 L
BRIDCUL Dehradun
28 Jan 2026
18 Dec 2025
1 Jan 2026
18 Dec 2025
1 Jan 2026
27 Dec 2025
26 Dec 2025
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group A
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group A
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire.
2 x 6 sq.mm. + 1 x 6 sq.mm. Earth wire
2 x 10 sq.mm. + 1 x 6 sq.mm. Earth wire
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
Supplying and fixing brass batten/ angle holder including connection etc. as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as Required.
Single pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following way, Single Pole and Neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).
8 Way Double door.
12 Way Double door.
16 Way Double door.
Supplying and fixing following Rating, Double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as Required.
Supplying and Fixing Following Size/ Modules, GI Box Alongwith Modular Base & Cover Plate for Modular Switches in Recess etc. as Required.
1 or 2 Module (75 mm x 75 mm)
Supplying and Fixing Following Modular Switch/ Socket on The Existing Modular plate & Switch Box including connections But Excluding Modular Plate etc. as required.
Telephone Socket outlet.
TV Antenna socket outlet.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, Unarmored Telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
Supply of Bracket Light fitting suitable for 15-20 Watt LED Light with all accessories as required.
Supply of 9W LED BULB with all accessories as required.
Supply of Surface Mounted Energy Efficient, LED Luminaires 12W LED DOWN LIGHT Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc.as required.
Supply of LED Luminaires BATTEN 20W LED Tube Light of Box Type Prewired Indoor Luminaire with Energy Efficient Electronic Ballast, with End Caps Complete as Required.
Supply of Bulk Head Luminaire, heat resistant Glass cover . suitable for 10W to 15W LED or Equivalent.
Supply of Surface Mounted Energy Efficient, LED Luminaires 18W LED DOWN LIGHT (Round) Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc.as required.
Supply, of Linear & Compact 10W Mirror Light with Decorative Grey Caps, Polycarbonate Body & Ribbed Opal Diffuser.
Supply of Following sweep exhaust fan with guard suitable operation on single phase 230 V, 50Hz. AC Supply, with lowers / shutters in the existing opening.
300 mm Sweep 900 rpm
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Installation, testing and commissioning of pre-wired, fluorescent fitting /compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as Required.
Installation of Exhaust fan in the existing opening, including making good the damage, Connection, Testing, Commissioning etc. as Required.
Upto 450 mm sweep
Fixing Louvers / Shutters for Exhaust Fan:
Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes.
Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing
MAIN DISTRIBUTION PANE/ CUM METER BOARD PANEL - TYPE II BLOCK (32 UNITS)
Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
INCOMER : 320 AMP FP MCCB
BUS BAR : 400 AMP, 415 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature.
OUT GOINGS :
32 No 40AMP DP MCB & Space For 32 No 1 Phase KWH Meter with Indication Lamps (Flat DB's)
1 No 100AMP FP MCCB (Common Services Panel)
1 No 100AMP FP MCCB (Spare)
2 No 40 AMP DP MCB (Spare)
complete panel as above and complete
MAIN DISTRIBUTION PANE/ CUM METER BOARD PANEL - TYPE II BLOCK (28 UNITS)
Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
INCOMER : 320 AMP FP MCCB
BUS BAR : 400 AMP, 415 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature.
OUT GOINGS :
28 No 40AMP DP MCB & Space For 28 No 1 Phase KWH Meter with Indication Lamps (Flat DB's)
1 No 100AMP FP MCCB (Common Services Panel)
1 No 100AMP FP MCCB (Spare)
2 No 40 AMP DP MCB (Spare)
complete panel as above and complete
COMMON SERVICES PANEL TYPE II BLOCK (28 and 32 UNIT)
Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
INCOMER : 100 AMP FP MCCB WITH 100A ATS SWITCH (as per SLD)
BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature.
OUT GOINGS :
1 No 40AMP DP MCB & Space For 1 No 1 Phase KWH Meter with Indication Lamps (Common area DB)
1 No 63 AMP 4P MCB with Indication Lamps (Lift)
1 No 40 AMP DP MCB with Indication Lamps (Machine Room DB)
1 No 63 AMP 4P MCB (Spare)
2 No 40 AMP DP MCB (Spare)
complete panel as above and complete
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.
3.5 C X 185 Sq.mm Al. XLPE arm.
3.5 C X 150 Sq.mm Al. XLPE arm.
3.5 C X 25 Sq.mm Al. XLPE arm.
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required.
upto 35 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.
3½ X 185 sq. mm (57mm)
3½ X 150 sq. mm (50mm)
3½ X 25 sq. mm (28mm)
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
SITC of CO2 Fire Extinguishers 4.5 kg capacity complete in all respect ISI : 15683 marked. As per Safety plus extinguisher fire carbondioxide 4.5kg, duly charged, portable and complete as per defence specification (safetyplus SPE C 4.5)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Providing and fixing of lightning conductor finial, made of 25mm dia 300mm long, G.I tube, having single prong at top with 85mm dia 6mm thick G.I base plate including holes etc. complete as required.
Providing and fixing G.I tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (for horizontal run)
Providing and fixing G.I tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (for vertical run)
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
SITC of 58.5 KVA CPCB-IV+ Silent D/G Set Comprising of Engine 75.5BHP/ Water Cooled, 1500RPM coupled with 58.5 KVA 3 phase alternator, Turbo charged, A1 class governing, 4 cylinders complete with all accessories including Base Frame, Fuel Tank, battery with leads, Sound Proof Canopy & AMF Control Panel.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.38 MB
sbdelectricalalliedworkdjddnf.pdf
Tender Documents • 1.83 MB
BOQ_106752.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid