Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹6.4 LAccepted-AOC 0 PARNERA DHODIA WAD PARNERA VALSAD GUJARAT 396001 UDYAM GJ 25 0047109 | VALSAD | GUJARAT | 396001 | L-1 | Accepted-AOC AOC | |
| 2 | L-2₹7.9 L+₹1.4 L (22.6%)Rejected-Finance HOUSE NO1201 NEAR HANUMAN MANDIR AT POST SHEL PIMPALGAON TAL KHED DIST PUNE PIN 410 501 | PALGHAR | MAHARASHTRA | 410501 | L-2 | Rejected-Finance Other than lowest bidder | |
| 3 | L-3₹10.0 L+₹3.6 L (56.4%)Rejected-Finance T 1 GARDEN VIEW APARTMENT NEW BANKER COLONY MUNDRA ROAD BHUJ KUTCH 370001 GUJARAT | KACHCHH | GUJARAT | 370001 | L-3 | Rejected-Finance Other than lowest bidder | |
| 4 | L-4₹13.4 L+₹7.0 L (109.7%)Rejected-Finance HOUSE NO 120 1 NEAR HANUMAN MANDIR AT POST SHEL PIMPALGAON TAL KHED DIST PUNE PIN 411014 | PUNE | MAHARASHTRA | 411014 | L-4 | Rejected-Finance Other than lowest bidder |
Tender Value
₹7 L
EMD Value
₹14,000
Closing Date
7 Feb 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) Naliya No. 1
GE AIR FORCE STATION NALIYA NO 01
REPAIR RENEWAL OF CERTAIN EM AND BR ITEMS AND ASSOCIATED WORK INSIDE TECHNICAL AREA AT AF STN NALIYA
2024_MES_636710_1
8953/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Naliya
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (AF) Naliya No. 1
₹14,000
Yes
15 Mar 2024
10 Jan 2024
9 Feb 2024
10 Jan 2024
7 Feb 2024
24 Jan 2024
Amount
M & L in replacement of earthing complete with galvanised steel earth plate electode 600 x 600 x 6 mm thick buried directly in ground earth pit with adequate quantity of charcoal and dust and common salt , not less than 2.25 mtr deep below ground level connected to & including galvanised earth lead wire 4 mm dia drawn through GI protection pipe of size ordered specified for protection of earthing lead from earth electrode to test point/main DB from mechanical injury or tempering by means of nuts and bolt check nuts and washers of galvanised iron sheet all as shown in electrical plate No 3 of SSR Part - I and connected to earthing test point complete including testing, refilling earth and removal of surplus soil upto 50 mtrs, PCC 1:3:6 type CI chamber precast RCC cover 40 mm thick reinforced with 6 mm dia MS bar 3 Nos both way with handle made out of 6 mm dia MS bar water pipe with wire mesh and connecting testing etc complete all as specified and directed.
M & L in replacement of earthing complete with copper plate electrode 600 x 600 x 3.15 mm thick burried directly in ground earth pit not less than 2.25 mtr deep below ground level connected to & inclduing copper strip 20x3 mm by means of nuts and bolt check nuts and washers and also brazing strip with plate, passing through protection pipe of 25 mm dia light grade GI pipe all as shown in electrical plate Nos 3 of SSR Part-I, and connected to earthing test point complete inclduing testing filling of adquate quantity of charcoal dust and common salt inclduing refilling earth and removal of surplus soil upto 50 mtrs apart and PCC 1:3:6 type C1 chamber precast RCC cover 40mm thick nrinforces with 6 mm dia MS bar 3 Nos both way with handle made out of 20 mm dia MS base water pipe with wire mesh, funnel etc and connecting testing etc complete all as specified and directed.
Supply and fix in repair Air termination, single point copper rod 12 mm dia and 300 mm long complete all as specified and directed.
S&F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw all as specified and directed.
Supply and fixing Copper strip 20 x 3.15 mm fixed with saddles, insulators and screws etc for roof conductor and down conductor above ground, including breazing at joints complete all as directed.
Fixing in repair Copper strip 20 x 3.15 mm fixed with saddles, insulators and screws etc for roof conductor and down conductor above ground, including breazing at joints complete all as directed.
Demolition of existing damaged valve pits and provn of new earth pit chamber of size 30cmx30cmx30cm constructed in PCC (1:2:4) type B1 using 20mm graded aggregate including cast iron frame with hinged pit cover of size 12"x12" having 7 kg weight all as per electrical plate No.3 and as directed.
Supply & fix GI pipe of size 25 mm 1.5 RM long Light grade vertically fixed by means of PCC 1:2:4 of size 2x2x1.5 Cubic Feet for mounting of Copper air termination rod including fabrication work for mounting insulators on GI Pipe all as directed
Supply and fix in repair Copper strip 32x6 mm fixed with saddles, insulators and screws etc for roof conductor and down conductor above ground, including breazing at joints complete all as directed.
Supply & Fix earthing strip insulators made of any material as PVC/Fiber/porcelain including nut and bolt suitable for fixing / support of copper/GI strip of size upto 32x6 mm complete all as specified and as directed.
Supply & Fix in Replacement Temperature and Humidity Multi Detector with below mentioned specifications : Measurement Range - 0-100% RH Output - 4-20 mA (two wire) Accuracy at 25 °C - ± 1.3% RH of Operating humidity span Hysteresis Repeatability - ± 0.6% RH Stability - ± 1% RH typical at 50% RH in 5 years Sensor - Capacitive Sensor Sensor Response Time - 15 sec in slowly moving air at 25 °C. Make: Radix / any ISI marked.
Supply and Fix in Replacement Signal converter 2 wire RS485 to RS232 converter for communication. Make: Electrocom / any ISI marked. .
Supply and lay 2 core 1.5 Sq mm unshethed flexible copper Cable with voltage grade upto for signal transmission from panel of AC2 building to Chiller plant operator room. Make: Polycab / Havells / Kei/ Finolex / Gloster / any approved make
Supply and Fix in Replacement SMPS 230V AC to 12/5V DC for power supply of Central processing unit card of Remote terminal unit panel located at AC2 building Make: Psynox / any ISI marked
Supply & fix in replacement Process Controller cum Indicator for display of temperature and humidity data Make: Radix / any ISI marked
M & L for removing old paint by paint removerrs or burning off by blow lamps and cleaning with scrapers, any number of coats, any width of girth from the existing suction/delivery pipe line including headers of any size complete all as specified and directed.
M & L for painting to existing surface by using spray gun with one coat of red oxide and two coats of synthetic enamel paint on existing suction suction/delivery pipe lines, inculding Headers of any size, cooling tower parts etc using Blue/Red/Black colour as per site requirement of first quality, all as specified and directed. Make : Berger / Asian / Nerolac / any approved make
S&F in replacement 80 / 100 mm dia butterfly valve of AC chillier plant circulation pipe line, of existing model, welding the same as per existing fixing arrangements complete all as specified and as directed.
M & L in repair of brazing only to the existing copper strip joint of any size including cost of equipment and material use for brazing all as directed.
S & F in replacement of 40 TR capacity Cooling Tower PVC filings along with sprinkler set, tension bar GI material,turn buckle, branch pipe of suitable size(approx 50 mm dia) and FRP eliminator blades for each cooling tower all as directed.
Supply & Fix in repair re-winding of 3 phase existing rooftop siren for auto/Manual operation. This includes repairs, installation and testing of siren on site complete all as specified and as directed.
M/s. AMIT ASSOCIATES
Venus Engineering
NILESH SUBHASH KARALE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .